Page 58

Dedicated I/O Units

Temperature Control Units CQM1-TC@0@

Temperature Control Units

CQM1-TC@0@ CQM1-TC00@/TC20@: Thermocouple Inputs CQM1-TC10@/TC30@: Platinum Resistance Thermometer Inputs • Temperature Control Units are available for either 4-loop temperature control or 2-loop temperature control, and Units with 2loop temperature control provide a heater burnout alarm. • Parameters can be set and data read for these Temperature Control Units by transferring commands. Therefore, only one word each is allocated to the Temperature Control Unit for inputs and outputs, enabling high-density temperature controls. Commands can be easily transferred using the TRANSFER I/O COMMAND instruction (see note 1) that was been added to the CQM1H CPU Units. The PID with advanced feed-forward circuitry (2 degrees of freedom) assures stable temperature control. The Units can also be set to ON/ OFF control. Note: 1. Parameters can be set and data read for the CQM1-TC20@ and TC30@ using the new IOTC(−−) instruction. The IOTC instruction is supported by the following combination of CPU Unit and Support Software: CX-Programmer version 2.0 or later and a CQM1H CPU Unit with a lot number of 0160 or later. 2. The SYSMAC Support Software can also be used by uploading the expansion instructions from a CPU Unit.

Performance Specifications Item

Input

Thermocouple input CQM1-TC00@

Input sensors and set point ranges

K: –200 to 1,300°C (–300 to 2,300°F) J: –100 to 850 °C (–100 to 1,500°F)

Number of control loops

Platinum resistance thermometer input CQM1-TC10@

Thermocouple input CQM1-TC20@

Platinum resistance thermometer input CQM1-TC30@

JPt: –99.9 to 450.0°C (–99.9 K, J, T, L, R, S, B to 800.0°F) (See the following table for Pt: –99.9 to 450.0°C (–99.9 temperature ranges.) to 800.0°F)

Pt100, JPt100 (See the following table for temperature ranges.)

Two (either 1 or 2 loops can be used)

4 loops or 2 loops with heater burnout alarm

Control mode

ON/OFF or advanced PID control (2 degrees of freedom)

ON/OFF control, advanced PID control (2 degrees of freedom), or manual operation

Setting and display accuracy

°C Ranges °C Ranges (Set point ±1% or ±3°C, which- (Set point ±1% or ±2°C, ever is larger) ±1 digit max. whichever is larger) ±1 digit max. °F Ranges (Set point ±1% or ±6°F, which- °F Ranges ever is larger) ±1 digit max. (Set point ±1% or ±4°F, whichever is larger) ±1 digit max.

°C Ranges (Set point ±0.3% or ±1°C, whichever is larger) ±1 digit max.

0.1°C Ranges (Set point ±0.3% or ±0.8°C, whichever is larger) ±1 digit max.

°F Ranges (Set point ±0.3% or ±2°F, whichever is larger) ±1 digit max.

0.1°F Ranges (Set point ±0.3% or ±1.6°F, whichever is larger) ±1 digit max. (See note 1.) 0.01°C Ranges (Set point ±0.3% or ±0.5°C, whichever is larger) ±1 digit max.

Temperature adjustment

0.8°C/°F

Proportional band

40.0°C/°F

0.1 to 999.9°C/°F (0.1°C/°F unit) 0.1 to 999.9°C/°F (0.1°C/°F unit)

Derivative time

240 s

0 to 3,999 s (1 s unit)

Integral time

40 s

0 to 3,999 s (1 s unit)

Manual output

---

0.0% to 100.0% (0.1% unit)

Control period

20 s

1 to 99 s (1 s unit)

61

Page 59

Dedicated I/O Units

Temperature Control Units CQM1-TC@0@

Item

Thermocouple input CQM1-TC00@

Platinum resistance thermometer input CQM1-TC10@

Thermocouple input CQM1-TC20@

Input shift range

---

–99.9 to 999.9°C/°F (0.1°C/°F unit)

Sampling period

1s

0.5 s

Output

Output refresh period

1s

0.5 s

Output form

NPN or PNP outputs (with short-circuit protection)

Maximum switching capacity 100 mA, 24 V DC +10%/–15%

Platinum resistance thermometer input CQM1-TC30@ 0.1°C Ranges –99.9 to 999.9°C/°F (0.1°C/ °F unit) 0.01°C Ranges –9.99 to 99.99°C/°F (0.01°C/ °F unit)

NPN or PNP outputs (with short-circuit protection) 100 mA, 24 V DC +10%/–15%

Leakage current

0.3 mA max.

0.1 mA max.

Residual voltage

3.0 V max.

0.8 V max.

External supply voltage

15 mA min., 24 V DC +10%/–15%

30 mA min., 24 V DC +10%/–15%

Internal current consumption

220 mA max. at 5 V DC

190 mA max. at 5 V DC

Heater burnout alarm

Maximum heater current

---

50 A, single-phase AC

Input current monitoring accuracy

---

±5 % FS ±1 digit

Heater burnout alarm setting ---

0.1 to 49.9 A (0.1 A unit) (See note 1.)

Minimum ON time for detection

200 ms (See note 2.)

---

Note: 1. Heater burnout detection will be disabled if the alarm is set to 0.0 A. The heater burnout alarm output will turn ON if the alarm is set to 50.0 A. 2. If the control output is ON for less than 200 ms, heater burnout will not be detected and the heater current will not be measured.

Temperature Ranges ■ Units for Thermocouples Input type

Code No.

°C

°F

K

0

–200 to 1300

–300 to 2300

K

1

0.0 to 500.0

0.0 to 900.0

J

2

–100 to 850

–100 to 1500

J

3

0.0 to 400.0

0.0 to 750.0

T

4

–200.0 to 400.0

–300.0 to 700.0

L

5

–100 to 850

–100 to 1500

L

6

0.0 to 400.0

0.0 to 750.0

R

7

0 to 1700

0 to 3000

S

8

0 to 1700

0 to 3000

B

9

100 to 1800

300 to 3200

■ Units for Platinum Resistance Thermometers Input type Pt100

Code No. 0

°C –200.0 to 650.0

°F –300.0 to 1200.0

JPt100

1

–200.0 to 650.0

–300.0 to 1200.0

Pt100

2

–20.00 to 250.00

Do not set.

JPt100

3

–20.00 to 250.00

62

Page 60

Dedicated I/O Units

Temperature Control Units CQM1-TC@0@

Example System Configuration CQM1-TC10@/30@

CQM1-TC00@/20@

Thermocouple

Platinum resistance thermometer

Output Circuits CQM1-TC@01/TC@03: Sinking Outputs (NPN) +DC Internal circuitry

OUT

COM CQM1-TC@02/TC@04: Sourcing Outputs (PNP) COM

OUT

Internal circuitry

0V

Current Detector Ratings Item Continuous maximum heater current

E54-CT1

E54-CT3

50 A

Range for accurate measurement

0 to 30 A

Withstand voltage

1,000 VAC

0 to 50 A

Shock resistance

50 Hz (Approx. 98 m/s2)

Hole diameter

5.8 mm

12.0 mm

Weight

Approx. 11.5 g

Approx. 50 g

Accessories

None

Contactors: 2 Plugs: 2

63