The text of a manual · part 2 of 11

4700 Series Installation and Operating Manual for MC4700, MCF4700, MCJ4700, MS4700 & MSF4700 Series, pages 11 to 20

Pages 11 to 20 of 101

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron MC4700

Page 11

.....

1

1 I MPORTANT S AFETY W ARNINGS !! WARNING! Read and understand this section prior to installing a 4700 system. ▲

A 4700 system is a general purpose presence sensing device designed to guard personnel working around moving machinery. Whether a specific machine application and light curtain installation complies with safety regulations depends on the proper application, installation, maintenance and operation of the light curtain. These items are the responsibility of the purchaser, installer and employer. The employer is responsible for the selection and training of personnel to properly install, operate, and maintain the machine and its safeguarding systems. A 4700 system should only be installed, verified and maintained by a qualified person. A qualified person is defined as “a person or persons who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training or experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.” (ANSI B30.2-1983) To use a 4700 series safety light curtain the following requirements must be met:, The guarded machine must be able to stop anywhere in its cycle. Do not use a safety light curtain on a press with a full-revolution clutch., The guarded machine must not present a hazard from flying parts., The guarded machine must have a consistent stopping time and adequate control mechanisms., Severe smoke, particulate matter and corrosives may degrade the efficiency of a safety light curtain. Do not use a 4700 system in this type of environment., All applicable governmental and local rules, codes, and regulations must be satisfied. This is the employer’s responsibility., All safety-related machine control elements must be designed so that a alarm in the control logic or failure of the control circuit does not lead to a failure to danger., Additional guarding may be required for access to dangerous areas not covered by the 4700 series system., Perform the STI test procedure at installation and after maintenance, adjustment, repair or modification to the machine controls, tooling, dies or machine, or the 4700 series system., Perform only the test and repair procedures outlined in this manual., Follow all procedures in this manual for proper operation of the 4700 series system. The enforcement of these requirements is beyond the control of STI. The employer has the sole responsibility to follow the preceding requirements and any other procedures, conditions and requirements specific to his machinery.

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev.D

9

Page 12

2

2

2 S IGNIFICANT F EATURES 2.1 S T A N D A R D F E A T U R E S Individual Beam Indicators External Device Monitoring (MPCE Monitoring) Automatic Start Mode Start Interlock Mode Start/Restart Interlock Mode Adjustable Mounting Brackets Floating Blanking Exact Channel Select Two Safety (PNP) Outputs Auxiliary Output Start Switch Input Selectable NO or NC

2.2 O P T I O N A L F E A T U R E S Relay Safety Outputs (Metal Chassis Controllers only) DeviceNet Multi-Channel Select (Non-CE)

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev. D

10

Page 13

.....

3 S YSTEM A CCESS , C OMPONENTS AND

3

I NDICATORS 3.1 A C C E S S T O C O N F I G U R A T I O N S W I T C H E S 3.1.1

LCM DIN C ONTROLLER

Switches for configuring system features are located under the front cover of the controller. Access to these switches is gained by the following procedure: 1. Remove the four screws holding the cover in place (see Figure 3-1 for location). 2. Place the blade of a thin flat-blade screwdriver between the cover and the main controller housing and gently lift the cover off. See Figure 3-1 for detail. The cover is not hinged and will be completely removed. To replace the cover: 1. Correctly position one end and push down on the opposite end to snap it in place. 2. Replace the four screws to properly retain the cover.

Figure 3-1 Accessing the Configuration Switches on the LCM DIN Controller

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev.D

11

Page 14

3

3.1.2

LCM M ETAL C HASSIS C ONTROLLER

Switches for configuring system features are located inside the front cover of the controller. Access to these switches is gained by the unlocking the clasp on the right-hand side of the controller box. The Clasp has provisions to accept a user-provided padlock. Only a qualified p erson should have possession of the key to the padlock, or to the optional Program/Start keyswitch.

R

Scientific Technologies Inc, Fremont, CA 94555 U.S.A. 1/888/510-4357

!

W http://www.sti.com

A

R

N

I

N

G

RUN PROGRAM

START

RUN STOP INTERLOCK FB/CS

Optional Keyswitch

Diagnostic Codes: 00 Normal Operation 01 Normal Operation, waiting for Start signal 02 Normal Operation, Floating Blanking active 03 Normal Operation, Exact Channel Select active 04 Normal Operation, Exact Channel Select and Floating Blanking active 20 General DIP switch fault 21 Invalid switch setting 22 DIP switch settings changed during operation 23 Invalid Channel Select or MPCE switch settings

30 40 41 43 50 51 52 53

General Safety Output fault General MPCE fault MPCE open before safety output (OSSD) activation MPCE open when power is applied Internal controller fault Receiver fault Transmitter fault Transmitter and receiver length mismatch or transmitter and receiver not connected 59 24 VDC power supply fault

TEST PROCEDURE To test the light curtain, use the appropriate STIsupplied test object, or properly sized opaque cylindrical object. If you are using the Channel Select or Floating Blanking features and the object to be ignored does not completely prevent access to the hazardous area, either (1) use a mechanical guard or other means to block access or (2) increase the minimum safe distance and use a larger test object diameter as explained in the Installation and Operating Manual. 1. Disable the machine. Power on the light curtain. 2. Inspect the machine to ensure entry to the hazardous area is only through the light curtain sensing field. If not, additional guarding, including mechanical barriers may be required. 3. Verify that the mounting distance of the light curtain is equal to or greater than the minimum safe distance from the hazardous point. Ensure the operator is not able to stand undetected between the light curtain and the hazard. 4. Check for external damage to the light curtain, the machine, electrical cables and wiring. 5. Interrupt the sensing field with the test object to check the effectiveness of the light curtain. Move the test object inside the perimeter (along the top, sides and bottom) of the sensing field and up and down through the center of the sensing field. Verify that the Red indicator is ON and the Green indicator is OFF while the test object is anywhere in the sensing field. watch for any unprotected access to the point of hazard. 6. Start the machine. Interrupt the sensing field with the test object. The machine should stop immediately. Never insert the test object into the dangerous parts of the machine! With the machine at rest, interrupt the sensing field with the test object. that the machine will not start with the test object in the sensing field. 7. Ensure the braking and machine stop systems are working properly in accordance with the machine manufacturer s requirements. If the machine does not stop fast enough, adjust the braking system or increase the distance from the light curtain to the point hazard. 8. If the safety devices or machine fail any of these tests, do not run the machine. Immediately lockout the machine to prevent its use and notify the supervisor 9. If the Channel Select is reprogrammed or disabled, you must repeat these test procedures. 10. Close and lock the light curtain contr enclosure door, if applicable.

Clasp

Do Not Remove Or Cover This Label STI Label P/N 28621-0010 re

Figure 3-2 Accessing the Configuration Switches on the LCM-Metal Chassis Controller

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev. D

12

Page 15

..... 3.2 L O C A T I O N O F T H E C O M P O N E N T S A N D I N D I C A T O R S Refer to Figure 3-3, Figure 3-4 and Figure 3-5 for the location of the components and indicators listed below.

Table 3-1 System Component Identification for the 4700 Transmitter and Receiver Chart #

1

RECEIVER

2

Individual Beam Indicators (one for each beam) – Red

3

Channel Select or Floating Blanking Indicator – Amber

4

Interlock or Fault Indicator – Yellow

5

Machine Stop Indicator – Red

6

Machine Run Indicator – Green

7

TRANSMITTER

8

Detection Zone

RECEIVER

DETECTION ZONE

RECEIVER TRANSMITTER

DETECTION ZONE "A"

3. GRN

1. AMBER 2. YEL

4. RED

1. CHANNEL SELECT or FLOATING BLANKING INDICATOR-AMBER 2. INTERLOCK or FAULT INDICATOR-YEL 3. MACHINE STOP INDICATOR-RED 4. MACHINE RUN INDICATOR-GRN

RX

MS4700

LED INDICATORS

MS4700

4. RED - STOP/BLOCKED

RX LED INDICATORS TRANSMITTER

MC4700

3. GRN - RUN/CLEAR

MC4700

1. AMBER - FLOATING BLANKING OR CHANNEL SELECT 2. YEL - INTERLOCK

1

GRN

AMBER 2

YEL

RED

4

3

TX

Figure 3-3 4700 Transmitter and Receiver

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev.D

13

Page 16

3

Table 3-2 System Component Identification for the LCM-1, LCM-2 and LCM-3 Controllers Chart #

4

EXact Channel Select 1 beam

5

EXact Channel Select 2 beams

6

EXact Channel Select 3 beams

7

EXact Channel Select Return

9

Channel Selector Floating Blanking Indicator - Amber

10

Interlock or Alarm Indicator - Yellow

11

Machine Stop Indicator - Red

12

Machine Run Indicator - Green

13

Diagnostic Code Display

14

Switch A

15

Program Button

16

Switch B

17

Removable Terminal Blocks for input and output connections

18

DeviceNet status indicators (optional)

19

Start Switch Type Jumper

20

Relay Board (metal chassis only)

21

Power In (metal chassis only)

22

MPCE Monitoring (metal chassis only)

23

Multi-channel Select terminals

24

Optional Keyswitch

NOTE: For DeviceNet Option, LCM-2 Series, Terminals 13 to 17 are indicated below.

NOTE: For Multi Channel Select Option, LCM-3 Series, Terminals 4 to 7 are indicated on below. Channel Select

DeviceNet

5

4

ECS 2

ECS 1

DATA H

6

CS Prog

Not Used

13

12

11

10

9

8

7

6

5

4

Not Used

Not Used

MPCE

MPCE RETURN

START RETURN

START

PROG RET

PROGRAM

Not Used

Not Used

Power

3

2

1

+24 VDC

0 VDC

Remote

14 DATA

Not Used

MPCE

16 15 Not Used

RS232

17

9

7

PROGRAM

13

ECS Return

14

CAN +

CAN V - 16 15 DATA L

17

WARNING SAFETY DEVICE not defeat or bypass. Severe injury to ! Dopersonnel could result.

R

LCM-1 Series

Scientific Technologies Inc.

FB/CS

Run

Stop

Fremont, CA, USA Tel: 510/608-3400, Fax: 510/744-1442 www.sti.com

Output

Xmtr

Xmtr/Rcvr

Rcvr

31

32

33

34 RED

30

YELLOW

29

GRAY

28

VIOLET

27

TAN

26

PINK

25

BROWN

24

BLACK

AUX1 OUT

23

SHIELD

OSSD RETURN

OSSD 2

22

WHITE

21

AUX2 OUT

20

BLUE

19

ORANGE

18 OSSD 1

12

Interlock

11

23

13

10

19 1 2 3

18

13 14 17

16 15

Figure 3-4 DIN Controller Components

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev. D

14

Page 17

..... Inside Front Lid of the metal chassis controller 19 J1 N.C. N.O.

START

8 7 6 5 4 3 2 1

15 J2 KEYSWITCH

PROGRAM

TB5

RX

R

Scientific Technologies Inc, Fremont, CA 94555 U.S.A. 1/888/510-4357

13

W

R

N

I

N

23

G

TB7

-Note: Shown with optional Relay Board.

RUN PROGRAM

18

J3 http://www.sti.com

A

TB6

TX

OPTIONAL DEVICENET BOARD

J1

!

5 4 3 2 1

START

SWA

1 MCS 2 1 2 PROG 1 START 2 1 MPCE 2

SWB

22 MPCE MON JMP2

RUN

OFFON

STOP INTERLOCK FB/CS

24 Diagnostic Codes: 00 Normal Operation 01 Normal Operation, waiting for Start signal 02 Normal Operation, Floating Blanking active 03 Normal Operation, Exact Channel Select active 04 Normal Operation, Exact Channel Select and Floating Blanking active 20 General DIP switch fault 21 Invalid switch setting 22 DIP switch settings changed during operation 23 Invalid Channel Select or MPCE switch settings

30 40 41 43 50 51 52 53 59

General Safety Output fault General MPCE fault MPCE open before safety output (OSSD) activation MPCE open when power is applied Internal controller fault Receiver fault Transmitter fault Transmitter and receiver length mismatch or transmitter and receiver not connected 24 VDC power supply fault

12 11 10 9

14

16 K1

P2 K2

PS1

AUX

20

TEST PROCEDURE To test the light curtain, use the appropriate STIsupplied test object, or properly sized opaque cylindrical object. If you are using the Channel Select or Floating Blanking features and the object to be ignored does not completely prevent access to the hazardous area, either (1) use a mechanical guard or other means to block access or (2) increase the minimum safe distance and use a larger test object diameter as explained in the Installation and Operating Manual. 1. Disable the machine. Power on the light curtain. 2. Inspect the machine to ensure entry to the hazardous area is only through the light curtain sensing field. If not, additional guarding, including mechanical barriers may be required. 3. Verify that the mounting distance of the light curtain is equal to or greater than the minimum safe distance from the hazardous point. Ensure the operator is not able to stand undetected between the light curtain and the hazard. 4. Check for external damage to the light curtain, the machine, electrical cables and wiring. 5. Interrupt the sensing field with the test object to check the effectiveness of the light curtain. Move the test object inside the perimeter (along the top, sides and bottom) of the sensing field and up and down through the center of the sensing field. Verify that the Red indicator is ON and the Green indicator is OFF while the test object is anywhere in the sensing field. watch for any unprotected access to the point of hazard. 6. Start the machine. Interrupt the sensing field with the test object. The machine should stop immediately. Never insert the test object into the dangerous parts of the machine! With the machine at rest, interrupt the sensing field with the test object. that the machine will not start with the test object in the sensing field. 7. Ensure the braking and machine stop systems are working properly in accordance with the machine manufacturer s requirements. If the machine does not stop fast enough, adjust the braking system or increase the distance from the light curtain to the point hazard. 8. If the safety devices or machine fail any of these tests, do not run the machine. Immediately lockout the machine to prevent its use and notify the supervisor 9. If the Channel Select is reprogrammed or disabled, you must repeat these test procedures. 10. Close and lock the light curtain contr enclosure door, if applicable.

0SSD1 0SSD2 RV1 R45 R44

C9

17

AUX

TB2

TB1 F1

TB3

C8 L

N

21 TB1

TB4

Do Not Remove Or Cover This Label STI Label P/N 28621-0010 re

+

_

Shown with DC Solid State Configuration Note: For Solid State Configuration, JMP2 and PS1 are not available.

Figure 3-5 Metal Chassis Controller Components

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev.D

15

Page 18

4

4

4 S YSTEM O PERATION

The 4700 system is a microprocessor-controlled, infrared transmitted-beam safety light curtain. The system consists of a receiver assembly and a transmitter assembly. Quick disconnect cables link the controller to the transmitter and receiver. The safety light curtain is often used where personnel protection is required. Typical applications include mechanical power presses, robotic work cells, filter presses, injection molders, food processing equipment and automated assembly equipment.

4.1 O P E R A T I N G S T A T E S The operating condition of a 4700 system is described in terms of states. The following operating states exist for the 4700 system. 4.1.1

M ACHINE R UN

The two system safety outputs are in the ON state, the green machine run indicator is lit, and the auxiliary output is in a state consistent with its configuration. See Section 7 on page 27. The protected machine is allowed to operate. Pressing and releasing the start button has no effect. 4.1.2

M ACHINE S TOP

☛

The two system safety outputs are in the OFF state, the red machine stop indicator is lit, and the auxiliary output is in a state consistent with its configuration. See section Section 7 on page 27. The protected machine is not allowed to operate. Press and releasing the start switch has no effect. 4.1.3

I NTERLOCK

The two system safety outputs are in the OFF state, the red machine stop indicator and yellow interlock indicator are lit. The auxiliary output is in a state consistent with its configuration. See Section 7 on page 27. The interlock state does not allow the protected machine to operate until the detection zone is clear of obstructions and the start button is pressed and released. 4.1.4

A LARM

The two system safety outputs are in the OFF state, the red machine stop indicator is lit, the yellow interlock indicator is flashing, and the auxiliary output is in the OFF state. The alarm state does not allow the protected machine to operate. The primary difference between alarm and interlock is that the 4700 system will remain in the alarm state until power is recycled or the start switch is pressed and released and the system has run a self-test.

4.2 O P E R A T I N G M O D E S System operating modes determine the start-up and operating behavior of the 4700 system. Operating mode definitions rely on the operating states presented above. Operating mode selection is performed via configuration switches under the front cover of the controller. NOTE! If internal faults are detected by the 4700 system during power-up or operation, it will enter the alarm state with its safety outputs in the OFF state. 4.2.1

A UTOMATIC S TART

The 4700 system will power-up with its safety outputs OFF, and perform system initialization and self tests. The 4700 system will enter the machine run state if no obstructions are present in the detection zone. In this state, when an object is sensed entering the detection zone, the 4700 system will change from machine run to machine stop and remain in this state until the obstruction is R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev. D

16

Page 19

..... removed. Once the detection zone is clear, the 4700 system will automatically change from machine stop to machine run. 4.2.2

S TART I NTERLOCK

The 4700 system will power-up with its safety outputs OFF and perform system initialization and self-tests. If no obstructions are detected in the protected zone, (or an exact channel select pattern satisfied), the 4700 system enters the interlock state. To enter the machine run state, the detection zone must be clear (or an exact channel select pattern satisfied), and then the operator must press and release the start switch. In the machine run state, when an object is sensed entering the detection zone the 4700 system will change from machine run to machine stop. Once the detection zone is clear, the 4700 system will automatically change from machine stop to machine run. 4.2.3

S TART /R ESTART I NTERLOCK

The 4700 system will power-up with its safety outputs OFF, and, if no faults are detected, enter the interlock state. To enter the machine run state, the detection zone must be clear (or an exact channel select pattern satisfied), and then the operator must press and release the start switch. In the machine run state, when an object is sensed entering the detection zone the 4700 will change from machine run to interlock. The 4700 system will remain in the interlock state even after the obstruction is removed from the detection zone. To enter the machine run state, the operator must press and release the start switch. If any obstruction is present in the detection zone when the start switch is pressed and released, the 4700 will remain in the interlock state. NOTE! The definitions above mention a start switch. See Section 10–“Connecting to the Machine Control Circuit” for wiring of the start switch. Power-Up

No

Start Pressed & Released

Yes

Power-On Self-Test

Machine run Yes

Fault

Failure Yes

No

Yes

Yes

Machine Stop

Failure

Failure

Beam blocked

Yes

No Beam Cleared

No Start/ Restart Interlock

Yes

No

Yes Yes

Failure

Interlock No

Yes

Beam Blocked

No

Start Pressed & Released

Yes

Figure 4-1 Functional Flow Diagram

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev.D

17

Page 20

5

4.3 O P E R A T I N G M O D E S E L E C T I O N Operating mode is selected by setting positions 1 and 2 of Switches A and B, located under the controller cover. Refer to Table 4-1. Any mismatch between the settings of Switch A and B will result in an alarm condition. In addition, if the configuration switch settings change while the system is on, it will enter the alarm state with the safety outputs off. ! Warning! Disconnect power before accessing the controller assembly. ▲ Table 4-1 Operating Mode Switch Settings SWITCH A

SWITCH B

OPERATING MODE

1

2

1

2

Automatic Start (default setting)

CLOSED/ON

CLOSED/ON

CLOSED/ON

CLOSED/ON CLOSED/ON

Start interlock

OPEN/OFF

CLOSED/ON

OPEN/OFF

Start/Restart interlock

OPEN/OFF

OPEN/OFF

OPEN/OFF

OPEN/OFF

Not Allowed

CLOSED/ON

OPEN/OFF

CLOSED/ON

OPEN/OFF

4.4 S T A R T S W I T C H T Y P E S E L E C T I O N The type of Start switch (Normally Open or Normally Closed) used by the 4700 system is selectable by a jumper located under the controller cover. Refer to Figure 3-4 - DIN Controller Components and Figure 3-5 - Metal Chassis Controller Components. Placing the jumper between Pins 1 and 2 of JMP 1 selects a Normally Closed Start Switch. Placing the jumper between 2 and 3 selects a Normally Open Start switch. Note: If there is a mismatch between the type of Start selected and used, (i.e. jumper between Pins 1 and 2 and Normally Open Start Switch used) the switch must be pressed and released twice before the system will enter a Run state.

5

5 D ETECTION O PTIONS

! Warning! Use of Exact Channel Select and/or Floating Blanking will make the 4700 ▲ system less sensitive to objects in the detection zone. Improper use of either can result in severe injury to personnel. Exact Channel Select may require a hard barrier guard (see Section 5.8 - Additional Guarding When Using Exact Channel Select), Exact Channel Select or Floating Blanking requires an increase in the safety distance. Read the following section carefully. - To prevent unauthorized modification of the detection zone. The system controller should be installed in an enclosure with supervisor-controlled access. - If the object to be ignored by the Channel Selected beams does not completely prevent access to the hazardous area, then either use a hard guard or other means to block access or increase the minimum safe distance as required by the proper formula. - Any beams which are not in alignment at the time of Channel Select programming may be inadvertently deselected. Use the STI Test Procedure to verify the correct configuration. - Floating Blanking increases the minimum safety distance therefore test object size will increase.

R

SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada

© STI 0806 PN99584-0050 Rev. D