The text of a manual · part 8 of 15
Programmable Controller SYSMAC CQM1H, pages 44 to 46
Pages 44 to 46 of 75: CQM1H-CLK21 Front Page; Dedicated I/O Units
The original document is the PDF (16 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron CQM1
Page 44
Communications Units
Controller Link Unit CQM1H-CLK21
Communications Units Controller Link Unit
CQM1H-CLK21 The Controller Link is an FA network that can send and receive large data packets flexibly and easily among the OMRON CQM1H-series, C200HX/HG/HE, and CSseries PLCs. The Controller Link supports data links that enable data sharing and a message service that enables sending and receiving data when required. Data link areas can be freely set to create a flexible data link system and effectively use data areas. • High-capacity, flexible, and efficient data links • Message service can transfer large quantities of data. • Simple twisted-pair wiring • Easily connects different PLC models and computers. • Flexible inter-network connections • Robust error-handling functions
■ Data Links ■ Message Service Controller Link Unit
Controller Link Unit
Transfer data when needed (for specific conditions.)
SEND
Constant data exchange (sharing)
PLC CPU
PLC CPU
PLC CPU
CPU
PLC CPU
PLC CPU
PLC
Network communications instruction User program
47
Page 45
Communications Units
Controller Link Unit CQM1H-CLK21
Unit Specifications Item Name
Specifications Controller Link Unit
Model number
CQM1H-CLK21
Applicable CPU Units
CQM1H-CPU51/CPU61
Unit classification
Communications Unit
Connection location and number One Unit only. of Units The Unit must be connected between the Power Supply Unit and the CPU Unit. Current consumption
270 mA
Dimensions
32 × 110 × 107 mm (W × H × D) (without terminals)
Weight
170 g max.
Communications Specifications Item
Specifications
Communications method
N:N token bus
Code
Manchester code
Modulation
Baseband code
Synchronization
Flag synchronization (conforms to HDLC frames)
Transmission path form
Multi-drop bus
Baud rate and maximum transmission distance
The maximum transmission distance varies with the baud rate as follows: 2 Mbps: 500 m 1 Mbps: 800 m 500 Kbps: 1 km
Media
Specified shielded twisted-pair cable Number of signal lines: 2, shield line: 1
Maximum number of nodes
32 nodes
Communications functions
Data links and message service
Number of data link words
Transmission area per node: 1,000 words max. Data link area in one CQM1H-series PLC (send/receive): 8,000 words max.
Data link areas
Bit areas (IR, AR, LR, CIO), data memory (DM), and extended data memory (EM)
Message length
2,012 bytes max. (including the header)
RAS functions
Polling node backup function Self-diagnosis function (hardware checking at startup) Echoback test and broadcast test (using the FINS command) Watchdog timer Error log function
Error control
Manchester code check CRC check (CCITT X16 + X12 + X5 + 1)
48
Page 46
Dedicated I/O Units
Summary of Dedicated I/O Units
Dedicated I/O Units Summary of Dedicated I/O Units Name
Specifications
Model number
Page
Analog Input Unit
4 analog input points –10 to +10 V, 0 to 10 V, 1 to 5 V, or 4 to 20 mA
CQM1-AD041
50
Analog Output Unit
2 analog output points –10 to +10 V or 0 to 20 mA
CQM1-DA021
51
Analog Power Supply Units
Power supply for Analog Input or Output Unit (required when using Analog Input or Out- CQM1-IPS01 52 put Unit) (Supplies 1 Unit.) CQM1-IPS02 (Supplies 2 Units.)
CompoBus/S Master Unit 128 points (64 inputs and 64 outputs), 64 points (32 inputs and 32 outputs), or 32 points CQM1-SRM21(16 inputs and 16 outputs) selectable with a switch. V1
53
DeviceNet I/O Link Unit B7A Interface Units
DeviceNet Slave: 32 points (16 inputs and 16 outputs)
CQM1-DRT21
56 58
16 output points
CQM1-B7A02
16 input points
CQM1-B7A12
32 output points
CQM1-B7A03
32 input points
CQM1-B7A13
16 input points and 16 output points
CQM1-B7A21
Temperature Control Units Thermocouple input (J/K), ON/OFF or advanced PID control, transistor (NPN) output, 2 CQM1-TC001 loops
61
Thermocouple input (J/K), ON/OFF or advanced PID control, transistor (PNP) output, 2 CQM1-TC002 loops Platinum resistance thermometer input (Pt, JPt), ON/OFF or advanced PID control, tran- CQM1-TC101 sistor (NPN) output, 2 loops Platinum resistance thermometer input (Pt, JPt), ON/OFF or advanced PID control, tran- CQM1-TC102 sistor (PNP) output, 2 loops Thermocouple input (K, J, L, T, R, S, B), ON/OFF or advanced PID control, manual op- CQM1-TC201 eration, transistor (NPN) output, 4 loops Thermocouple input (K, J, L, T, R, S, B), ON/OFF or advanced PID control, manual op- CQM1-TC202 eration, transistor (PNP) output, 4 loops Thermocouple input (K, J, L, T, R, S, B), heater burnout alarm, ON/OFF or advanced PID CQM1-TC203 control, manual operation, transistor (NPN) output, 2 loops Thermocouple input (K, J, L, T, R, S, B), heater burnout alarm, ON/OFF or advanced PID CQM1-TC204 control, manual operation, transistor (PNP) output, 2 loops Platinum resistance thermometer input (Pt100, JPt100), manual operation, ON/OFF or CQM1-TC301 advanced PID control, transistor (NPN) output, 4 loops Platinum resistance thermometer input (Pt100, JPt100), manual operation, ON/OFF or CQM1-TC302 advanced PID control, transistor (PNP) output, 4 loops Platinum resistance thermometer input (Pt100, JPt100), heater burnout alarm, manual CQM1-TC303 operation, ON/OFF or advanced PID control, transistor (NPN) output, 2 loops Platinum resistance thermometer input (Pt100, JPt100), heater burnout alarm, manual CQM1-TC304 operation, ON/OFF or advanced PID control, transistor (PNP) output, 2 loops Safety Relay Unit
Emergency stop unit: 2 inputs/2 outputs, 4 general-purpose inputs
CQM1-SF200
64
49