Page 47
Dedicated I/O Units
Analog Input Unit CQM1-AD041
Analog Input Unit
CQM1-AD041 The CQM1-AD041 Analog Input Unit retrieves four analog signals from sensors or measuring equipment. Use this Unit in combination with a Power Supply Unit.
Performance Specifications Item
Specification
No. of analog input points
4 or 2 (selected with DIP switch)
Input signal range
Voltage input
–10 to +10 V 0 to 10 V 1 to 5 V
Current input
4 to 20 mA
Input impedance
Voltage input
1 MΩ min.
Current input
250 Ω
Resolution
1/4000
Accuracy
±1.0%
Conversion speed
2.5 ms/1 pt.
Internal current consumption
80 mA max. at 5 V DC
System Configuration Example CQM1-AD041 Analog Input Unit
Liquid flow
CQM1-IPS02 Power Supply Unit
CQM1-DA021 Analog Output Unit
K3T@ Intelligent Signal Processor
Pressure Temperature Current Voltage Power
50
K3FK Signal Transmitter
Temperature recorder 3G3@V Inverter
Page 48
Dedicated I/O Units
Analog Output Unit CQM1-DA021
Analog Output Unit
CQM1-DA021 A single Analog Output Unit makes twopoint digital-to-analog conversion possible at a speed of 0.5 ms/two points. Use the Analog Output Unit together with the Power Supply Unit.
Performance Specifications Item No. of analog output points Output signal range
Specification 2 Voltage output
–10 to 10 V
Current output
0 to 20 mA
External output permissible load resistance
Voltage output
1 kΩ min.
Current output
520 Ω max. (including wiring impedance)
External output impedance
Voltage output
0.5 Ω max.
Resolution
Voltage output
1/4096
Current output
1/2048
Accuracy
±1.0%
Conversion speed
0.5 ms/2 points
Internal current consumption
90 mA at 5 V DC
System Configuration Example CQM1-AD041 Analog Input Unit
Liquid flow
CQM1-IPS02 Power Supply Unit
CQM1-DA021 Analog Output Unit
K3T@ Intelligent Signal Processor
Pressure Temperature Current Voltage
K3FK Signal Transmitter
Temperature recorder 3G3@V Inverter
Power
51
Page 49
Dedicated I/O Units
Power Supply Units CQM1-IPS01/IPS02
Power Supply Units
CQM1-IPS01/IPS02 The Analog Input and Output Units require a Power Supply Unit. There are two kinds of Power Supply Units (i.e., a Power Supply Unit connecting to a single Analog Unit and the other one connecting to two Analog Units).
Specifications Item
Specification
Internal current consumption
CQM1-IPS01 Connecting to a single Analog 5 V DC 420 mA max. Unit. CQM1-IPS02 Connecting to two Analog Units.
5 V DC 950 mA max.
Note: The CQM1-IPS02 connects to a maximum of two Analog Input Units. A single Analog Input Unit and single Analog Output Unit can be connected to the CQM1-IPS02 Power Supply Unit. Two Analog Output Units cannot be connected to the CQM1-IPS02 Power Supply Unit. When using two Analog Output Units, prepare two CQM1-IPS01 Power Supply Units.
System Configuration Example CQM1-AD041 Analog Input Unit
Liquid flow
CQM1-IPS02 Power Supply Unit
CQM1-DA021 Analog Output Unit
K3T@ Intelligent Signal Processor
Pressure Temperature Current Voltage Power
52
K3FK Signal Transmitter
Temperature recorder 3G3@V Inverter