Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact

The text of a manual · part 3 of 9

V600 RFID System V600-CD1D-V Serial Interface ID Controller Operation Manual, pages 21 to 30

Pages 21 to 30 of 89

The original document is the PDF (566 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron V600-CD1D-V2

Page 21

Section

DIP Switch Setting

3-1

3-1

DIP Switch Setting The communications interface is set by the DIP switches on the ID Controller. To gain access to the DIP switches, remove the cover on the monitor unit connector. Set the DIP switches in accordance with the communication specifications of the host computer.

Connector Cover Removal

DIP switch 1 DIP switch 2

Slide the connector cover upward. Insert the tip of a flat-blade screwdriver into the notch at the right of the cover and remove the cover. Switch Cover

Mode selector switch

DIP switch 1

DIP switch 2

When the switch cover is opened, a mode selector switch and two DIP switches, 1 and 2, are visible.

Setting Mode Selector Switch

The ID Controller operates as follows depending on the mode selector switch setting. Settings 0

Mode

Operation

RUN

Operates as specified by command from host controller. Although the IC Controller operates in the same manner regardless of where the selector switch is set (positions 0 through 3), set the switch to position 0.

TEST

Continuously reads 1 byte from address 0000 (read test).

1 2 3 4 5

Continuously writes 1 byte from address 0000 (write test).

6

RESERVED

7

Used by manufacturer for repairs.

8 and 9

Inhibited

Note Do not set switches 7 through 9 during normal operation. The Mode is set to “0” when the unit is delivered.

12

Page 22

Section

DIP Switch Setting

3-1

Dip Switch Settings DIP Switch 1

SW1

Display mode

0

Error Display Mode

1

I/O Display Mode

SW2

SW3

0

0

Transmission speed (bps) 2,400

0

1

4,800

1

0

9,600

1

1

19,200

SW4

SW5

SW6

Data length (bit)

STOP bits (bit)

Parity type

0

0

0

7

2

Even

0

0

1

7

2

Odd

0

1

0

7

1

Even

0

1

1

7

1

Odd

1

0

0

8

2

None

1

0

1

8

1

None

1

1

0

8

1

Even

1

1

1

8

1

Odd

SW7

Local communications mode setting

1

Speed priority mode

0

Distance priority mode

The setting of SW7 is only valid if the EEPROM-type (batteryless-type) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (battery-type) DC. Refer to the R/W Head Manual and Data Carrier Manual for details. SW7 must be set to OFF when the V620 is used. SW8 is not used. (Keep it switched OFF.) DIP Switch 2

SW1

SW2

0

0

Synchronous condition OFF (LL level)

0

1

ON (HL level)

1

0

Trailing edge

1

1

Leading edge

SW3 through SW7 are not used. (Keep them switched OFF.) Before setting the switches, be sure to turn OFF the Power to the ID Controller. The switch settings are read when Power is switched ON. To change the switch settings, turn OFF the Power once, change the setting, and then turn ON the Power again.

13

Page 23

Section

DIP Switch Setting

3-1

Modes The ID Controller operates in two Modes: RUN and TEST Modes. RUN Mode

In this Mode, the ID Controller operates as specified upon a command sent from the host controller, and sends the result of the operation to the host controller as a response. Response ID Controller Host controller

Command

TEST Mode

Communications testing can be conducted between the ID Controller and a DC in the off-line state. The ID Controller repeatedly communicates with a DC at 1-second intervals. During communication with the DC, the HEAD Indicator lights. When the processing has been completed, an end code, which is the result of the processing, is displayed on the monitor. ID Controller Host controller

In the TEST Mode, two kinds of tests can be conducted: Read and Write Tests. The Read Test repeatedly reads 1-byte data, while the Write Test repeatedly writes 1-byte data. At this time, however, the contents of the DC’s data have not changed. Use this TEST Mode for initial checking of the system.

Write Command Memory A write command executed by this Controller is recorded until either the next write command or the Power reset is executed. The write commands of the Controller include write, auto write, and polling write commands. The recorded write command can be executed by a repeat command.

ID Controller Memory contents

Operation (Memory initialization)

(Power ON) Write command 1

Write command 1

Execution of Write command 1

Repeat command

Write command 1

Execution of Write command 1

Read command

Write command 1

Execution of Read command

Repeat command

Write command 1

Execution of Write command 1

Write command 2

Write command 2

Execution of Write command 2

Manipulation

14

Page 24

Section

DIP Switch Setting

3-1

Trigger Input The ID Controller is provided with a trigger input that informs the Controller when to start processing the DC. After receiving a command from the host controller, the ID Controller waits until the conditions of this trigger input are satisfied, and then starts communications with the DC.

N

Command reception Y

N

Trigger input active Y Command processing

Response processing

Note Even if there are changes to the trigger input status while the ID Controller is processing a command, processing is not suspended. The condition of the trigger input can be specified to be L level (OFF) or H level (ON) by using a DIP switch. Command reception

Command processing starts

Trigger input wait (a) (L level active) (b) (H level active) (c) (Leading edge active) (d) (Trailing edge active)

When the auto command is used, the ID Controller waits for the DC approach after the trigger input has become active. Consequently, the Controller does not perform Read/Write processing even if a DC approaches before the trigger input becomes active. Auto command reception

Trigger input active

Trigger input wait*

DC approaches

Waits until DC approaches

Response transmission

DC communications processing

*The ID Controller does not perform processing even when a DC approaches in the trigger input wait state. Note When the trigger input is not used, set the trigger condition to L level, and open the TRG terminal (set pins 1 and 2 of DIP switch 2 to the OFF positions).

15

Page 25

Section

Mounting of ID Controller

3-2

3-3

Installation Environment Although the ID Controller has a high reliability and strong environmental durability as a control component, take the following into consideration when installing the ID Controller in order to improve the reliability of the overall system and to make the best use of its functions:

Installation Location Do not install the ID Controller at the following locations: • Where the temperature falls below –10°C or rises above +55°C, or where the temperature fluctuation is great and condensation is generated. • Where the relative humidity falls below 35% or exceeds 85%. • Where it is subject to corrosive gas, flammable gas, dust, salt, and iron chips. • Where it is subject to direct vibration or shock. • Where it is subject to direct sunlight. • Where it is subject to splashes of water, oil, and chemical substances.

Mounting Position in a Control Panel The operating temperature range of the ID Controller is from –10°C to +55°C. When installing the Controller in a control panel, pay attention to the following points: • Provide enough space around the Controller for ventilation purposes. • Do not install the Controller in the vicinity of equipment generating heat (such as heaters, transformers, and large resistors). • If there is a possibility that the temperature exceeds +55°C, install a fan or air conditioner for forced cooling.

3-3

Mounting of ID Controller

Panel Mounting

53

68

81 115

80 Two, M4

ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ ÉÉ

When installing the ID Controller in a control panel, be sure to use plane washers and M4 screws.

16

Page 26

Section

Connecting Connector

3-4

DIN Rail Mounting DIN rail

80 End plate

Mounting hook

Spacer

A

Recommended DIN rail

B

1, 2, 3...

1. To mount the ID Controller on a DIN rail, first engage part A, and then push the ID Controller in direction B. 2. To remove the Controller from the DIN rail, pull the mounting hook of the Controller toward you.

3-4

Connecting Connector

To Connect

Rubber mold

1, 2, 3...

1. Hold the rubber mold of the connector and insert the connector into the mating connector on the ID Controller. 2. Push the connector straight in until it is locked. Note The connector is not locked when it is pushed while holding the ring. Be sure to hold the rubber mold.

17

Page 27

Section

Wiring

3-5

To Disconnect

Ring

To remove the connector, pull it straight out while holding the ring. Note The connector must not be pulled while holding the rubber mold. If an excessive force is applied to the cable, the cable may break or become damaged.

3-5

Wiring

Power Supply Line and Ground Line Line filter

Grounding at less than 100 Ω

M3.5 screws are used for the Power and ground terminals. In the case of solderless terminals, use the following. Keep the tightening torque to within 8 kg-cm. 7.0 max.

M3.5 7.0 max.

Supply 24 VDC to the ID Controller. Make sure that the voltage fluctuation is within the range of 20.4 to 26.4 VDC (24 VDC+10%/–15%). The countermeasures against noise provided to the IC Controller is sufficient to suppress noise superimposed on power lines. However, by supplying power through a filter, noise can be substantially reduced. The power dissipation of the ID Controller is 7.2 W maximum with a maximum configuration. Note, however, that an inrush current of about 20 A (at 24 VDC)

18

Page 28

Section

Wiring

3-5 flows into the ID Controller upon Power application. Take appropriate measures against the inrush current. Use a power cable 2 mm2 diameter minimum to prevent voltage drops. The use of twisted pair cables is recommended. To improve noise immunity, ground at less than 100 Ω. For a ground cable, use a cable of 2 mm2 diameter minimum (green cable), and keep the cable length to within 20 m. Recommended Power Supply (Small, DIN Rail Type) <OMRON> Model

Output

Input voltage

S82K-0124

24 VDC, 0.6 A

100 VAC

S82K-2124

24 VDC, 0.6 A

200 VAC

Note Although the rated power dissipation of the ID Controller is 24 VDC, 0.3 A (7.2 W), take into consideration the power supply ratings taking the inrush current into the ID Controller. Use a power supply of 24 VDC, 0.6 A minimum.

Input and Output lines RESET Signal Input

+ RESET input

24 VDC

+ 24 VDC To ERROR output

Make sure that the input voltage of the RESET signal does not exceed the maximum voltage (26.4 V). If this is exceeded, the ID Controller may malfunction. To improve the noise immunity, separate the wiring of the input lines from hightension equipment or power lines. ERROR Signal Output The maximum switching capacity of the output terminals is 24 VDC (+10%/–15%), 100 mA. If a voltage or load that exceeds the maximum switching capacity is used, the ID Controller may malfunction. Use of an auxiliary relay (24 VDC, 100 mA max.) in the output circuit is recommended.

19

Page 29

Section

RS-232C Interface Connection

3-6

Solderless I/O Terminal The I/O terminals employ M3.5 screws. When using solderless terminals, use the following: 7.0 max.

(M3.5) 7.0 max.

Keep the tightening torque to within 8 kg-cm.

3-6

RS-232C Interface Connection Signal name

Abbr.

I/O

Pin no.

Ground

GR

–––

1

Signal ground

SG

–––

9

Send data

SD

Output

2

Receive data

RD

Input

3

Request to send

RS

Output

4

Clear to send

CS

Input

5

ID Controller

Host computer

GR

FG

SG

SG

SD

SD

RD

RD

RS

RS

CS

CS (Shielded cable)

Note

5

1

9

6

1. Ground the shielded cable at either the ID Controller side or host computer side to prevent malfunctioning. The above left figure shows an example of shielded cable grounding at the ID Controller side. 2. Internally short-circuit pins 4 (RS) and 5 (CS).

Assembly and Connection of Communications Connector ID Controller side

Host computer side Cable

Recommended cable 5PX28AWG, 7 dia. Plug XM2A-0901* (supplied as an accessory) (OMRON)

Hood XM2S-0911* (supplied as an accessory) (OMRON)

*Use the accessory connector as the communications connector. Separately prepare the connecting cable and the connector of the host computer. The connector of the ID Controller is made by OMRON and takes countermeasures against EMI.

20

Page 30

Section

RS-232C Interface Connection

3-6

Assembly of Connector 1, 2, 3...

1. Process the ends of the cables. 40

35

5

Core Shield mesh Shield tape

10±1 12

Cable bushing

• Run the cable bushing through the cable in advance. • Loosen the shield mesh and return it on the cable bushing. At this time, keep the returning length to about 10 mm. • Wind the shield tape onto the shield mesh. 2. Solder the cores of the cables to the pins.

Plug Crossover line

Pin no.

Abbr.

Cable bushing Aluminum tape

Signal name

1*

GR

Frame ground

9

SG

Signal ground

2

SD

Send data

3

RD

Receive data

4**

RS

Request to send

5**

CS

Capable to send

*GR is grounded to the connector hood and is therefore connected to the GR of the ID Controller through the connector hood. It is therefore unnecessary to connect GR to pin 1. **Short-circuit pins 4 (RS) and 5 (CS) with a crossover line. 3. Set the plug to the housing A2 of the hood and clamp the aluminum tape.

Lock screw (2-M2.6)

Housing A2 Cable clamp

Housing B2

4. Set the two connector tightening screws and attach housing B2 to A2 to complete the connector.

21