Dedicated I/O Units

DeviceNet I/O Link Unit CQM1-DRT21

DeviceNet I/O Link Unit

CQM1-DRT21 The DeviceNet I/O Link Unit is a DeviceNet slave that conforms to the multivender DeviceNet standards. DeviceNet I/O Link Units can be used to connect one or more CQM1H PLCs to a DeviceNet Master.

Performance Specifications Communications power supply voltage

11 to 25 V DC supplied through communications connector

Current consumption

Communications power supply:40 mA max. at 24 V DC Internal circuit power supply:80 mA max. at 5 V DC

Number of I/O points

16 inputs and 16 outputs (32 in total)

Number of occupied words

1 input word and 1 output word (2 words in total)

Weight

185 g max.

Communications Specifications (Conforming to DeviceNet Standards) Connection method

Multi-drop, T-type bifurcation (both require external terminating resistor)

Baud rate

500, 250, or 125 kbps (selectable with a switch)

Communications cycle time

9.3 ms with 16 Input Slaves (16 inputs) and 16 Output Slaves (16 outputs) at a speed of 500 kbps.

Cable

Dedicated 5-conductor cable (with two signal wires, two power wires, and a shield wire)

Communications distance

Baud rate 500K bps 250K bps 125K bps

Max. network length (see note 1) 100 m max. (see note 2) 250 m max. (see note 2) 500 m max. (see note 2)

Branch line length 6 m max. 6 m max. 6 m max.

Total branch line length 39 m max. 78 m max. 156 m max.

Max. number of connectable nodes

CVM1 or CV Series: 64 nodes, C200HX/HG/HE: 50 nodes, C200HS: 32 nodes

Error control

CRC errors, node address duplication, scan line checks

Note: 1. The maximum network length refers to the distance between two nodes farthest from each other. 2. The communications distance will be 100 m or less if a thin dedicated cable is used for the trunk line.

56

Page 54

Dedicated I/O Units

DeviceNet I/O Link Unit CQM1-DRT21

Words Allocated by CQM1H Slaves The CQM1H treats the I/O Link Unit as a single I/O Unit that has one input word and one output word. Words are allocated like I/O Units (i.e., input words from IR 001 and output words from IR 100 in order of the Units) beginning with the leftmost Unit.

■ Allocation Example Master Unit CQM1H I O D O R U I N U T T T N

16 Points 16 Points 21 Points 16 Points

P S C P U

PS: Power Supply Unit CPU: CPU Unit IN: Input Unit OUT: Output Unit DRT: I/O Link Unit

Word Allocations Input

IR 000 IR 001 IR 002

Output

IR 100 IR 101 IR 102

From Master Unit OUT area To Master Unit IN area

System Configuration Example C200HW-DRM21-V1 DeviceNet Master Unit

C200HX/HG/HE DeviceNet

SYSMAC CQM1H

DRT1-ID08/16(-1) DRT1-OD04/16(-1) Remote I/O Terminal

DRT1-AD04@ Analog Input Terminal DRT1-DA02 Analog Output Terminal

DRT1-HD165 Sensor Terminals

Other manufacturer's DRT1-COM peripheral device Communications Unit (MULTIPLE I/O TERMINAL)

Note: For details on DeviceNet, refer to the DeviceNet catalog (Catalog number: Q102-E1-@)

57

Page 55

Dedicated I/O Units

B7A Interface Unit CQM1-B7A

B7A Interface Unit

CQM1-B7A02/03/12/13/21 A B7A Interface Unit can connect to I/O devices located up to 500 m way using a single cable. Units are available with a wide range of I/O capacities to help reduce wiring in just about any application. Connect to PLCs for simple digital communications, connect to a control panel, or connect to a robot. Whatever you connect to, you’ll achieve more efficient wiring by reducing the number of connection cables required.

Performance Specifications Item

Specification

I/O points

CQM1B7A21:16 input points (see note 1), 16 output points B7A13:32 input points (see note 2) B7A03:32 output points B7A12:16 input points (see note 1) B7A02:16 output points

I/O word allocation

CQM1B7A21:1 word each for input and output (2 words in total) B7A13:2 words for input B7A03:2 words for output B7A12:1 word for input B7A02:1 word for output

Communication method Unidirectional, time-shared multiplex Transmission distance

STANDARD: RAPID:

500 m max. (see note 3) 100 m max. (see note 3)

I/O delay

STANDARD: 19.2 ms (rated delay), 31 ms max. RAPID: 3 ms (rated delay), 5 ms max. (STANDARD or RAPID set via switch.)

Power consumption

100 mA at 5 V DC

External power supply

12 to 24 V DC ±10%, 0.11 A min. (excluding the power required by the B7A Link Terminals)

Weight

200 g max.

Dimensions

32 x 110 x 107 mm (W x H x D)

Note: 1. Input mode setting allows selection between 16-point input and 15-point+1 error input. 2. Input mode setting allows selection between 32-point input and 30-point+2 error input. 3. The transmission distance depends on the power supply wiring methods.

58

Page 56

Dedicated I/O Units

B7A Interface Unit CQM1-B7A

B7A Link Terminals ■ Input Units Name

Model

Screw terminal models

B7A-T6@1

Transmission delay time STANDARD (19.2 ms)

B7AS-T6@1 B7A-T6@6

RAPID (3 ms)

B7AS-T6@6 Module models PLC connector models

B7A-T6D2

STANDARD (19.2 ms)

B7A-T6D7

RAPID (3 ms)

B7A-T@E3

STANDARD (19.2 ms)

B7A-T@E8

RAPID (3 ms)

■ Output Units Name

Model

Screw terminal model

B7A-R6@@1

Transmission delay time STANDARD (19.2 ms)

B7AS-R6@@1 B7A-R6@@6

RAPID (3 ms)

B7AS-R6@@6 G70D-R6R@1-B7A

STANDARD (19.2 ms)

G70D-R6M@1-B7A Module model PLC connector models

B7A-R6A52

STANDARD (19.2 ms)

B7A-R6A57

RAPID (3 ms)

B7A-R@A@3

STANDARD (19.2 ms)

B7A-R@A@8

RAPID (3 ms)

Note: Combine B7A Interface Units and B7A Link Terminals with equal transmission delay times. Do not connect B7A Link Terminals with 10 points and mixed I/O points.

■ I/O Unit and 32-point Input Unit Name Screw terminal model

I/O

Model

Transmission delay time

B7AM-6BS

STANDARD (19.2 ms)/ RAPID (3 ms) (switchable)

32 inputs B7AS-T3BS (16 pts/circuit)

59

Page 57

Dedicated I/O Units

B7A Interface Unit CQM1-B7A

System Configuration CQM1-B7A21 (16 input and 16 output points) CQM1-B7A03 (32 output points) CQM1-B7A13 (32 input points) CQM1-B7A02 (16 output points) CQM1-B7A12 (16 input points)

CQM1H

B7A Link Terminals

16 inputs

16 outputs

60

16 inputs

16 inputs

16 outputs

16 outputs

16 inputs

16 outputs