Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact
Page 1 of AMV 30-041 Connection Module: Technical Information

Spec sheet · Sick

AMV 30-041 Connection Module: Technical Information

Spec sheet8 pagesPDF 344 KB

Technical information for the SICK AMV 30-041 connection module that wires one CLV 21x to 28x bar code scanner to a host, PLC and power.

Download the PDF344 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

The technical information sheet for the SICK AMV 30-041 connection module, a wall-mounted terminal box that connects one SICK CLV 21x/22x or CLV 23x/25x/28x bar code scanner to a host, PLC or sensors and to its 24 V supply. It lists features, scope of delivery and system requirements, recommended cable lengths per interface, the layout and DIL switch settings, terminal assignments and wiring diagrams for RS 232, RS 422, CL 20 mA and RS 485 hosts, dimensions, technical data and ordering numbers for cables and connectors.

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

SICK technical information for the AMV 30-041 connection module, not the AMV 30-061 the site files it under. The module links one CLV 21x/22x or CLV 23x/25x/28x bar code scanner to a host, PLC, sensors and its DC 24 V supply. It shows the DIL switch settings, terminal assignments and wiring for each host interface, with technical data and order numbers of cables and connectors.

Device
AMV 30-041 connection module for one CLV 21x/22x or CLV 23x/25x/28x bar code scanner p. 1
Operating voltage
DC 24 V ± 20 % (to IEC 742) p. 8
Host interfaces
CL 20 mA, RS 232 and RS 422/485 (including the SICK network) p. 2, 7
Power needed
CLV 21x/22x: approx. 6 W, wire at least 0.09 mm2; CLV23x to 28x: approx. 15 W, at least 0.28 mm2 p. 3
Connections
Terminal strips; 7 x PG 11 conduit thread (cable dia. 4 to 10 mm); 9pin D Sub plug for the terminal interface; 9pin D Sub service socket p. 8
Fuse
4 A, slow-blowing, dia. 5 mm x 20 mm p. 8
Enclosure
Poly carbonate housing, IP 65 (to DIN 40 050), class 3 (to VDE 0106) p. 8
Weight
approx. 600 g p. 8
Temperature
0 to +40 °C operating; –20 to +75 °C storage p. 8
Humidity
Max. 90%, non-condensing p. 8
Order number
1 015 435 (AMV 30-041) p. 8
Scanner cables
6 010 137 (CLV 21x/22x, 15pin, 2m); 2 020 262 host/term and 2 013 574 I/O (CLV 23x...28x, 9pin, 3m) p. 8
PC cable
2 014 054 RS 232 data cable, two 9pin D Sub sockets, 3m p. 8
Host cable to 1,000 m
CL 20 mA at max. 9,600 Bit/s: max. 1,000 m to the host p. 2

What this sheet walks you through

  • Mounting the module near the scanner p. 2
  • Setting the S1 and S2 DIL switches for the host interface p. 2, 4
  • Wiring the function inputs and outputs, operating voltage and terminal interface p. 4
  • Wiring an RS 232 host p. 5
  • Wiring an RS 422 host and switching in line termination p. 5
  • Wiring a CL 20 mA host, passive or through the module's current sources p. 6
  • Wiring an RS 485 SICK network p. 7
  • Connecting a PC with CLV Setup to the scanner's terminal interface p. 4

Good to know

  • Wrong S1 and S2 DIL switch settings may destroy internal modules in the connected scanner. p. 4
  • The module cannot supply a bar code scanner with integrated heating. p. 3
  • Unused inlets must be sealed with the supplied blank covers to reach IP 65. p. 4
  • The power supply output must be insulated from its input by double insulation and a safety isolating transformer. p. 3
  • Do not run data cables long distances parallel to power supply and motor cables. p. 3

Questions this sheet answers

Which SICK scanners work with the AMV 30-041?

One scanner of the CLV 21x/22x or CLV 23x/25x/28x series per module. p. 1

What PC settings does CLV Setup need through the AMV 30-041?

2,400 Bit/s, 8 data bits, no parity, 1 stop bit, with the PC on the "Term 1" 9pin D Sub plug inside the module. p. 4

What fuse does the AMV 30-041 use?

A 4 A slow-blowing fuse, 5 mm x 20 mm. p. 8

What power supply does the AMV 30-041 need?

DC 24 V ± 20 % to IEC 742, about 6 W for a CLV 21x/22x or about 15 W for a CLV23x to 28x. p. 3, 8

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8

The file

Revision and size

Revision8 008 165/I938/12-2000
PublisherSICK AG
Pages8
PDF344 KB
TextText from the PDF itself.

The first pages · 4 of 8

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 8
Page 2
Page 2of 8
Page 3
Page 3of 8
Page 4
Page 4of 8

More documents · 1

For the same models