For the Accu-Time CS2100 and Accu-Time CSS110

Page 22

Chapter 2

General Installation Guidelines

Installation

The Cyber Series time and data collection terminal is a durable industrial-grade device that can endure harsh environments, but environmental constraints exist and care should be taken when selecting a location for installing and operating the Cyber Series terminal. ATS recommends the Cyber Series terminal operate in an ambient temperature range of between 32° and 110° Fahrenheit. Non-condensing relative humidity should be less than 95%. The terminal should be mounted on a vibration-free surface. The standard Cyber Series terminal is designed to operate indoors. Exposure to outdoor elements such as rain or snow will void the manufacturer warranty and may cause damage to the device. If your application requires outdoor installation, Accu-Time Systems offers a NEMA 4X certified terminal. Select a location with adequate lighting and accessibility so employees can operate the terminal safely. After you have installed the terminal in its location and run the wiring to the host computer, refer to Chapter 3, Setup, Test, Diagnostics, and Maintenance, for information about configuring and testing the terminal.

Cyber Series Time and Attendance Terminals

2-1

Page 23

Installation

Installation

Basic Requirements

Cyber Series terminals are available in three enclosure styles: locking base mount, gullwing flange mount, and NEMA 4X flange mount. Each type has similar wiring and location requirements.

Locate a flat wall surface on which to mount the Cyber Series terminal. A convenient mounting height for most Cyber Series terminals is 48 inches from the floor to the terminal display. The CSxG finger geometry terminals should be mounted slightly lower. ATS recommends mounting a CSxG back plate so that its “keyhole” mounting screw slots are approximately 44 1/4” above the floor. These heights are compliant with the Americans with Disabilities Act. Observe OSHA and local safety codes when operating tools during all phases of the installation. Be sure the distance from the terminal’s location to the host computer does not exceed the wire length limitation of the connection type you plan to use. These limits are shown in Table 2-1.

Connection Type

Maximum Terminal-to-Host Distance

RS232

50 wire-feet

RS485

Combined terminal/host drop points should not exceed 5,000 wire-feet.

Ethernet 10/100BASE-T

328 wire-feet (100 meters) from terminal to Ethernet hub or switch

Installing Power Wiring

A Cyber Series terminal requires 12VDC power for operation. In a typical installation, this power is supplied by plugging the output cable from an ATS 12VDC power pack directly into the back of the terminal. Ensure that a conventional 120VAC wall outlet (220VAC in Europe and other areas, check local electrical code requirements) is available to accept the power pack assembly. The outlet should be within 4 feet of the terminal’s location.

Installing Data Wiring

The Cyber Series terminal can communicate using three types of data connection: RS232, RS485, and Ethernet. Each requires a different cable type with different requirements, as described in the sections below. Figure 2-5 gives the RS485 and RS232 pinouts used by Accu-Time Systems terminals.

RS232 Cable Installation

When using an RS232 connection, the Cyber Series terminal must be no more than 50 wire-feet from the host computer. EIA standards for RS232 protocol data transmission dictate this cable distance. Exceeding this requirement greatly increases the chances for transmission error and excessive data re-transmission.

Cyber Series Time and Attendance Terminals

2-2

Introduction

Table 2-1: Wire Length Limitations

Page 24

Installation

For RS232 applications, ATS recommends using its modular telephone type data cable. This eight conductor shielded flat cable has RJ45 modular plugs on each end. The 50-foot cable can run along side base moldings, walls, overheads, or in hostile environments through conduit tubing. Terminate one end of the cable at the Cyber Series terminal’s communication port and the other end at the host computer’s serial port through an ATS RS232 Communication Adapter. Be sure to select RS232 protocol when you set up the terminal’s COMM port (see Setting the COMM Port on page 3-11). Figure 2-1: Sample RS232 Installation

12 VDC POWER SUPPLY

ATS

Cyber Series

LOW

INVALID

VALID

POWER

1

2

3

F1

F5

4

5

6

F2

F6

7

8

9

F3

F7

CLEAR

0

ENTER

F4

F8

1 2 3 4 5 6 7 8

Earth Ground Receive Transmit N/C N/C Ground +VDC Ground

NOTE: Pinouts are referenced to the terminal

COMM ADAPTER DB25-RJ45 W/PWR

Modem Installation

You can also establish a serial connection using a modem. Figure 2-2 shows the inside of a typical Cyber Series base plate with a modem card installed. (Modem cards in older terminals may look slightly different.) Figure 2-6 on page 2-12 shows the location of the modem board in a Cyber Series finger geometry terminal. If you have the modem option, be sure the short jumper cable from the modem is plugged into the serial jack in the back of the terminal (see Figure 2-5 on page 2-11 or Figure 2-6). Plug a standard RJ11 modular phone cable into the other jack on the modem card and into an analog telephone wall jack. The modem does not support digital telephone lines. You will need to configure the modem using the terminal setup commands described in Chapter 3, Setup, Test, Diagnostics, and Maintenance.

Cyber Series Time and Attendance Terminals

2-3

Introduction

TO HOST

Page 25

Installation

Figure 2-2: Cyber Series Modem Connections

To Serial jack on terminal

Introduction

To analog telephone jack

Cyber Series Time and Attendance Terminals

2-4

Page 26

Installation

When using an RS485 connection, the total cable length of the combined RS485 terminal/host drop points should not exceed 5,000 wire-feet. EIA standards for RS485 protocol data transmission dictate this cable distance. Exceeding this requirement greatly increases the chances for continual data re-transmission, which may never be acknowledged. For RS485 communication applications, ATS recommends using a network trunk cable that adheres to the following specifications: • Five conductor shielded 24-gage wire with a drain. • The impedance of the cable should be 100 ohms. • The capacitance should be 12 pico-farads per foot. • The jacket of the cable is typically PVC or plenum material. The short drops from a RS485 hub to the individual terminals can be ATS modular cable, as shown in Figure 2-3 on page 2-6. NOTE: If the host computer is not equipped with an RS485 communication port, you can use an ATS RS232/485 converter with 12 volt power pack assembly to convert the terminal communication lines to host RS232 levels. The host output of the RS232/485 converter plugs directly into the ATS RS232 Communication Adapter. Using an RS485 connection lets the Cyber Series terminal be used in multi-dropped networks. Thirty-two terminals can be supported on a single host communication port. ATS Series 1000 network controllers support up to 256 terminals on a single host communication port. Be sure to select RS485 protocol when you set up the terminal’s COMM port (see Setting the COMM Port on page 3-11).

Cyber Series Time and Attendance Terminals

2-5

Introduction

RS485 Installation

Page 27

Installation

Figure 2-3: Sample RS485 Installation RS232 to RS485 Converter

Host

Pgnd N/C Pgnd Net DI+ Net DONet DO+ Net DIEgnd

1

1 2 3 4 5 6 7 8

2

E.GND

1

Comm Adapter DB25-RJ45 W/PWR

3

4

5

3

4

7

8

P.GND +VDC P.GND

COMM

2

6

5

E.GND

6

7

8

P.GND+VDC P.GND

COMM

Network Continued 1

2

3

4

6

5

7

8

TO HOST 12 VDC POWER SUPPLY

E.GND

P.GND+VDC P.GND COMM DC POWER

Pin # 1 2 3 4 5 6 7 8

Description Earth Ground DI DO + DO DI + Ground +VDC Ground

JP2

JP1

NC

JP3

DROP 1

JP4 NC

NO

DROP 2

DROP 3

DROP 4

NO

E.GND

12 VDC POWER SUPPLY

Ethernet Installation

12 VDC POWER SUPPLY

When using an Ethernet connection, the Cyber Series terminal can be located at any point in a TCP/IP Ethernet 10/100BASE-T network, providing the single segment length from the network hub or switch to the terminal does not exceed 328 wire-feet. A typical topology for the Cyber Series terminal in an Ethernet 10/100BASE-T network is a star configuration. For Ethernet communication applications, ATS recommends using CAT-5 unshielded twisted-pair high-speed data transmission cable with RJ45 plugs wired according to the EIA/TIA 568B standard. One end of the RJ45-terminated cable plugs into the Cyber Series terminal’s Ethernet communication port, while the other end plugs into the network hub. ATS follows the IEEE 802.3 Ethernet standard.

Cyber Series Time and Attendance Terminals

2-6

Introduction

NOTE: Pinouts are referenced to the terminal

Page 28

Installation

Refer to Figure 2-5 or Figure 2-6 to find the location of the Ethernet jack on the back of your Cyber Series terminal. Early Cyber Series terminals had a separate Ethernet interface card, as shown in the top drawing of Figure 2-5. This is known as the twoboard design. Later Cyber Series terminals have the Ethernet interface built into the terminal’s main board, shown in the lower drawing of Figure 2-5 and in Figure 2-6. Functionality is the same for both designs, but the location of the Ethernet jack is different. Figure 2-4: Sample Ethernet Installation

System Network Cable

Hub POWER SUPPLY

Ethernet Hub

ATS 12VDC POWER SUPPLY

ATS 12VDC POWER SUPPLY

ATS ATS

Cyber Series

Cyber Series LOW

LOW

INVALID

VALID

Connecting a Printer

2

3

F1

F5

4

5

6

F2

F6

7

8

9

CLEAR

0

ENTER

F3 F4

VALID

POWER

POWER

1

INVALID

1

2

3

F1

F5

4

5

6

F2

F6

7

8

9

F3

F7

CLEAR

0

ENTER

F4

F8

F7 F8

If you have an optional printer, you will need to connect it to the terminal. This can be done in two ways: • Through the serial COMM port. Use this connector when the terminal is equipped with a biometric finger scanner or a relay. If you use this connector, the terminal can communicate with the host only through an Ethernet connection. • Through the AUX1 (DIDO) port. Use this connector unless the terminal has a biometric finger scanner or relay. This will let you use either serial or Ethernet communication with the host. The pinouts are different for each connector. Consult the factory if you need assistance.

Cyber Series Terminal

2-7

Page 29

Installation

Be sure you select the printer option for the COMM or AUX1 port during terminal setup, as described in Setting the COMM Port on page 3-11 or Setting the AUX1 Port on page 3-12. You should set the printer baud rate to 9600 baud. (Look for a DIP switch setting on the printer.)

Introduction

To print to the printer, refer to the description of the LPT command in the UCS manual.

Cyber Series Time and Attendance Terminals

2-8