Page 1
RFL 9745 Teleprotection Channel
Key Features and Benefits • One product for audio, digital or fiber applications • Up to four independent functions per audio system, seven for digital/fiber • Sequence-of-events recording • Address and checkback testing • Bi-directional channel delay measurement • Trip output failure detection
• User-defined teleprotection logic and alarms • Remote RS-232 setup and diagnostics • Diagnostics and setup of remote RFL 9745 through the local RFL 9745 • Three year warranty • Optional Ethernet/Telnet adapter for remote LAN/WAN access.
The RFL 9745, is a fully programmable Teleprotection Channel suitable for Direct Transfer Trip, Permissive Transfer Trip, Blocking and Unblocking applications. Flash memory and remote RS-232 communications allows new firmware to be loaded making field programming possible without having to open the chassis. The communications interface can be converted in the field to adapt to different types of media. An unprecedented level of diagnostic information is available and easily accessible with the RFL 9745. RFL’s sequence-of-events, diagnostics package provides a convenient method for evaluating communications system performance during the fault clearing process.
RFL Electronics Inc. July 2004
PI9745
Page 2
Applications
• Channel propagation delay measured and reported • Channel delay in each direction available with IRIG-B The RFL 9745 communications interface can be configured • Commissioning can be accomplished remotely or from for audio, digital or fiber optic media. It is well suited for all a single terminal standard and non-standard pilot protections schemes such as: Figure 1 shows the record number, the name of the parameter that changed state to trigger the event, and the date and time • Permissive Transfer Trip the event occurred. Below this, the status of all inputs, out• Direct Transfer Trip puts, and alarm outputs at the time of the event are listed. This • Blocking and Unblocking information can be used to analyze the system conditions at the precise instant the event occurred. Diagnostics and Testing Diagnostic information is available and easily accessible with the RFL 9745. RFL's diagnostic package takes the guesswork out of power system fault analysis and evaluating communications system performance during the fault-clearing process. The RFL 9745 provides the following standard features: • Two RS-232 ports for local and remote access • Optional Ethernet/Telnet adapter for remote LAN/WAN access. • Trip output circuit failure detection • 100 Sequence-of-events records • Internal real-time system clock • IRIG-B Clock sync input • Six-digit cumulative operations counters • System outage timer • Current status of all system parameters • Diagnostic information about the remote end • Checkback testing either locally or remotely initiated • Automatic checkback by interval time between tests Record 003
Programmability
Changes in field are no longer necessary for logic functions can be changed or fine-tuned remotely through the RFL 9745's RS-232 port or optional Ethernet/Telnet adapter. User Programmable Logic Functions Change timer values, logic states and logic functions without ever removing a module or opening the chassis. User Programmable Inputs and Outputs The RFL 9745 can be supplied with two Input/Output modules. Each module provides optically isolated inputs, solidstate or dry relay contact outputs, as well as form "C" alarm contacts. The function of all of these inputs and outputs can be individually programmed to meet the application requirements. Create your own alarm conditions The RFL 9745 can be equipped with either three or six fullyprogrammable alarm/annunciator relays.
Event Trigger: Annunc Relay 1A Inactive Event Time: 01/01/98, 00:07:06.260
Input 1A Input 2A Input 3A Input 4A Input 1B Input 2B Input 3B Input 4B
I I I I I I I I
Output 1A Output 2A Output 3A Output 4A Output 1B Output 2B Output 3B Output 4B
I I I I I I I I
Rx Freq High Ch1 Rx Freq High Ch2 Rx Freq High Ch3 Rx Freq High Ch4 Rx Freq Low Ch1 Rx Freq Low Ch2 Rx Freq Low Ch3 Rx Freq Low Ch4
I A I A A I A I
Annunc Relay 1A Annunc Relay 2A Annunc Relay 3A Annunc Relay 1B Annunc Relay 2B Annunc Relay 3B
I I A I I I
Annunc Output 1 Annunc Output 2 Annunc Output 3 Annunc Output 4 Annunc Output 5 Annunc Output 6
I I I I I I
Tx Function Ch1 Tx Function Ch2 Tx Function Ch3 Tx Function Ch4 Address Test Fail Autotest Timeout
I A I A I I
Run Auto Test FM Noise Ch1 FM Noise Ch2 FM Noise Ch3 FM Noise Ch4 Comms CPU Failure
I I I I I I
Channel Delay AM Noise Ch1 AM Noise Ch2 AM Noise Ch3 AM Noise Ch4 Outage Timer Active
I I I I I I
Bus Error Left Power Low Right Power Low Battery Failure RS232 Active Test in Progress
I I A A A I
Autotest Complete
I
Figure 1. Typical individual event record display for the Audio System RFL Electronics Inc. July 2004
2
PI9745
Page 3
Programming to a disk file for future downloading to the RFL 9745. The DOS program can also be utilized as a training tool to allow users to become familiar with the equipment.
The RFL 9745 is programmed using RFL's Asynchronous Programming and Remote Interrogation Language (PC APRIL). PC APRIL provides the user with a verbose man/ machine interface in an ASCII format. It is accessible using any standard terminal emulation or communication software on a personal computer.
A specialized software, the RFL Expert System, has been developed to allow graphical design of the system logic by using a specialized symbols library. The RFL Expert System is a WINDOWSTM -based application software package which allows the user to develop his own protection schemes. This software is intended for customers who want to create, modify, or simulate applications for their RFL 9745 without having the hardware in front of them.
All functions that require adjustments during normal installation and maintenance are also available by using the frontpanel display and push-button switches. All programming levels available over the RS-232 (or Telnet adapter) interface are password-protected.
The RFL Expert System consists primarily of an OrCADTM Schematic Capture Program coupled with an RFL designed WINDOWSTM -based editing system and RFL's easy-to-use PC APRIL programming language. This system includes a digital simulator which allows the user to simulate logic inputs to the newly designed system logic and verify the expected results prior to uploading.
Every RFL 9745 is supplied pre-programmed with a default operating program. On the audio tone version, after the standard program is uploaded into the system, all the user needs to do is enter the operating frequencies and bandwidths. Figure 2 shows the parameter settings for the audio tone version, Figure 3 shows the parameter settings required for RFL 9745's configured with any of the several digital interfaces available.
OrCADTM Software is used to design RFL 9745 alarm logic and primitive logic diagrams. The RFL Expert System software is used to run simulations on the logic diagrams and to combine the primitive and alarm logic diagrams into one set of files for the RFL 9745. These files are then used to program the RFL 9745 using PC April Software.
A DOS version of the RFL 9745 PC APRIL software package is supplied with every order. This version allows the application engineer to save revised programing parameters # 999 001 002 003 005 006 008 010
PARAMETER System Label Channel 1 Tone 1 Tx Freq Transmit Level Tone 1 Rx Freq Rx Bandwidth Rx Alarm FM Noise
SETTING sec/dep Single 1540 Hz 1690 Hz 0.00 dBm 1540 Hz 1690 Hz 225 Hz -40 dBm 15 %
016 017 018 020 021 023 025
Channel 2 Tone 2 Tx Freq Transmit Level Tone 2 Rx Freq Rx Bandwidth Rx Alarm FM Noise
Single 1200 Hz 1350 Hz 0.00 dBm 1200 Hz 1350 Hz 225 Hz -40 dBm 15 %
031 032 033 035 036 038 040
Channel 3 Tone 3 Tx Freq Transmit Level Tone 3 Rx Freq Rx Bandwidth Rx Alarm FM Noise
Single 2220 Hz 2370 Hz 0.00 dBm 2060 Hz 2370 Hz 225 Hz -40 dBm 15 %
046 047 048 050 051 053 055 060 062 064 066 068
Channel 4 Tone 4 Tx Freq Transmit Level Tone 4 Rx Freq Rx Bandwidth Rx Alarm FM Noise Opt Status Board Chan delay alarm Date Hour Adjust Remote Address
Single 1880 Hz 2030 Hz 0.00 dBm 1880 Hz 2030 Hz 225 Hz -40 dBm 15 % No 8 ms 01/01 -1 0
#
PARAMETER
SETTING
004
Boost Level
0 dB
007 009
Rx Level AM Noise (SNR)
0 dBm 9 dB
019
Boost Level
0 dB
022 024
Rx Level AM Noise (SNR)
0 dBm 9 dB
034
Boost Level
0 dB
037 039
Rx Level AM Noise (SNR)
0 dBm 9 dB
049
Boost Level
0 dB
052 054
Rx Level AM Noise (SNR)
0 dBm 9 dB
061 063 065 067 069
EE Pot J10 Year Time Local Address Reset Log
B 1998 02:07:38 0
Figure 2. Typical Audio System parameter settings display RFL Electronics Inc. July 2004
3
PI9745
Page 4
System Specifications Audio Communications
SPURIOUS OUTPUT All harmonics and spurious outputs are at least 40 dB lower than the carrier.
Audio tone versions of the RFL 9745 can be supplied with two or four FSK audio tone transceivers. All transceivers are bidirectional and can be programmed for any operating frequency or bandwidth between 300 and 4,000 Hz. Channel one can be set to operate as a modem channel. This channel provides a communication link to the remote terminal for remote interrogation, setting changes or system testing from the local terminal.
TRANSMITTER STABILITY The transmitter frequency is stable within 0.02 percent over the full range of temperature and input power variations. TRIP BOOST Amplitude: Adjustable from zero to +12 dB in 1 dB steps. Duration: Adjustable from zero to 30 seconds in .5ms steps.
AUDIO INTERFACE CONFIGURATIONS Single Two-Wire Terminals Dual Two-Wire Terminals Single Four-Wire Terminals Dual Four-Wire Terminals
INPUT AND OUTPUT IMPEDANCE 600 Ohms
Digital Communications
RECOMMENDED CHANNEL FREQUENCIES Range: 300 Hz to 4000 Hz Resolution: 1Hz
The RFL 9745 is available with five types of serial digital interfaces: 56Kbps/RS-449, 64Kbps/G.703 Codirectional and Contra-directional interfaces, 64Kbps/X.21, and 2.048Mbps/ G.703.
TRANSMIT LEVEL Adjustable from -40 dBm +10 dBm in 0.25 dB steps RECEIVER SENSITIVITY Minimum Input Level: -40 dBm Maximum Input Level: 0 dBm
The digital interfaces conform to the standards set forth in their respective specifications (RS-449, CCITT G.703, X.21). Figure 3 represents a typical parameter settings display for the digital system.
RECEIVER DYNAMIC RANGE (referenced to center point) -17 dB to + 11 dB
Fiber Optic Communications Interfaces and System Gains are as follows:
Fiber Optic Communications
Wavelength & Emitter Type 850 nm LED 1300nm LED 1300nm LED 1300nm Laser 1550nm Laser 850 nm LED
ADJACENT CHANNEL REJECTION 40 dB 60-HZ REJECTION A received tone at -30 dBm will not be affected by a 50 Hz or 60 Hz signal as great as 40 Vrms with optional 50/60 Hz blocking filter. AMPLITUDE STABILITY The Transmit level will vary by no more than ±1 dB. #
PARAMETER
SETTING
999 011 012 013 014
System Label Functions 1-7 Major Data Error Minor Data Error Alarm BER sec/dep Digital 6, 500 400, 200000 1E-04
060 063 065 067 069
Opt Status Board Year Time Local Address Reset Log
No 2000 00:00:21 0
(short haul)
Fiber Type
Connector Type
Multimode Multimode Singlemode Singlemode Singlemode Multimode
ST ST ST ST ST ST
Receiver Output Sensitivity Level -18 dBm -46 dBm -13 dBm -39 dBm -17 dBm -39 dBm 0 dBm -39 dBm -3 dBm -39 dBm -19dBm -32dBm
#
PARAMETER
SETTING
062 064 066 068
Chan delay alarm Date Hour Adjust Remote Address
8 ms 01/01 -1 0
System Gain 25 dB 25 dB 18 dB 36 dB 30 dB 13dB
Figure 3. Typical parameter settings display for the Digital System. Specifications subject to change without notice.
RFL Electronics Inc. July 2004
4
PI9745
Page 5
850 NM SHORT HAUL FIBER INTERFACE The RFL 9745 is typically located close to the protective relaying equipment. The communications equipment, could be located in a different room or building in the substation. The RFL 9745 when configured with the Short Haul Fiber Interface, eliminates the ground potential rise and induced voltage concerns associated with routing a copper communications cable between two sites. A pair of 850 nm multimode fiber optic cables are routed between the two locations. The fibers can be up to 1 kilometer (3,280 feet) long and terminated with ST type connectors. There are two ways to implement short haul fiber communications between the RFL 9745 and a multiplexer. The Short Haul Fiber Interface for the RFL 9745 is compliant to the ANSI C37.94 Short Haul Fiber Standard and will directly communicate to a multiplexer with a compliant interface. If the multiplexer does not support the standard, RFL can provide a remote Fiber Optic Service Unit that converts the optical signal into an electrical signal that will be accepted by the multiplexer. The digital output of the Fiber Optic Service Unit is connected to the communications equipment by a short electrical cable as shown in Figure-4. If the communications equipment supports the ANSI 37.94 Short Haul Fiber Interface standard the fiber optic cables can be interfaced directly to it as shown in Figure 5. SHORT HAUL SERVICE UNIT FIBER OPTIC TRANSCEIVERS Compliant to ANSI C37.94 Short Haul Fiber Standard Fiber Type:
50 Micron core, 850 NM Multimode 62.5 Micron core, 850 NM Multimode
Optical Budget: 9db for 50 Micron core 13db for 62.5 Micron core Fiber Connector: ST Digital Connector: RS-449, 64kbps, DB37 Male Connector V.35, 64kbps, DB37 Male Connector X.21, 64 Kbps, DB15 Male Connector G.703, 64-768 Kbps, DB15 Male Connector INPUT POWER Less than 5W with a 38-150VDC power supply input.
Relay
Comm unication
Relay Building Building
Building Building Communication
9745 RRFL FL 9745 Short H Haul wwith ith Short aul Fiber Interface Fiber Interface
Communication Comm unication MMultiplexer ultiplexer Equipment Equipment
RS449 Cable Cable
Fiber Service Unit
R emote Fiber O ptic Service U nit
Approximately11KKm maximum Approximately mm um distance distance
Multim ode Fiber Cable Pair W ire Trough
Figure 4. Typical RFL 9745 Short Haul Fiber Optic Application with Fiber Service Unit
Relay
Comm unication
RelayBuilding Building
Communication Building Building Communication Comm unication Multiplexer MEquipment ultiplexer Equipment
9745 RRFL FL 9745 Short H Haul wwith ith Short Fiber Interface Fiber Interface
Short Haul Fiber Interface
RS449 Cable R emote Fiber O ptic Service U nit
Approximately 11 Km Approximately K mmaximum m axim umdistance distance
Multim ode Fiber Cable Pair W ire Trough
Figure 5. Typical RFL 9745 Short Haul Fiber Interface Application direct to multiplexer with C37.94 compliant I/O Specifications subject to change without notice.
RFL Electronics Inc. July 2004
5
PI9745
Page 6
Real Time Clock a 10 Base-T Ethernet network that is becoming very common in a substation envirement.
IRIG-B The RFL 9745 accepts the IRIG-B Standard Time Code on a 1kHz modulated carrier. Nominal signal levels are 3.3 volts peak-to-peak (± 0.5v) for a logic "1" and 1 volt peak-to-peak (± 0.2v) for a logic "0". The IRIG-B input presents a 3.7k ohm impedance and is transformer isolated.
The adapter is plugged into the right options bay of the RFL 9745. One of the two serial ports is called the Craft port and the other is the Data port. These RS232 ports are three-wire RS232 ports with a DB9 connector. The Craft power is used to set up the TCP/IP and Data port parameters.
RESOLUTION 1 ms
I/O Options
ACCURACY Free Running: Within 1 minute per month Under IRIG-B Control ±1msecs
The RFL 9745 can be configured with a maximum of two I/ O modules. There is a Solid-State, a Relay/Solid-State, and a HS Relay version available. All versions provide four optically isolated keying inputs and three independent form "C" alarm output contacts. The Solid-State version provides four independent solid-state outputs. The Relay/Solid State version provides three independent jumper selectable form "A" or form "B" output contacts and one solid-state output and the HS Relay version provides four independent jumper selectable form "A" or form "B" output contacts.
RESET Manual or by IRIG-B code ISOLATION The RFL 9745's RS-232 ports (front and rear panel) are isolated from circuit common and chassis ground to a surge withstand level of 500 Vdc.
Solid-State I/O
EVENTS STORAGE The Sequence of Events Recorder can store up to 100 events. After this limit is reached, older events are overwritten. The Events Log keeps a running tally of the number of times each function, input, output and alarm is active along with the time and date the event occurred. Up to 1,000,000 counts can be stored for each item.
OPTICALLY ISOLATED INPUTS Quantity: Four per module Required Operation Range: 24 Volt Units: 14.6 to 60 Vdc, Nominal Input Current 8.8 mA 48 Volt Units: 31 to 60 Vdc, Nominal Input Current 5.8 mA 125 Volt Units: 75 to 150 Vdc, Nominal Input Current 4.6 mA 250 Volt Units: 155 to 280 Vdc, Nominal Input Current 5.25 mA Input Current: 10 mA maximum Minimum Acceptable Pulse Width: 100 micro-seconds
RS-232 INTERROGATION PORTS The 9745 provides two RS-232 Ports, located on the front and rear of the chassis. The RS-232 Port located on the front of the chassis has priority. The front of the RS-232 port is configured as a DCE Interface. The rear RS-232 port is configured as a DTE Interface. DATA RATES 300 bps, 1200 bps, 2400 bps, 9600 bps or 19.2 Kbps. Selection is made using front panel switches.
SOLID-STATE OUTPUTS Quantity: Four per solid-state I/O module Output Current: Maximum 1 ampere continuous, 2 amperes for one minute, or 10 amperes for 100 msec Open-Circuit Voltage: 280 Vdc maximum S/S Pick-up Time: 0 msec
Communication Parameters: Number of Data Bits: Eight Number of Stop Bits: One Parity: None Flow Control: XON/XOFF
Ethernet Telnet Adapter For applications where a telnet link is required, the RFL 9745 can be equiped with the optional Telnet Adapter module. This adapter contains one Ethernet port and two RS232 serial ports. The basic function is to pass Ethernet mesages into a serial port, and to pass RS232 messages in an Ethernet port. The adpter allows the carrier set to be integrated into RFL Electronics Inc. July 2004
ALARM RELAYS Quantity: Three per I/O module Contact Configurations: SPDT (Form C) Maximum Output Current: 1 ampere continuous Maximum Breaking Current: 1 ampere (non-inductive) at 125 Vdc; derated to 0.25 amperes at 280 Vdc Open Circuit Voltage: 280 Vdc Maximum
Specifications subject to change without notice.
6
PI9745
Page 7
Relay/Solid-State I/O OPTICALLY ISOLATED INPUTS Quantity: Four per module. Required Operation Range: 24 Volt Units: 14.6 to 60 Vdc, Nominal Input Current 8.8 mA 48 Volt Units: 31 to 60 Vdc, Nominal Input Current 5.8 mA 125 Volt Units: 75 to 150 Vdc, Nominal Input Current 4.6 mA 250 Volt Units: 155 to 280 Vdc, Nominal Input Current 5.25 mA Input Current: 10 mA maximum Minimum Acceptable Pulse Width: 100 micro-seconds
125 Volt Units: 75 to 150 Vdc, Nominal Input Current 4.6 mA 250 Volt Units: 155 to 280 Vdc, Nominal Input Input Current: 10mA maximum Minimum Acceptable Pulse Width: 100 micro-seconds RELAY OUTPUT Quantity: Four per module Contact Configuration: SPST Form A or Form B -Jumper Selectable Relay Pick-up Time: 5 msec Output Current Rating: 5 amperes continuous Surge: 30 amperes for 200 msec
ALARM RELAYS Quantity: Three per I/O Module SOLID-STATE OUTPUTS Contact Configurations: SPDT (Form C) Quantity: One per relay/solid-state I/O Module Maximum Output Current: 1 ampere continuous Output Current: Maximum 1 ampere continuous, 2 amperes Maximum Breaking Current: 1 ampere (non-inductive) at 125 for one minute, or 10 amperes for 100 ms. Vdc; derated to 0.25 amperes at 280 Vdc 48 Volt Units: Open-Circuit Voltage: 150 Vdc maximum Open-Circuit Voltage: 280 Vdc maximum 250 Volt Units: Open-Circuit Voltage: 280 Vdc maximum S/S Pick-up Time: 0 msec ANNUNCIATOR CHASSIS The RFL 9745 can be supplied with an optional one rack RELAY OUTPUT unit Annunciator Chassis. This additional chassis is mounted Quantity: Three per module below the standard Three Rack Unit Chassis and provides Contact Configuration: six programmable solid-state outputs. Each output can be SPST Form A or Form B -Jumper Selectable individually programmed to provide specific output annunRelay Pick-up Time: 7 msec ciation, such as Trip Sent, Trip Received, RS-232 Port AcOutput Current Rating: 5 amperes continuous tive, etc. Surge: 30 amperes for 200 msec OUTPUT RATINGS ALARM RELAYS Maximum Output Current: 1 A continuous Quantity: Three per I/O Module Breaking Current: 100 mA (non-inductive) Contact Configurations: SPDT (Form C) Maximum Output Current: 1 ampere continuous Maximum Breaking Current: 1 ampere (non-inductive) at 125 Vdc; derated to 0.25 amperes at 280 Vdc Open-Circuit VoltAuxiliary Trip Relays age: 280 Vdc maximum.
HS Relay I/O OPTICALLY ISOLATED INPUTS Quantity: Four per module Required Operation Range: 24 Volt Units: 14.6 to 60 Vdc, Nominal Input Current 8.8 mA 48 Volt Units: 31 to 60 Vdc, Nominal Input Current 5.8 mA
The RFL 9745 can be configured with up to two auxiliary high speed trip relays which are mounted in either the primary or redundant power supply I/O module. The relays are typically controlled by one of the solid-state function outputs and provide two normally open and one normally closed contact each. Relay Ratings: Pick-up Time: 4 msec Contact Rating: 5 amperes continuous, 30 amperes for 200 msec
Specifications subject to change without notice.
RFL Electronics Inc. July 2004