Dedicated I/O Units
CompoBus/S Master Unit CQM1-SRM21-V1
CompoBus/S Master Unit
CQM1-SRM21-V1 The CompoBus/S Master Unit supports both a High-speed Communications Mode and a Long-distance Communications Mode. • Number of I/O points per Master: 128 max. (may be set to 64 or 32 points) • Number of Slaves per Master: 16 or 32 • Communications cycle time: 0.5 ms max. (baud rate: 750 kbps) • Communications distance: 500 m max. (baud rate: 93.75 kbps) • Supports Analog Terminal connections.
Communications Specifications Communications protocol
Dedicated CompoBus/S protocol
Code
Manchester code
Connection method
Multi-drop, T-type bifurcation (both methods require external terminating resistor) (See note 1.)
Baud rate
750 kbps, 93.75 kbps (selectable with a DIP switch) (See note 2.)
Communications cycle time
High-speed Communications Mode
0.5 ms (with a maximum number of 8 Input and 8 Output Slaves) 0.8 ms (with a maximum number of 16 Input and 16 Output Slaves)
Long-distance Communications Mode
4.0 ms (with a maximum number of 8 Input and 8 Output Slaves) 6.0 ms (with a maximum number of 16 Input and 16 Output Slaves)
Cable
Two-conductor cable (VCTF 0.75 x 2), four-conductor cable (VCTF 0.75 x 4), or dedicated flat cable
Communications distance
High-speed Communications Mode
Two-conductor VCTF cable
Communications Mode
Trunk line length
Branch line length
Total line length
High-speed mode
100 m max.
3 m max.
50 m max.
Long-distance mode
500 m max.
6 m max.
120 m max.
Dedicated flat cable/ four-conductor VCTF cable Trunk line length
Branch line length
Total line length
High-speed mode (see note 3)
30 m max.
3 m max.
30 m max.
Long-distance mode (see note 4)
Free branching (total cable length: 200 m max.)
Communications Mode
Max. number of connectable nodes
32
Error control
Manchester code, frame length, and parity checks
Note: 1. 2. 3. 4.
An external Terminating Resistor is required. Setting must be made using the DIP switch. (Change the DM setting for selecting the communications mode. Default setting: 750 kbps) If the number of Slaves connected is smaller than 16, the trunk line length can be less than 100 m and the total line length can be less than 50 m. There are no restrictions on the branching method, trunk line length, branch line length, or total line length. Connect the Terminating Resistor farthest from the Master.
53
Page 51
Dedicated I/O Units
CompoBus/S Master Unit CQM1-SRM21-V1
Master Unit Specifications Internal current consumption
180 mA max. at 5 V DC
Number of I/O points
128 points (64 inputs and 64 outputs), 64 points (32 inputs and 32 outputs), or 32 points (16 inputs and 16 outputs) selectable with a switch.
Number of occupied words
128 points:4 input words and 4 output words 64 points:2 input words and 2 output words 32 points:1 input word and 1 output word
Number of points per node
8 or 4 points (selectable with a switch)
Max. number of connectable Slaves
32 (with 4 points per node)
Status data
Alarm terminal output
Weight
200 g max.
Note: For details regarding CompoBus/S, refer to the CompoBus/S catalog (Catalog number: Q103-E1-@)
Connections with Flat Cable Master
CQM1H
Master Unit (64 inputs and 64 outputs max. points)
Slaves
Remote I/O Terminal (Transistor model: 4/8 inputs and 4/8 outputs)
Sensor Terminals (4/8 sensor inputs)
Bit Chain Terminals (8 inputs and 8 outputs)
Remote I/O Terminal (Relay model: 8/16 outputs)
B1T Slave
B1T terminator
Press-fit connector for bifurcation Press-fit connector with terminating resistor
54
Dedicated flat cable
Page 52
Dedicated I/O Units
CompoBus/S Master Unit CQM1-SRM21-V1
Connections with VCTF Cable Master
CQM1H
Master Unit (64 inputs and 64 outputs max.)
Slaves Remote I/O Terminal (Transistor model: 4/8 inputs and 4/8 outputs)
Sensor Terminals (4/8 sensor inputs)
Bit Chain Terminals (8 inputs and 8 outputs)
B1T Slave Remote I/O Terminal (Relay model: 8/16 outputs) Multiple bifurcation
T-type bifurcation
B1T terminator
Multi-drop branching Press-fit connector with terminating resistor
Note: For details regarding CompoBus/S, refer to the CompoBus/S catalog (Catalog number: Q103-E1-@)