Page 58
Dedicated I/O Units
Temperature Control Units CQM1-TC@0@
Temperature Control Units
CQM1-TC@0@ CQM1-TC00@/TC20@: Thermocouple Inputs CQM1-TC10@/TC30@: Platinum Resistance Thermometer Inputs • Temperature Control Units are available for either 4-loop temperature control or 2-loop temperature control, and Units with 2loop temperature control provide a heater burnout alarm. • Parameters can be set and data read for these Temperature Control Units by transferring commands. Therefore, only one word each is allocated to the Temperature Control Unit for inputs and outputs, enabling high-density temperature controls. Commands can be easily transferred using the TRANSFER I/O COMMAND instruction (see note 1) that was been added to the CQM1H CPU Units. The PID with advanced feed-forward circuitry (2 degrees of freedom) assures stable temperature control. The Units can also be set to ON/ OFF control. Note: 1. Parameters can be set and data read for the CQM1-TC20@ and TC30@ using the new IOTC(−−) instruction. The IOTC instruction is supported by the following combination of CPU Unit and Support Software: CX-Programmer version 2.0 or later and a CQM1H CPU Unit with a lot number of 0160 or later. 2. The SYSMAC Support Software can also be used by uploading the expansion instructions from a CPU Unit.
Performance Specifications Item
Input
Thermocouple input CQM1-TC00@
Input sensors and set point ranges
K: –200 to 1,300°C (–300 to 2,300°F) J: –100 to 850 °C (–100 to 1,500°F)
Number of control loops
Platinum resistance thermometer input CQM1-TC10@
Thermocouple input CQM1-TC20@
Platinum resistance thermometer input CQM1-TC30@
JPt: –99.9 to 450.0°C (–99.9 K, J, T, L, R, S, B to 800.0°F) (See the following table for Pt: –99.9 to 450.0°C (–99.9 temperature ranges.) to 800.0°F)
Pt100, JPt100 (See the following table for temperature ranges.)
Two (either 1 or 2 loops can be used)
4 loops or 2 loops with heater burnout alarm
Control mode
ON/OFF or advanced PID control (2 degrees of freedom)
ON/OFF control, advanced PID control (2 degrees of freedom), or manual operation
Setting and display accuracy
°C Ranges °C Ranges (Set point ±1% or ±3°C, which- (Set point ±1% or ±2°C, ever is larger) ±1 digit max. whichever is larger) ±1 digit max. °F Ranges (Set point ±1% or ±6°F, which- °F Ranges ever is larger) ±1 digit max. (Set point ±1% or ±4°F, whichever is larger) ±1 digit max.
°C Ranges (Set point ±0.3% or ±1°C, whichever is larger) ±1 digit max.
0.1°C Ranges (Set point ±0.3% or ±0.8°C, whichever is larger) ±1 digit max.
°F Ranges (Set point ±0.3% or ±2°F, whichever is larger) ±1 digit max.
0.1°F Ranges (Set point ±0.3% or ±1.6°F, whichever is larger) ±1 digit max. (See note 1.) 0.01°C Ranges (Set point ±0.3% or ±0.5°C, whichever is larger) ±1 digit max.
Temperature adjustment
0.8°C/°F
Proportional band
40.0°C/°F
0.1 to 999.9°C/°F (0.1°C/°F unit) 0.1 to 999.9°C/°F (0.1°C/°F unit)
Derivative time
240 s
0 to 3,999 s (1 s unit)
Integral time
40 s
0 to 3,999 s (1 s unit)
Manual output
---
0.0% to 100.0% (0.1% unit)
Control period
20 s
1 to 99 s (1 s unit)
61
Page 59
Dedicated I/O Units
Temperature Control Units CQM1-TC@0@
Item
Thermocouple input CQM1-TC00@
Platinum resistance thermometer input CQM1-TC10@
Thermocouple input CQM1-TC20@
Input shift range
---
–99.9 to 999.9°C/°F (0.1°C/°F unit)
Sampling period
1s
0.5 s
Output
Output refresh period
1s
0.5 s
Output form
NPN or PNP outputs (with short-circuit protection)
Maximum switching capacity 100 mA, 24 V DC +10%/–15%
Platinum resistance thermometer input CQM1-TC30@ 0.1°C Ranges –99.9 to 999.9°C/°F (0.1°C/ °F unit) 0.01°C Ranges –9.99 to 99.99°C/°F (0.01°C/ °F unit)
NPN or PNP outputs (with short-circuit protection) 100 mA, 24 V DC +10%/–15%
Leakage current
0.3 mA max.
0.1 mA max.
Residual voltage
3.0 V max.
0.8 V max.
External supply voltage
15 mA min., 24 V DC +10%/–15%
30 mA min., 24 V DC +10%/–15%
Internal current consumption
220 mA max. at 5 V DC
190 mA max. at 5 V DC
Heater burnout alarm
Maximum heater current
---
50 A, single-phase AC
Input current monitoring accuracy
---
±5 % FS ±1 digit
Heater burnout alarm setting ---
0.1 to 49.9 A (0.1 A unit) (See note 1.)
Minimum ON time for detection
200 ms (See note 2.)
---
Note: 1. Heater burnout detection will be disabled if the alarm is set to 0.0 A. The heater burnout alarm output will turn ON if the alarm is set to 50.0 A. 2. If the control output is ON for less than 200 ms, heater burnout will not be detected and the heater current will not be measured.
Temperature Ranges ■ Units for Thermocouples Input type
Code No.
°C
°F
K
0
–200 to 1300
–300 to 2300
K
1
0.0 to 500.0
0.0 to 900.0
J
2
–100 to 850
–100 to 1500
J
3
0.0 to 400.0
0.0 to 750.0
T
4
–200.0 to 400.0
–300.0 to 700.0
L
5
–100 to 850
–100 to 1500
L
6
0.0 to 400.0
0.0 to 750.0
R
7
0 to 1700
0 to 3000
S
8
0 to 1700
0 to 3000
B
9
100 to 1800
300 to 3200
■ Units for Platinum Resistance Thermometers Input type Pt100
Code No. 0
°C –200.0 to 650.0
°F –300.0 to 1200.0
JPt100
1
–200.0 to 650.0
–300.0 to 1200.0
Pt100
2
–20.00 to 250.00
Do not set.
JPt100
3
–20.00 to 250.00
62
Page 60
Dedicated I/O Units
Temperature Control Units CQM1-TC@0@
Example System Configuration CQM1-TC10@/30@
CQM1-TC00@/20@
Thermocouple
Platinum resistance thermometer
Output Circuits CQM1-TC@01/TC@03: Sinking Outputs (NPN) +DC Internal circuitry
OUT
COM CQM1-TC@02/TC@04: Sourcing Outputs (PNP) COM
OUT
Internal circuitry
0V
Current Detector Ratings Item Continuous maximum heater current
E54-CT1
E54-CT3
50 A
Range for accurate measurement
0 to 30 A
Withstand voltage
1,000 VAC
0 to 50 A
Shock resistance
50 Hz (Approx. 98 m/s2)
Hole diameter
5.8 mm
12.0 mm
Weight
Approx. 11.5 g
Approx. 50 g
Accessories
None
Contactors: 2 Plugs: 2
63