Page 11

5

Location Planning

The PLS monitors hazardous areas and protects operating personnel and plants. To enable it to fulfil these tasks, you need to observe a number of rules and safety criteria when choosing its location. The key information with regard to this is presented on the following pages. Note: It may be that other standards and regulations not cited here are also of importance to your application. If you are uncertain about your application, please contact your local SICK office. Always choose a location – which provides the maximum safety in the hazardous area, – in which no obstacles can obstruct the field of vision of the PLS or cause umber shadows, – in which the PLS is protected against damp, dirt and damage, – in which the PLS is not influenced by sunlight or artificial light sources, – which is as accessible as possible for electrical installation work. Please note that intrusion into needle-formed protective fields/ protective field sections (protective field segments only consist of a single pixel) is ignored by the device for reasons of availability. If such forms of protective fields cannot be avoided, always programme at least one more adjacent pixel. Approval of the PLS for use as a personal protection appliance is based on area protection. Other mounting locations are, following an assessment of potential risks and with the approval of the relevant authorities, also possible. The possibility of people being endangered must always be excluded.

Range of the PLS The PLS measures its surroundings in a semicircular plane – (scanning angle 180°). Employment of an optoelectronic safety device as area protection requires a minimum resolution of 70 mm at a specific mounting height of 300 mm. The PLS guarantees this resolution to a distance of 4 metres. Therefore the system software of PLS type 101-312 limits the maximum radius of the protected field automatically to 4 metres. The PLS type 201-313 does not have this limitation, and so is not certified for personal protection. The protective field safeguarding the hazardous area of a machine- or vehicle may have a maximum radius of 4 metres. The PLS shuts the machine down or stops the vehicle in the event of an intrusion into the protective field. The warning field may have any radius up to 50 metres. You should note, however, that the sensor is only able to detect objects with a reflectance of approx. 20 – 30 % to a distance of 15 metres. The measuring range of the PLS extends to a radius of 50 metres. Up to that distance the PLS is able to detect the contour of its surroundings (e.g. the space contour). It can then additionally evaluate this data for the protective field and the warning field, provided the reflectance of the object is sufficient to be detected.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

11

08.07.2004, 15:54

11

Page 12

5.1 Stationary protection with PLS Important notes on configuration In “with restart inhibit” mode the actuating element for the restart inhibit must- be positioned so that there is full visibility of the hazardous area. The actuating element for the restart inhibit must not be accessible from the point directly in front of the sensor. In “with restart inhibit” mode the close-up zone1) of the sensor (4 cm wide area measured from the front screen outer area) is either to be rendered inaccessible (e.g. by a bar or undercut), or a proximity scanner with a 4 cm detection range is to be mounted over the sensor. For area protection, side access to the machine base is also to be taken into account when configuring the protective field. This assumes that a person approaches the machine base from the side. If side access is possible (no solid restrictions such as a wall), the protective field should be configured wider than the machine base. In area protection applications it must be ensured that, with protective field widths over 2 metres, there are no retroreflectors in the immediate proximity of the protective field on the scanning plane. Otherwise corruption of the measured values is to be expected under extreme conditions. If it is impossible to avoid having retroreflectors in the scanning plane, an extra 20 cm should be added to the maximum measuring error2). The maximum measuring error is • 94 mm for protective fields ≤ 2 m • 131 mm for protective fields > 2 m Where there are fixed restrictions (walls) there must be no retroreflectors in the scanning plane, as otherwise someone could move along the wall to bypass the protective field. For both graphic and numerical programming, it must be ensured for reasons of functionality (solid barriers should not lead to unintentional shutdown) that where fixed contours exist a distance of 94 mm for protective fields below 2 metres and 131 mm for protective fields over 2 metres is observed. Where the teach-in function is used, a 45 mm supplement on top of the maximum measuring error is required for the accuracy of the learned contour. Recommendation: When installing stationary plants, it is recommended that you mark out the shape of the protective field on the floor to make it easier to perform the regular machinery checks.

12

1)

2)

An optical radar cannot distinguish between a dirty front screen and an obstacle directly in front of the sensor. For the sake of functionality, the PLS was designed to reliably detect solid black bodies such as black cord or shoe leather only at a distance of 4 cm measured from the outer contour of the front screen. Accuracy of the sensor in safety applications: the sensor determines the distance of an obstacle from the flight time of a very short light pulse. To attain optimum accuracy against obstacles of solid black material (1.8% reflectance) up to precision triple reflectors (10,000% reflectance), the PLS compensates the received signal. If there is a dark object in front of a retroreflector, under certain circumstances (see above) the error distance of 20 cm may be too large. This would mean that a person could intrude 20 cm into the monitored area without being detected by the PLS. This measuring error occurs only when the following conditions simultaneously apply: – the distance to the target is greater than 2 metres, – the target is smaller than 140 mm, – the retroreflector is on the scanning plane, – the reflector is aligned perpendicular to the sensor within an angle of ± 30°, – the target reflectance is in the area of 1.8%, – the retroreflector is not more than 2 metres behind the target, and – the reflector has high reflectance.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

12

08.07.2004, 15:54

Page 13

Location planning There are two basic alternative procedures for defining mounting locations: First option: using the so-called teach-in mode. In this mode the PLS measures the ambient contour and stores it (after automatic correction) as the outer protective field. The following formulae must be applied to check compliance with the relevant specifications, such as the safety distance and mounting height-, retrospectively.

Hazard area

PLS HD = 0

Second option: using graphical or numerical protective field input. In this the specifications to be complied with are ascertained at the outset and are then set in programming of the scanner.

C = 1200

1)

The basis for planning the mounting location of the PLS is as per EN 999. It describes the necessary safety distance from the hazardous area by: S = (K x T) + C

Case 1: Scanning plane parallel to ground (HD = 0)

Where: S is the minimum distance in millimetres, measured from the hazardous area to the detection point, detection line, detection plane or protective field; K is a parameter in millimetres per second, derived from data relating to approach speeds of the body or body parts; T is the stopping time of the overall system in seconds C is an additional distance in millimetres which takes account of the possibility of intrusion into the hazardous area before tripping of the safety device.

Hazard area

In access protection applications, an approach speed of 1600 mm/s is applied as K.

HD = 875

T results from addition of the response time of the sensor and the stopping time of the hazardous movement. C = 850

1)

C describes the possibility of reaching over the protective field without tripping the sensor, and varies with the height of the protective field limit according to the following correlation: C = 1200 mm - 0.4 HD (HD = height of detection) where C ≥ 850 mm Consequently: where HD = 0 : CHD=0 = 1200 mm where HD = 875 : CHD=875 = 850 mm This correlation is shown graphically in the adjacent diagrams (cases 1 and 2).

Case 2a: Scanning plane at maximum height and parallel to ground (HD = 875)

Hazard area

Note: The protective field supplement C is to be chosen depend-ing on the height of detection HD. In case 2b, protection of marginal areas, note that the scanning plane is not raised. Also note that if the sensor is not mounted parallel to the floor the effective protective field length is reduced.

HD = 875

C

1)

C = 900 with multiple evaluation = 2 C = 950 with multiple evaluation = 4 etc. 1)

Supplement to safety distance Case 2b: Scanning plane at maximum height, not parallel to ground (HD = 875)

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

13

08.07.2004, 15:54

13

Page 14

As a secondary condition, EN 999 stipulates the following minimum height: HD = 15 x (d - 50) mm Application of this formula is necessary as the leg diameter changes with the distance from the floor. Here, d is the resolution of the PLS (d is dependent on the distance from the scanner).

Machine ma x fie . pro ld te Protective field leng ctive th

The resolution of the scanner must always be determined at the point of the greatest measuring distance, i.e. at the greatest occurring protective field length SLmax. Based on the working principle of the PLS by means of radial scanning of the surroundings, a resolution is produced which decreases as the distance from the sensor increases. Thus a protective field length SL greater than 2.70 metres (only up to this distance is a scanner resolution of 50 m guaranteed) makes a certain detection height necessary. In this way it is possible to compensate for the lower resolution with greater leg diameter.

Resolution of the scanner at the point of longest protective field length SL.

These correlations between SL, HD, HS and C are shown graphically- in the adjacent diagrams. In this, HD is the height of the scanner plane, measured directly on the sensor. With horizontal mounting there is no risk of unwanted accessing at mounting heights below 100 mm (for example crawling under the scanning plane). To prevent children from crawling underneath, the maximum mounting height is 200 mm. Mounting heights of less than 100 mm are generally not to be recommended, as in such cases it is possible that the scanner may accidentally shut down as a result of the increased dust concentration directly on the floor. For these reasons this mounting range is often preferred, and consequently is identified as such in the diagram.

Using the diagram: Define the maximum protective field length SLmax in your layout. Shift the right Y-axis (HD) in parallel onto the located value SLmax. Then place the desired scanning plane in the remaining area shaded grey. The plotted scanning line must not leave the grey area at any point. Within the area shaded grey in the diagram any mounting orientation is possible, provided it does not impair the safety distance.

HS (mm)

1000 HD 875

850

PLS scanning area C 300

300 Preferred area for horizontal installation

100

100

0

1200 2m Longest protective field length

3m 2.9 m

4m

Correlation between protective field length, resolution of sensor and height of scanning plane

14

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

14

08.07.2004, 15:54

Page 15

Read-off example: You determine a maximum protective field length of 3.50 metres. To determine the minimum field length at the edge of the protective field, shift the right Y-axis in parallel onto the value 3.50 metres. You will then see that the detection height must not be lower than 150 mm. The mounting height of the sensor is freely selectable up to a height of 1000 mm. Thus the scanning plane does not go beyond the grey area.

HS (mm) 1000

HD 875

850

PLS Application area C 300

Note: Please note that the height of the beam HS is 63 mm above the bottom edge of the housing.

100

150 1200

0 2m 3 m 3,5 m Longest protective field length

4m

There are three common mounting orientations for the PLS. The optimum mounting orientation depends on the situation. The table provides some assistance in making the right choice.

Advantages

Disadvantages

Case 1: Scanner low (HS < 300 mm) low scanning plane inclination (HD approx. HS )

No external dazzling crawling under beam not possible

Large protective field supplement C

Case 2: Scanner high (HS > 300 mm) low scanning plane inclination (HD approx. H S)

Small protective field supplement C

Risk of crawling under beam (from front and sides)

Case 3: Scanner low (HS < 300 mm) high scanning plane inclination (HD > HS)

Small protective field supplement C

Risk of crawling under beam (from front) external dazzling possible

Scanner setting

* HD = detection height, HS = height of scanner mounting

Any other mounting orientation and intermediate height which prevents a hazardous situation arising is possible, provided the safety distance is observed. Always take account of the marginal area protection. The protective field supplement C is determined on the basis of the choice of mounting orientation. We recommend for an initial calculation: In case 1: C = 1200 mm In case 2: C = 1000 mm In case 3: C = 1000 mm The formula to be applied is: S = (1600 mm/s x T) + C + ZM + ZR + ZE whereby: ZM is a supplement for the general measuring error of the PLS ZR is a supplement for any reflection-related measuring error of the PLS ZE is a supplement for the measuring error of the PLS resulting from teach-in (see important notes on configuration for stationary protection). Note: Every time the parameters are changed, check that the protective field is still adequately dimensioned and that no unwanted access (from the side or by crawling underneath the scanning plane) is possible! Make sure that all necessary supplements are taken into account in the calculation.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

15

08.07.2004, 15:54

15

Page 16

Restart definition The machine should preferably be operated with restart inhibit. If the machine control has no restart inhibit, the internal restart inhibit of the PLS can be used. A restart inhibit is always essential when the protective field can be exited towards the hazardous area. Where necessary, check whether this can be prevented by plant design (see following subsection: Mounting recommendations for PLS).

If a machine can only be operated without restart inhibit, it is essential that the following points should be observed. – A person must be reliably detected at every point in the hazardous area. – A person must not be allowed to exit the protective field in the direction of the hazardous area (such as by crawling underneath it, stepping behind it or climbing over it). Make sure this is prevented by plant design (see following subsection: Mounting recommendations for PLS)!

Mounting recommendations for PLS The following considerations must be taken into account when designing the plant: The mirror pivot point of the PLS determines the position of the front edge of the protective field. Since the mounting area and the mirror pivot point are at a set distance from one another, a zone is produced in front of the mounting area which is not detected by the scanner. This zone becomes Iarger if the PLS is mounted on the mounting bracket, for example. The size of this dead zone – measured from the back edge of the PLS or the mounting kit – is: PLS direct-mounted PLS with mounting kit 1 PLS with mounting kit 1 and 2 PLS with mounting kit 1, 2 and 3

109 mm 112 mm 127 mm 142 mm

There are cases in which design measures must be applied to prevent persons from being in the hazardous area but outside the protective field (such as by crawling un-derneath it, stepping behind it or climbing over it). To exclude this possibility where a laser scanner is mounted on the machine, one of the following measures (or a combination of them) is essential: – undercutting, – retraction of the laser scanner, – mounting of the laser scanner opposite or to the side of the machine base.

16

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

16

08.07.2004, 15:54

Page 17

Undercutting:

US

The undercut must always be at least as low as the dead zone. With regard to the mounting height the observations presented under “Location Planning” apply. To prevent entry into the undercut, it is necessary to limit its height.

Machine table

H

Scanning level

Undercutting

Retraction of the laser scanner: Z

Retraction of the laser scanner into the machine contour presents an alternative to the undercut. However, retracting the PLS too far will mean that the scanner is unable to monitor the full 180°. In such cases you need to design the shadow sides to he inaccessible (point-of-operation guard).

Machine table

If you need to monitor the full 180°, for geometric reasons the retraction depth of the scanner must be limited to a maximum of 69.5 mm (corresponding to a protrusion of the PLS beyond the front of the machine of at least 86.5 mm). The observations regarding the detection reliability of the PLS and the stipulations of EN 999 result in the following correlation between the minimum height of the scanning plane on the scanner HSmin and the protrusion Z from the front of the machine.

Scanning level

Scanner retraction

HSmin = 15 x (Z - 90) where: HS ≤ 1000mm, 86.5 mm ≤ Z ≤ 156 mm Note: Before the scanner is mounted it is essential that the height of the scanning plane HS should be translated into the attachment height HA ! The necessary dimensions of the scanning plane in relation to the fixed holes for the scanner are shown in the dimensional drawings in the section headed “Mounting the PLS”. The minimum mounting height is based on the retraction depth. The deeper you can retract the PLS, the lower you can mount it. Take into consideration the possible shadowing of the marginal areas when retracting the scanner. With regard to the resolution of the PLS and the danger of crawling underneath the scanning plane, the points made under “Location planning” apply.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

17

08.07.2004, 15:54

17

Page 18

Mounting of the laser scanner opposite or to the side of the machine base: US lf the PLS is in the way when installed on the machine base, it can alternatively be mounted opposite. For this, because of the measuring tolerances of the PLS, it is essential that an undercut be made in the machine base.

Scanning level

H

The necessary minimum undercut USmin on the machine is calculated on the basis of

Machine table

The maximum measuring error is dependent on the size of the maximum protective field length, and at up to 2 metres the maximum measuring distance is 94 cm; at over 2 metres the maximum measuring distance is 131 mm. The resolution at this measuring distance is given in the diagram. For application of this formula, the distance between the protective field limit and the machine must not be greater than the maximum measuring error. If the protective field limit is further away from the machine, USmin is increased accordingly.

Machine table

USmin

USmin = (2 x SFdistance) – d = (2 x max. measuring error) – d ma fie x. pr Protective field ld len otec gth tive

Mounting of a scanner opposite or to the side of the machine base

Read-off example: In your protective field you determine the maximum protec-tive field length as 3500 mm. From the diagram you read off a resolution dmax of 60 mm.

Diagram: Protective field length and calculation

18

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

18

08.07.2004, 15:54

Page 19

5.2 Mobile protection with PLS In mobile protection the sensor can be operated both with and without restart inhibit, depending on the application. The regulations applicable to the vehicle must be observed. In “with restart inhibit” mode the actuating element for the restart inhibit must be positioned so that there is full visibility of the hazardous area. The actuating element for the restart inhibit must not be accessible from the point directly in front of the sensor. In “with restart inhibit” mode the close-up zone1) of the sensor (4 cm wide area measured from the front screen outer area) is either to be rendered inaccessible (e.g. by a bar or undercut) or a proximity scanner with a 4 cm detection range is to be mounted over the sensor. For mobile protection, side access to the vehicle is also to be taken into account when configuring the protective field. This assumes that a person approaches the vehicle from the side, for instance in concealed areas (e.g. crossways). If side access is possible (no solid restrictions such as a wall), the protective field should be configured wider than the vehicle. In mobile protection applications it must be ensured that, with protective field widths over 2 metres, there are no retroreflectors in the immediate proximity of the protective field on the scanning plane. Otherwise corruption of the measured values is to be expected under extreme conditions. lf it is impossible to avoid having retroreflectors in the scanning plane, an extra 10 cm should be added to the maximum measuring error2). The maximum measuring area is • 94 mm for protective fields ≤ 2 m • 131 mm for protective fields > 2 m Where there are fixed restrictions (walls) there must be no retroreflectors in the scanning plane, as otherwise someone could move along the edge of the protective field to bypass it. For both graphic and numerical programming, it must be ensured for reasons of functionality (solid barriers should not lead to unintentional shutdown) that where fixed contours exist a distance of 94 mm for protective fields below 2 metres and 131 mm for protective fields over 2 metres is observed. Where the teach-in function is used, a 45 mm supplement on top of the maximum measuring error is required for the accuracy of the learned contour. Recommendation: When installing mobile plants, you are advised to attach a notice or a configuration diagram to the vehicle to simplify the regular checks.

1)

2)

An optical radar cannot distinguish between a dirty front screen and an obstacle directly in front of the sensor. For the sake of functionality, the PLS was designed to reliably detect solid black objects such as black cord or black shoe leather only at a distance of 4 cm measured from the outer contour of the front screen. Accuracy of the sensor in safety applications: the sensor determines the distance of an obstacle from the flight time of a very short light pulse. To attain optimum accuracy against obstacles of solid black material (1.8% reflectance) up to precision triple reflectors (10,000% reflectance), the PLS compensates the received signal. If there is a dark object in front of a retroreflector, under certain circumstances (see above) the error distance of 20 cm may be too large. This would mean that a person could intrude 20 cm into the monitored area without being detected by the PLS. This measuring error occurs only when the following conditions simultaneously apply: – the distance to the target is greater than 2 metres, – the target is smaller than 140 mm, – the retroreflector is on the scanning plane, – the reflector is aligned perpendicular to the sensor within an angle of ± 30°, – the target reflectance is in the area of 1.8%, – the retroreflector is not more than 2 metres behind the target, and – the reflector has high reflectance.

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

19

08.07.2004, 15:54

19

Page 20

Location planning The following observations take into account only the vehicle speed, not the speed of a running person. The reason is that it is assumed that a person approaching the vehicle recognises the danger and at least stands still.

Vehicle Scanning level H

Mounting of a PLS on a vehicle

Mounting height: Due to the intrinsic movement of the scanner in the mobile application, a resolution of 70 mm is adequate for detection of persons in mobile applications (stationary application: 50 mm). For this reason, the mobile application requires no increase protective field ranges over 2.90 m. The sensor is to be calibrated in accordance with EN 1525 such that a body of maximum 200 mm height under all circumstances is detected in the protective field range necessary to bring the vehicle to a safe stop. (Recommendation: setting to 150 mm height).

Pre-set protective field length

Vehicle max. 272 mm 150 mm

Mounting height

The scanning plane should not be below 100 mm, as the increased dust concentration on the floor could cause the scanner to shut off unintentionally.

Mounting mode:

Dead zone

A basic distinction is made between two modes of mounting the PLS: Protruding front mounting The dead zones created at the sides of the sensor in protruding front mounting must be eliminated by mechanical trim covers or switch strips, or the vehicle must not be accelerated to speeds above 0.3 m/s in less than three seconds.

Protective field

Vehicle

Integral in-vehicle trim panel: The sensor is installed such that no dead zones, or no dead zones > 70 mm, are created to the side of it. The vehicle may then be accelerated to a speed of 0.3 m/s within one second. In order to meet this condition, the PLS must not protrude more than 109 mm over the front edge of the vehicle.

Mounting mode: protruding front mounting max. 109mm

If the close-up zone of the sensor (4 cm wide area measured from the front screen outer contour) is either rendered inaccessible (e.g. by a bar or undercut) or is monitored by a proximity scanner or a switch strip with a 4 cm detection range, the vehicle may be accelerated at will. Vehicle

Protective field

Mounting mode: integral in vehicle trim panel

20

8 008 316/O801/07-07-04 Technical Description • PLS © SICK AG • Industrial Safety Systems • Germany • All rights reserved

PLS_TB_GB_06_05_02_M844.pmd

20

08.07.2004, 15:54