Page 53
Dedicated I/O Units
DeviceNet I/O Link Unit CQM1-DRT21
DeviceNet I/O Link Unit
CQM1-DRT21 The DeviceNet I/O Link Unit is a DeviceNet slave that conforms to the multivender DeviceNet standards. DeviceNet I/O Link Units can be used to connect one or more CQM1H PLCs to a DeviceNet Master.
Performance Specifications Communications power supply voltage
11 to 25 V DC supplied through communications connector
Current consumption
Communications power supply:40 mA max. at 24 V DC Internal circuit power supply:80 mA max. at 5 V DC
Number of I/O points
16 inputs and 16 outputs (32 in total)
Number of occupied words
1 input word and 1 output word (2 words in total)
Weight
185 g max.
Communications Specifications (Conforming to DeviceNet Standards) Connection method
Multi-drop, T-type bifurcation (both require external terminating resistor)
Baud rate
500, 250, or 125 kbps (selectable with a switch)
Communications cycle time
9.3 ms with 16 Input Slaves (16 inputs) and 16 Output Slaves (16 outputs) at a speed of 500 kbps.
Cable
Dedicated 5-conductor cable (with two signal wires, two power wires, and a shield wire)
Communications distance
Baud rate 500K bps 250K bps 125K bps
Max. network length (see note 1) 100 m max. (see note 2) 250 m max. (see note 2) 500 m max. (see note 2)
Branch line length 6 m max. 6 m max. 6 m max.
Total branch line length 39 m max. 78 m max. 156 m max.
Max. number of connectable nodes
CVM1 or CV Series: 64 nodes, C200HX/HG/HE: 50 nodes, C200HS: 32 nodes
Error control
CRC errors, node address duplication, scan line checks
Note: 1. The maximum network length refers to the distance between two nodes farthest from each other. 2. The communications distance will be 100 m or less if a thin dedicated cable is used for the trunk line.
56
Page 54
Dedicated I/O Units
DeviceNet I/O Link Unit CQM1-DRT21
Words Allocated by CQM1H Slaves The CQM1H treats the I/O Link Unit as a single I/O Unit that has one input word and one output word. Words are allocated like I/O Units (i.e., input words from IR 001 and output words from IR 100 in order of the Units) beginning with the leftmost Unit.
■ Allocation Example Master Unit CQM1H I O D O R U I N U T T T N
16 Points 16 Points 21 Points 16 Points
P S C P U
PS: Power Supply Unit CPU: CPU Unit IN: Input Unit OUT: Output Unit DRT: I/O Link Unit
Word Allocations Input
IR 000 IR 001 IR 002
Output
IR 100 IR 101 IR 102
From Master Unit OUT area To Master Unit IN area
System Configuration Example C200HW-DRM21-V1 DeviceNet Master Unit
C200HX/HG/HE DeviceNet
SYSMAC CQM1H
DRT1-ID08/16(-1) DRT1-OD04/16(-1) Remote I/O Terminal
DRT1-AD04@ Analog Input Terminal DRT1-DA02 Analog Output Terminal
DRT1-HD165 Sensor Terminals
Other manufacturer's DRT1-COM peripheral device Communications Unit (MULTIPLE I/O TERMINAL)
Note: For details on DeviceNet, refer to the DeviceNet catalog (Catalog number: Q102-E1-@)
57
Page 55
Dedicated I/O Units
B7A Interface Unit CQM1-B7A
B7A Interface Unit
CQM1-B7A02/03/12/13/21 A B7A Interface Unit can connect to I/O devices located up to 500 m way using a single cable. Units are available with a wide range of I/O capacities to help reduce wiring in just about any application. Connect to PLCs for simple digital communications, connect to a control panel, or connect to a robot. Whatever you connect to, you’ll achieve more efficient wiring by reducing the number of connection cables required.
Performance Specifications Item
Specification
I/O points
CQM1B7A21:16 input points (see note 1), 16 output points B7A13:32 input points (see note 2) B7A03:32 output points B7A12:16 input points (see note 1) B7A02:16 output points
I/O word allocation
CQM1B7A21:1 word each for input and output (2 words in total) B7A13:2 words for input B7A03:2 words for output B7A12:1 word for input B7A02:1 word for output
Communication method Unidirectional, time-shared multiplex Transmission distance
STANDARD: RAPID:
500 m max. (see note 3) 100 m max. (see note 3)
I/O delay
STANDARD: 19.2 ms (rated delay), 31 ms max. RAPID: 3 ms (rated delay), 5 ms max. (STANDARD or RAPID set via switch.)
Power consumption
100 mA at 5 V DC
External power supply
12 to 24 V DC ±10%, 0.11 A min. (excluding the power required by the B7A Link Terminals)
Weight
200 g max.
Dimensions
32 x 110 x 107 mm (W x H x D)
Note: 1. Input mode setting allows selection between 16-point input and 15-point+1 error input. 2. Input mode setting allows selection between 32-point input and 30-point+2 error input. 3. The transmission distance depends on the power supply wiring methods.
58
Page 56
Dedicated I/O Units
B7A Interface Unit CQM1-B7A
B7A Link Terminals ■ Input Units Name
Model
Screw terminal models
B7A-T6@1
Transmission delay time STANDARD (19.2 ms)
B7AS-T6@1 B7A-T6@6
RAPID (3 ms)
B7AS-T6@6 Module models PLC connector models
B7A-T6D2
STANDARD (19.2 ms)
B7A-T6D7
RAPID (3 ms)
B7A-T@E3
STANDARD (19.2 ms)
B7A-T@E8
RAPID (3 ms)
■ Output Units Name
Model
Screw terminal model
B7A-R6@@1
Transmission delay time STANDARD (19.2 ms)
B7AS-R6@@1 B7A-R6@@6
RAPID (3 ms)
B7AS-R6@@6 G70D-R6R@1-B7A
STANDARD (19.2 ms)
G70D-R6M@1-B7A Module model PLC connector models
B7A-R6A52
STANDARD (19.2 ms)
B7A-R6A57
RAPID (3 ms)
B7A-R@A@3
STANDARD (19.2 ms)
B7A-R@A@8
RAPID (3 ms)
Note: Combine B7A Interface Units and B7A Link Terminals with equal transmission delay times. Do not connect B7A Link Terminals with 10 points and mixed I/O points.
■ I/O Unit and 32-point Input Unit Name Screw terminal model
I/O
Model
Transmission delay time
B7AM-6BS
STANDARD (19.2 ms)/ RAPID (3 ms) (switchable)
32 inputs B7AS-T3BS (16 pts/circuit)
59
Page 57
Dedicated I/O Units
B7A Interface Unit CQM1-B7A
System Configuration CQM1-B7A21 (16 input and 16 output points) CQM1-B7A03 (32 output points) CQM1-B7A13 (32 input points) CQM1-B7A02 (16 output points) CQM1-B7A12 (16 input points)
CQM1H
B7A Link Terminals
16 inputs
16 outputs
60
16 inputs
16 inputs
16 outputs
16 outputs
16 inputs
16 outputs