The text of a manual · part 13 of 15
Programmable Controller SYSMAC CQM1H, pages 61 to 68
Pages 61 to 68 of 75: CQM1-SF200 Front Page; Ordering Information
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron CQM1
Page 61
Dedicated I/O Units
Safety Relay Unit CQM1-SF200
Safety Relay Unit
CQM1-SF200 • Reduces wiring effort and installation space for safety circuits. • Monitors the following four statuses of the safety circuit 1. Safety Circuit Output Status Monitors if the safety circuit is operating and producing outputs. 2. Safety Circuit Power Status Monitors the status of the power supply to the safety circuit. 3. K1 Relay Operating Status 4. K2 Relay Operating Status Monitors the status of the internal relays that form the safety circuit. This helps troubleshooting safety circuit problems.
• General-purpose Inputs In addition to the safety circuit, a general-purpose input section (4 inputs and 1 common) is provide, which can be used for general controls.
Performance Specifications Item
Specifications
Contact resistance (See note 1.)
100 mΩ
Operating time (See note 2.)
300 ms max.
Response time (See notes 2 and 3.)
10 ms max.
Durability
Mechanical
5 million operations min. (switching frequency: 7,200 times/hour)
Electrical
100,000 operations min. (rated load, switching frequency: 1,800 times/hour)
Error rate (P level: reference value)
1 mA at 5 VDC
Weight
260 g max.
Note: 1. Measurement conditions: 1 A at 5 VDC voltage drop method 2. Bounce time is not included. 3. The response time is from when the input is turned OFF to when the main contact turns OFF.
Ratings (Safety Circuit) Power Supply Section Item Supply voltage
Switching Section Specifications
24 VDC
Permissible voltage fluctuation –15%/+10% of supply voltage range Power consumption
24 VDC: 1.7 W max.
Input Section Item Input current
64
Specifications 75 mA max.
Item
Specifications
Load
Resistive load (cos=φ1)
Rated load
5 A at 250 VAC
Rated switching current
5A
Page 62
Dedicated I/O Units
Safety Relay Unit CQM1-SF200
Ratings (General-purpose Input) Item
Specifications
Rated input voltage
24 VDC –15%/+10%
Input impedance
4.0 kΩ
Input current
6 mA typical (24 VDC)
ON voltage/ON current
14.4 VDC min./3 mA min.
OFF voltage/OFF current
5 VDC max./1 mA max.
ON/OFF response time
8 ms max. (selectable from 1 to 128 ms using System Setup.)
Number of circuits
4 inputs and 1 common
Number of points that turn ON 100% simultaneously ON simultaneously Internal current consumption
50 mA max.
Control Input Specifications
General-purpose Inputs
Safety circuits
Indicator
Indicator
Internal Circuits
Indicator
4.0 kΩ 0.01 µF
820 Ω
Input indicator
65
Page 63
Ordering Information
Ordering Information ■ International Standards The products shown in the attached tables are those that conform to the UL, CSA, cULus, cUL, NK, Lloyd’s Register, and EC Directives as of the end of September 2001. (U: UL, C: CSA, UC: cULus, CU: cUL, N: NK, L: Lloyd, CE: EC Directives) Please contact OMRON representative for application conditions.
■ EMC Directives Applicable Standards
Low Voltage Directive
EMI:EN50082-2 EMS:EN61131-2 and EN61000-6-2 (See note.) PLCs are electrical devices that are incorporated in machines and manufacturing installations. OMRON PLCs conform to the related EMC standards so that the devices and machines into which they are built can more easily conform to EMC standards. The actual PLCs have been checked for conformity to EMC standards. Whether these standards are satisfied for the actual system, however, must be checked by the customer. EMC-related performance will vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which the PLC is installed. The customer must, therefore, perform final checks to confirm that the overall machine or device conforms to EMC standards.
Applicable Standard
66
EN61131-2 Devices that operate at voltages from 50 to 1,000 VAC or 75 to 150 VDC must satisfy the appropriate safety requirements. With PLCs, this applies to Power Supply Units and I/O Units that operate in these voltage ranges. These Units have been designed to conform to EN61131-2, which is the applicable standard for PLCs.
Page 64
Ordering Information
Power Supply Units
Power Supply Units Name
Specifications Rated voltage
AC Power Supply 100 to 240 V AC Units 50/60 Hz
Allowed voltage range 85 to 265 V AC
110/230 V AC 50/60 Hz DC Power Supply 24 V DC Units
Model
Output capacity
Service power supply
International standards
18 W
None
CQM1-PA203
U, C, N, L, CE
30 W
24 V DC 0.5 A
CQM1-PA206
U, C, L, N
80 to 138 V AC 160 to 276 V AC
30 W
24 V DC 0.5 A
CQM1-PA216
N, L, CE
20 to 28 V DC
30 W
---
CQM1-PD026
UC, N, L, CE
CPU Units (with 16 built-in DC input points) Specifications Memory capacity
I/O capacity
Program: 3.2 Kwords DM area: 3 Kwords
256 points
Program: 7.2 Kwords DM area: 6 Kwords
512 points
Built-in inputs 16 DC inputs
Model
Built-in RS232C port No
Support of Inner Boards
Support of Controller Link Unit
No
No
Yes
CQM1H-CPU11
International standards
U, C, N, L, CE
CQM1H-CPU21 Yes
Yes
Program: 15.2 Kwords DM area: 6 Kwords EM area: 6 Kwords
CQM1H-CPU51
UC, N, L, CE
CQM1H-CPU61
U, C, N, L, CE
Inner Boards Name
Specifications
Model
International standards
High-speed Counter Board
4 pulse inputs (high-speed counter) at 500 kHz max. 4 external outputs
CQM1H-CTB41
U, C, N, L, CE
Pulse I/O Board
2 pulse inputs, Single-phase: 50 kHz, Differential phase: 25 kHz 2 pulse outputs, 50 kHz max. Both fixed and variable duty factors are supported.
CQM1H-PLB21
U, C
Absolute Encoder Interface Board
2 absolute encoder (gray code binary) inputs (4 kHz)
CQM1H-ABB21
U, C, N, L
Analog Setting Board
4 analog settings
CQM1H-AVB41
U, C, N, L, CE
Analog I/O Board
4 analog inputs of 0 to 5 V, 0 to 20 mA, –10 to +10 V 2 analog outputs of 0 to 20 mA, –10 to +10 V
CQM1H-MAB42
CE
Serial Communications Board
One RS-232C port and one RS-422A/485 port
CQM1H-SCB41
U, C, N, L, CE
Model
International standards
Communications Units Name Controller Link Unit (Wired)
Specifications Data link (Maximum number of words per node: 8,000) Message communications (SEND/RECV/CMND instructions)
CQM1H-CLK21
U, C, CE
67
Page 65
Ordering Information
Memory Cassettes
Memory Cassettes Memory Flash memory
Memory capacity/Clock function 16 Kwords
EEPROM
CQM1H-ME16K with clock
CQM1H-ME16R with clock
CQM1-ME08R with clock
CQM1-ME04R
8 Kwords
CQM1-ME08K
4 Kwords EPROM Memory Cassette (Memory chip not included) EPROM chip
Model
International standards U, C, N, L, CE UC, N, L, CE
CQM1-ME04K
Cassette with IC socket only (EPROM chip sold separately) with clock
U, C, N, L, CE
CQM1-MP08K CQM1-MP08R
256 KB (16 Kwords), 150 ns, 27256 IC or equivalent, 12.5 V
ROM-JD-B
512 KB (32 Kwords), 150 ns, 27512 IC or equivalent, 12.5 V
ROM-KD-B
CE
Available Models Memory
Memory capacity/Clock function
Model
I/O Control Unit
Connects to right-hand side of CPU Block
CQM1H-IC101
I/O Interface Unit
Connects to left-hand side of Expansion I/O Block
CQM1H-II101
I/O Extension Cable
For connection with I/O Control Unit and I/O Interface Unit
Cable length: 0.3 m
CS1W-CN313
Cable length: 0.7 m
CS1W-CN713
International standards U, C, CE L, CE
I/O Units ■ Input Units Input type DC inputs
AC inputs
Specifications
Model
International standards
8 points, 12 to 24 V DC (independent commons, 1 point/common × 8 circuits)
CQM1-ID211
U, C, N, L, CE
16 points, 12 V DC (16 points/common × 1 circuit)
CQM1-ID111
U, C
16 points, 24 V DC (16 points/common × 1 circuit)
CQM1-ID212
UC, N, L, CE
32 points, 12 V DC (32 points/common)
CQM1-ID112
U, C
32 points, 24 V DC (32 points/common)
CQM1-ID213
U, C, N, L, CE
32 points, 24 V DC (32 points/common × 1 circuit)
CQM1-ID214
U, C, CE
8 points, 100 to 120 V AC (8 points/common)
CQM1-IA121
U, C, L, CE
8 points, 200 to 240 V AC (8 points/common)
CQM1-IA221
■ Output Units Output type Contact outputs Transistor outputs
AC outputs
Specifications
Model
8 points, 250 V AC (cosφ = 1.0/0.4)/24 V DC 2 A (16 A/Unit), independent commons
CQM1-OC221
16 points, 250 V AC (cosφ = 1.0/0.4)/24 V DC 2 A (8 A/Unit)
CQM1-OC222
UC, N, L
8 points, 250 V AC 2 A (cosφ = 1.0/0.4)/24 V DC 2 A, independent common
CQM1-OC224
CE
8 points, 24 V DC, 2A (5 A/Unit), 8 points/common
CQM1-OD211
U, C, N, L, CE
16 points, 50 mA at 4.5 V DC to 300 mA at 26.4 V DC, 16 points/common
CQM1-OD212
32 points, 16 mA at 4.5 V DC to 100 mA at 26.4 V DC
CQM1-OD213
16 points, 24 V DC, 300 mA, PNP outputs
CQM1-OD214
8 points, 24 V DC, 1.0 A, PNP outputs (4 A/Unit), short-circuit protection
CQM1-OD215
U, C, N, L
U, C, L, CE
32 points, 24 V DC, 0.5 A, PNP outputs (5 A/Unit), short-circuit protection
CQM1-OD216
CE
8 points, 0.4 A at 100 to 240 V AC, two circuits with 4 points/common each
CQM1-OA221
U, C, L
6 points, 0.4 A at 100 to 240 V AC, two circuits with 4 points/common and 2 points/com- CQM1-OA222 mon
68
International standards
CE
Page 66
Ordering Information
Dedicated I/O Units
Dedicated I/O Units Name CompoBus/S Master Unit
Specifications
Model
Number of I/O points per Master: 128 (64 inputs and 64 outputs) CQM1-SRM21-V1 Communications cycle time: 0.5 ms min.
International standards U, C, CE
DeviceNet I/O Link Unit
Number of I/O points: 16 inputs and 16 outputs
CQM1-DRT21
Analog Input Unit
Analog inputs: 4 points
CQM1-AD041
Analog Output Unit
Analog outputs: 2 points
CQM1-DA021
Power Supply Units
Required for Analog Input and Output For one Analog Unit Units. For two Analog Units
CQM1-IPS01
B7A Interface Unit
16 outputs
CQM1-B7A02
---
16 inputs
CQM1-B7A12
U, C
32 outputs
CQM1-B7A03
Temperature Control Units
U, C, N, CE
CQM1-IPS02
32 inputs
CQM1-B7A13
16 inputs and 16 outputs
CQM1-B7A21
---
Thermocouple input, transistor (NPN) output, 2 loops
CQM1-TC001
U, C
Thermocouple input, transistor (PNP) output, 2 loops
CQM1-TC002
Platinum resistance thermometer, transistor (NPN) output, 2 loops
CQM1-TC101
Platinum resistance thermometer, transistor (PNP) output, 2 loops CQM1-TC102
Safety Relay Unit
Thermocouple input, transistor (NPN) output, 4 loops
CQM1-TC201
U, C, CE
Thermocouple input, transistor (PNP) output, 4 loops
CQM1-TC202
U, C, CE
Platinum resistance thermometer, transistor (NPN) output, 2 loops (with heater burnout alarm)
CQM1-TC203
U, C, CE
Platinum resistance thermometer, transistor (PNP) output, 2 loops CQM1-TC204 (with heater burnout alarm)
U, C, CE
Thermocouple input, transistor (NPN) output, 4 loops
CQM1-TC301
U, C, CE
Thermocouple input, transistor (PNP) output, 4 loops
CQM1-TC302
U, C, CE
Platinum resistance thermometer, transistor (NPN) output, 2 loops (with heater burnout alarm)
CQM1-TC303
U, C, CE
Platinum resistance thermometer, transistor (PNP) output, 2 loops CQM1-TC304 (with heater burnout alarm)
U, C, CE
Emergency stop unit: 2 inputs/2 outputs, 4 general-purpose inputs CQM1-SF200
U C, CE
DIN Track Name Mounting Tracks
Specifications Track length: 50 cm
Height: 7.3 mm
Track length: 1 m Track length: 1 m End Plate
Model PFP-50N
International standards L
PFP-100N Height: 16 mm
PFP-100N2
Fasten mounting brackets on both sides of the PLC to prevent it PFP-M from sliding left or right. Two End Plates are provided with the CPU Unit.
Note: DIN Track products must be ordered in lots of ten.
69
Page 67
Ordering Information
Programming Devices and Accessories
Programming Devices and Accessories ■ Programming Consoles Name
Specifications
Programming Consoles
Connecting Cables Peripheral Port Conversion Cable
Model
International standards
2-m Connecting Cable included (No other Connecting Cables re- CQM1H-PRO01-E quired.)
U, C, CE
2-m Connecting Cable included (compatible with C-series PLCs) CQM1-PRO01-E The CS1W-CN114 peripheral port conversion cable must be purchased separately (see below).
U, C, N, CE
C200H-PRO27-E Requires a separate Connecting Cable. The C200H-CN222 conecting cable, C200HS-CN222 connecting cable, or CS1W-CN114 peripheral port conversion cable must be purchased separately (see below).
U, C, N, CE
Cable length: 2 m
C200H-CN222
N
Cable length: 2 m (for CPUs complying with EC directives)
C200HS-CN222
CE
Connects the peripheral port on the CQM1H to a personal com- CS1W-CN114 puter or Programming Console through a CQM1-CIF01/02 cable.
CE
■ CX-Programmer (Windows) Name CX-Programmer (V1.2 or later)
Specifications CD-ROM, OS: Windows 95, 98, Me, NT4.0, 2000, or XP
Model WS02-CXPC1-E-V3@
International standards ---
■ CX Protocol (Windows) Name CX-Protocol
Specifications Protocol macro software OS: Windows 95, 98, Me, NT4.0, 2000, or XP
Model WS02-PSTC1-E
International standards ---
■ Support Software Product
Model
International standards
Expansion Memory Unit
CPM1-EMU01-V1
---
EEPROM (256 K)
EEROM-JD
---
Maintenance Products Product
Function
Model
Battery
Backs up memory in the CPU Unit.
End Cover
Connects to the I/O Unit located on the extreme CQM1H-TER01 right
70
CPM2A-BAT01
International standards --U, C, CE
Page 68
Ordering Information
Programming Device Connecting Cables
Programming Device Connecting Cables Name
Specifications
Model
Connecting Cables (Peripheral port to Programming Device (computer))
Connects to Programming Console or CQM1-CIF01/02.
Connecting Cables (Peripheral port to RS-422)
Peripheral port to RS-422 conversion cable (length: 0.2 m)
CQM1H-CIF12
U, C, CE
D-Sub 9-pin computer cable (length: 2 m)
CS1W-CN226
CE
Connecting Cables (RS-232C port to Programming Device (computer))
CS1W-CN114
International standards
Connects to a D-Sub 9-pin port of an IBM PC/AT or compatible CQM1-CIF02 computer. (Use together with the CS1W-CN114.) Length: 3.3 m
CE U, C, N, L, CE
D-Sub 9-pin computer cable (length: 6 m)
CS1W-CN626
CE
D-Sub 9-pin receptacle (length: 0.1 m)
CS1W-CN118
CE
D-Sub 9-pin computer cable (length: 2 m)
XW2Z-200S-V
---
D-Sub 9-pin computer cable (length: 2 m) (anti-static)
XW2Z-200S-CV
---
D-Sub 9-pin computer cable (length: 5 m)
XW2Z-500S-V
---
D-Sub 9-pin computer cable (length: 5 m) (anti-static)
XW2Z-500S-CV
---
USB-Serial Conversion Cable
Converts between USB and RS-232C, cable length: 0.5 m. PC Driver included (CD-ROM).
CS1W-CIF31
N, CE
RS-422 Adapter
Converts peripheral port levels, cable length: 0.2 m.
CQM1-CIF121
U, C, CE
71