Page 69
Peripheral Device
Labor-saving Connectors
Peripheral Devices Labor-saving Connectors Converts the wiring of the 32-point I/O Unit connector into a terminal block, simplifying wiring and reducing the amount of wiring within the panel.
Units with I/O Connectors ■ Cables and Connectors Connector/Terminal Conversion Unit
XW2B-40G5 XW2B-40G4
XW2C-20G5-IN16 (see note)
Connecting Cable
PLC Unit
XW2Z-@@@B
CQM1-ID213 CQM1-ID214 CQM1-OD213 CQM1-OD216
XW2Z-@@@D
CQM1-ID213 CQM1-ID214
Note: This Unit is for an Input Unit only, with LED input indicators and NPN inputs.
■ Servo Relay Unit and Cables Servo Driver
Connecting Cables
Servo Relay Unit
Relay Cable
PLC CPU Unit
SMART STEP
XW2Z-@@@J-B5
R7D-AP@@@ W-series
XW2Z-@@@J-B4 XW2B-20J6-3B
R88D-WT@@H@
72
XW2Z-@@@J-A3 CQM1H-CPU61/51 (CQM1H-PLB21)
Page 70
Peripheral Devices
Labor-saving Connectors CQM1-ID/OD
I/O Blocks and Cables
Cables with Connectors Each Cable connects to two I/O Blocks. Model
CQM1-ID213/214
Length (mm)
For inputs
For outputs
Long
G79-I100C-75
G79-O100C-75
1,000
750
Short
G79-I150C-125
G79-O150C-125
1,500
1,250
G79-I200C-175
G79-O200C-175
2,000
1,750
G79-I300C-275
G79-O300C-275
3,000
2,750
G79-I500C-475
G79-O500C-475
5,000
4,750
CQM1-OD213
I/O Blocks Model
Specifications
G7TC-IA16
16 inputs 100/110 V AC, 200/220 V AC
G7TC-ID16
A-side: Word m B-side: Word m+1
24 V DC
G7TC-OC16
16 outputs
Contact output: 24 V DC, 5 A/2 A (cos φ = 1/0.4) 220 V AC, 2 A/1 A (cos φ = 1/0.4)
G7VC-OC16
Contact output, 24 V DC/220 V AC 2 A (cos φ = 1.0) 0.8 A (cos φ = 0.4)
G7VC-OA16
SSR, AC output: 75 to 264 V AC, 0.1 to 0.5 A
G7VC-OD16
SSR, DC output: 3 to 26 V DC, 0.1 to 0.5 A
Long cable connection: Word m+1
G7TC I/O Block
For inputs or outputs, G79-1 or G79-0 Connecting Cable (1:2)
Short cable connection: Word m
Note: For more details on I/O Blocks and I/O Terminals, refer to the I/O Terminal Series Catalog (X44-E1-@).
Direct DIN Track-mounting Power Supplies S82K-series Power Supplies The S82K Power Supplies provide DC power to a variety of I/O devices. Use S82K Power Supplies when using a CQM1H that requires a DC power supply or when the CQM1H cannot supply enough power to the connected I/O devices.
Model
Input voltage
Output current/voltage
Power rating
Dimensions
S82K-05024
12 V DC, 2.5 A 30 W 100 or 200 V AC 24 V DC, 1.3 A (switchable) 24 V DC, 2.1 A 50 W
75 × 90 × 96 mm (H×W×D)
S82K-10024
24 V DC, 4.1 A 100 W
75 × 135 × 96 mm (H×W×D)
S82K-03012 S82K-03024
H D W
Power Supply Specifications Model
Input voltage
Output current/voltage
S82K-01505
100 to 200 V AC
5 V DC, 2.5 A
S82K-01512 S82K-01524
12 V DC, 1.2 A 24 V DC, 0.6 A
Power rating 15 W
Dimensions 75 × 45 × 96 mm (H×W×D)
73
Page 71
Peripheral Devices
Expansion Memory Unit CPM1-EMU01-V1
Expansion Memory Unit
CPM1-EMU01-V1 The Expansion Memory Unit can be used to upload and download user programs and data memory with the press of a button allowing simply program maintenance.
Connections CPM1-EMU01-V1
CS1W-CN114
The CPM2C-CN111 can also be used.
Specifications Item
Specification
Supported PCs
CPM1, CPM1A, CPM2A, CPM2C, SRM1 (-V2), CQM1, CQM1H
Read/Write memory areas
User program: 15.2 Kwords max. Data memory: DM 6144 to DM 6655 (Read-only DM and PC Setup) Expansion instructions: 18 instructions
Connector
Connector compatible with peripheral port on CPM1, CPM1A, CPM2A, SRM1 (-V2), and CQM1 PCs. For CPM2C and CQM1H PCs, connect via CS1WCN114 or CPM2C-CN111 Connecting Cable.
EEPROM (See note.)
256-Kbit EEPROM ATMEL: AT28C256 OMRON: EEROM-JD
Current consumption
129 mA max.
Dimensions
Main body (not including cables or connectors): 57 × 92 × 38 mm (W × H × D)
Weight
200 g max. (not including EEPROM)
Note: The EEPROM must be purchased separately.
74
Page 72
Peripheral Devices
Expansion Memory Unit CPM1-EMU01-V1
Dimensions
Memory Areas The memory areas that are uploaded or downloaded vary with the button used as shown in the following table. Area
Button UPLOAD + DM
Ladder program and expansion instructions DM 6144 to DM 6655
Read from PC to EEPROM.
UPLOAD Read from PC to EEPROM.
DOWNLOAD TO PLC All contents of EEPROM written to PC.
Not affected.
For details on program size, DM area, and the availability of expansion instructions, refer to the relevant PC manual.
75