The text of a manual · part 3 of 8
Technical Description: Proximity Laser Scanner PLS, pages 21 to 30
Pages 21 to 30 of 78
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Sick PLS101
Page 21
Calculation of the necessary protective field When configuring the protective field for vehicle applications, in addition to the actual stopping distance of the vehicle the following supplements must also be taken into account: For the protective field length SL: SL = SA + ZM + ZR + ZE + ZF + ZB where: SA is the stopping distance of the vehicle ZM is the supplement for the general measuring error of the vehicle; ZR is the supplement for any reflection-related measuring error of the PLS; ZE is the supplement for the measuring error of the PLS resulting from teach-in (see Important notes on configuration for mobile protection); ZF is the supplement for a lack of ground clearance of the vehicle; ZB is the supplement for the decreasing brake force of the vehicle. The stopping distance SA is composed of the actual braking distance of the vehicle from maximum speed and the maximum load SBr, as well as its distance covered during the response time of the sensor SAns. SA = SBr + SAns where SA is given in the specification of the vehicle manufacturer, and SAns = TAns x Vmax. The response time of the sensor TAns set when the PLS is shipped is 80 ms. The supplement ZM results from the maximum measuring distance of the PLS. For measuring distances up to 2 metres the maximum measuring error is 9.4 cm; for measuring distances above 2 metres the error is 13.1 cm. The maximum protective field length SLmax results from the maximum distance of the edge of the protective field from the centre of the PLS (see Important notes on configuration for mobile protection). The supplement ZR is necessary when there are objects with retroreflective properties on the scanning plane. lf the presence of retroreflectors cannot be excluded, for protective field lengths above 250 cm a supplement of 10 cm is required (see important notes on configuration for mobile protection). The supplement ZE is necessary when you define the protective field using the teach-in method. This supplement takes account of the accuracy in registering the ambient contour. This supplement is independent of background conditions, and needs to be set at a constant 45 mm. The supplement ZF is necessary because people are generally detected above foot level, and so the braking action is unable to take account of the length of the foot in front of the point of detection. A person could therefore suffer injuries to the foot as a result of a lack of ground clearance.
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
21
08.07.2004, 15:54
21
Page 22
The adjacent diagram shows the necessary extension of the protective field based an the supplement necessary for the lack of ground clearance of a vehicle.
Vehicle
The supplement for the declining braking force of the vehicle must be set at 10% of the stopping distance, unless already taken into account in the stopping distance.
Protective field width
Ground clearance BF
As ZM for the protective field width – like ZM for the protective field length - results from the maximum protective field length SLmax, those supplements are always identical.
BF
The protective field width SB also requires a supplement. Here the supplement ZM for the general measuring error of the PLS is applied (as necessary ZR and ZE)
ZF
120
60 50 0
50
100 150 Supplement Z F
Supplement on protective field A resulting from lack of ground clearance Configuration examples Notes: In the user software always enter whole values in centimetres. For this, the results of all calculations must be rounded up to the next centimetre. The stopping distance s is the stopping distance required by the vehicle (including the sensor response time) from maximum speed.
22
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
22
08.07.2004, 15:54
Page 23
5.3 If you use several PLS units The PLS is designed so that mutual interference by sensors where more than one is deployed is highly unlikely. To be absolutely sure to of avoiding error shutdowns, you should mount the sensors offset to one another.
In any event, be sure to observe the stipulations of EN 999. There are three different mounting kits which enable you to align the sensors at various angles. You can find diagrams illustrating all the mounting kits together with more detailed information in the chapter headed “Mounting the PLS”.
PLS1
PLS2 min 10
P LS 1
0 mm
P LS 2 min 20
0 mm
PLS1 min. 200 mm
PLS2
PLS 2
PLS 1 min 1 00 mm min. 2 m
PLS1 min. 200 mm
PLS2
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
23
08.07.2004, 15:54
23
Page 24
6
Supply Package
You receive: – one PLS sensor – one connection set (one connection box each for power supply and interface) – the PLS user software (on three 3.5" floppy discs) – the operating instructions manual – this technical description manual
Recommended accessories At this point we can only give you a few pointers to the major accessories. You can find a complete list in the Appendix. Connection set You will normally receive connection set 1. It contains one connection box each for the power supply and the interface, without cables. If you wish, instead of connection set 1 you can order one of the connection sets 2 to 7, which include a cable fitted to the power connector. The cable is routed upward out of the connection box. Various cable lengths are available: Order no. Connection set 1, without cable
2 016 184
Connection set 2, with 3 m cable
2 016 185
Connection set 3, with 5 m cable
2 016 186
Connection set 4, with 10 m cable
2 016 187
Connection set 5, with 15 m cable
2 016 188
Connection set 6, with 20 m cable
2 016 189
Connection set 7, with 30 m cable
2 016 190
Interface cable To connect the sensor to a PC you can use the interface cable. It is available in three lengths. For RS 232: Order no. 3 m interface cable
2 016 401
5 m interface cable
2 016 402
10 m interface cable
2 016 403
For RS 422: Order no.
24
3 m interface cable
2 019 130
5 m interface cable
2 019 131
10 m interface cable
2 019 132
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
24
08.07.2004, 15:54
Page 25
7
Mounting the PLS
You can mount the PLS without auxiliary fittings directly on a wall or on the floor. Threaded holes are provided for this on the bottom and on the back of the PLS. Note: Mount the PLS so it is protected against damp, dirt and damage. Ensure that the area visible to the entire front screen is not restricted by refitting measures. Also avoid excessive shock and vibration impact on the scanner. Please observe the relevant specifications set out in the Appendix under “Technical Data”.
13,5
20,5
9,1
210
185
136,8
23,5
63
53,2
38
31,7
50
120
78,5
M8x9
Space allowed for connection approx. 265
M6x8
77,5
69,5
155
18,5
156
45
59
118
55
M6x8 21
12
(All dimensions in mm)
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
25
08.07.2004, 15:54
25
Page 26
There are three mounting kits which allow the PLS to be fineadjusted and then securely fixed in position. Mounting kit 1 is attached directly to the back of the PLS, and is for wall mounting. The contact areas on the PLS and an mounting kit 1 are so precise that you can replace the PLS at any time without realigning if this becomes necessary. Mounting kit 2 is attached as an add-on to mounting kit 1, and permits fine adjustment of the PLS in two planes (see arrows in the illustration). The medium adjustment angle is ± 11°. Mounting kit 3 (only in conjunction with mounting kits 1 and 2) can be used either for stable floor mounting of the PLS or, on uneven wall surfaces, ensures that the transverse axis on mounting kit 2 remains precisely adjustable. The maximum adjustment angle is ± 3.3°. Dimensional drawings for all mounting kits are set out on the next page. Note: Where systems are subject to heavy vibration, you should prevent the adjusting and fixing screws from working loose by using suitable locking mechanisms, and regularly check that the screws are tight.
Sensor mounting screws
Sensor mounting screws
26
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
26
08.07.2004, 15:54
Page 27
Notes: The scanning plane is 63 mm above the bottom edge. When a PLS is mounted using mounting kits 1, 2 and 3, the scanning plane (with horizontal alignment) is 102.5 mm above the bottom edge of mounting kit 3.
.5 46 .5 31
193.2 175 120 ø9
.5 16
22.5
87.5
51.8 102
30
DIN74 Am 6
183
106.1 160 220
71
ø9 ø9
67
80
46 30
60
71
(All dimensions in mm)
32,5
102 71
51,5
66,6
30
9
51,8
ø9
247,77
For counter-sunk screws M6 DIN 74 - Am6
19,1
17,5
120
193,2 87,5
22,5
175
(All dimensions in mm)
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
27
08.07.2004, 15:54
27
Page 28
8
Connecting up the PLS
The PLS is supplied with two plug-in connection boxes for the power supply and interface. The electrical contact in each case is made by a 9-pin sub-D connector screwed into the connection box.
Connection box with interface connector (X2.) Connection box with power supply connector (X1.)
Only when both connection boxes, with their seals under them, are inserted flush with the housing and fixed with the side fixing screws does the PLS conform to protection class IP65. If the interface is not used, the connection box fitted with dummy plugs must be used.
Cable connection can be routed either upward or to the rear
You can order pre-assembled connection sets in which the power connector is fitted with an upward-routed cable. You can find more details about the available connection sets in the Appendix under “Accessories”. If you assemble the connection yourself, you can choose whether the connecting cable is routed out of the connector housing upward or to the rear. The unused threaded hole in either case must be plugged with a dummy plug. Notes: Lay all wires and connecting cables so that they are protected against damage. lf you are using the PLS to protect hazardous areas: make sure that the connected controller and all other devices also have the necessary safety level. Make sure the connection boxes for the power supply and the interface are not mixed up when assembling the cable sets. Do not drop the connection boxes with the connectors. The sub-D connector could be pushed into the housing as a result.
• •
•
28
Check that the seals sit firmly on the connection boxes.
Connecting up the PLS
Insert the connectors right-side up into the receptacles in the PLS housing. Push the connectors lightly into the PLS housing. You will know that a proper connection has been made if the connectors terminate flush on the housing. Only then should you secure the connection boxes with the hexagon socket screws on the sides.
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
28
08.07.2004, 15:54
Page 29
Connecting the power connector The PLS requires a DC voltage of 24 V for its power supply. You can find more information about this in the Appendix under “Technical Data”. The power connector must have the following terminals: – VCC_EXT and GND_EXT: a 24 V DC power pack to deliver the power – RESTART: The restart button to release the PLS after a protective field infringement – OSSD1 and OSSD2: the two protective semiconductor outputs which safely activate when the protective field is infringed – WEAK SIGNAL: An additional output which activates optionally in case of dirt contamination of the front screen or infringement of the warning field, or both. If the PLS detects an error in its routine self-test, the output activates 4 times per second (see Chapter 10: “LEDs on the PLS”) Note: Each safety output (OSSD) may only be connected to one switching element. If more than one switching element is required, a suitable contact multiplier must be provided. lf you connect loads such as lamps directly to the semiconductor outputs, you must pay attention to the following points: – As a result of the initial resistance of a load (such as a lamp) the maximum possible current rating of the outputs must not be exceeded otherwise the outputs' current limiter will be activated. – The loads must exhibit low-pass behaviour (fg < 500 Hz) so that the test pulses monitoring the output do not cause a shutdown. – The maximum capacitive load is 100 nF. This must be observed particularly when using downstream safety modules.
"
#
"
#
- $
%
,) ' ()*+ !
! !
- $
%
-
"
#
- $
%
0
! ' ! ! ! ! ! !
Power connector for PLS type 101-312
Pin no.
Signal designation
Wire colours
1 2 3 4 5
GND_EXT (ground) RESET/RESTART VOC_EXT (DC 24 V) NC WEAK-SIGNAL (contamination signal or warning field infringed) NC NC OSSD_2 (protective output 2) OSSD_1 (protective output 1)
brown blue red – grey
6 7 8 9
– – turquoise orange
Power connector: wire colours
Connection examples You need to connect the power connector pins differently depending on the application. The following pages give examples of various applications. If you want to use one or more PLS together with an LSI (Laser Scanner Interface), then the safety outputs (OSSD) of the PLS may not be used.
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
29
08.07.2004, 15:54
29
Page 30
+24V
1) X1.
x y
3
PLS 8 k1 k2 x
9 y z k1
5 1 k2 X2.
Y36 S12
S52 z
A1 13 23 33 41 pilz PNOZ8 Y1 Y2 A2S21 S22 14 24 34 42 k1 k2
H2
K1
K2
0V
PNOZ 8 / Without restart inhibit, with contact monitoring
+24V
1)
k1 k2 x k1 y k2 x
3)
y z
A1 A2 PE To PE T13T14X1 1X12 T21 T22X21X22 13 23 31 k1
LCU-X k2
C1 D1 PE C2 D2 PE T3 T4 C3 D3 PE C4 D4 14 24 32 z
X1. 3
PLS 8 9 5 1
X2.
K1
K2
0V PE
LCU-X / Protective operation without restart inhibit, with contact monitoring
30
8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved
PLS_TB_GB_06_05_02_M844.pmd
30
08.07.2004, 15:54