Page 41
Inner Boards
Analog I/O Board CQM1H-MAB42
Analog I/O Board
CQM1H-MAB42 • The Analog I/O Board is an Inner Board with four analog inputs and two analog outputs. • The signal ranges that can be used for each of the four analog inputs are –10 to +10 V, 0 to 10 V, 0 to 5 V, and 0 to 20 mA. Each input’s signal range can be set independently. • The signal ranges that can be used for each of the two analog output points are –10 to +10 V and 0 to 20 mA. Each output’s signal range can be set independently.
System Configuration Analog I/O Board
Two analog outputs Four analog inputs
Specifications Item
Specifications
Name
Analog I/O Board
Model number
CQM1H-MAB42
Applicable CPU Units
CQM1H-CPU51/61
Unit classification
CQM1H-series Inner Board
Mounting locations and number of Boards
1 Board in Inner Board slot 2 (right slot)
Analog inputs
4 inputs
Analog outputs
2 outputs
Current consumption (Supplied from Power Supply Unit)
5 V DC, 400 mA max.
Dimensions
25 × 110 × 107 mm (W × H × D)
Weight
100 g max.
Standard accessories
Plugs: XM2D-1501 (OMRON) x 2 Hoods: XM2S-1511 (OMRON) x 2
44
Page 42
Inner Boards
Analog I/O Board CQM1H-MAB42
Analog Inputs Item
Specifications
Input signals
Voltage inputs
Number of analog inputs
4 inputs
Input signal ranges1
–10 to 10 V 0 to 10 V 0 to 5 V
A/D conversion time2
1.7 ms max./point
Resolution
1/4,096
A/D conversion output data
12-bit binary data –10 to +10 V: F800 to 07FF Hex 0 to 10 V, 0 to 5 V:0000 to 0FFF Hex
Current inputs 0 to 20 mA
12-bit binary data 0 to 20 mA: 0000 to 0FFF Hex
External input impedance
1 MΩ typical
250 Ω typical
Absolute maximum rated input
±15 V
±30 mA
Overall precision3
23±2°C
±0.5% of FS
0 to 55°C
±1.0% of FS
Note: 1. Separate input signal ranges can be set for each input. 2. The A/D conversion time is the time taken for an analog signal to be stored in memory as digital data. At least one cycle is required to transfer the data to the CPU Unit. 3. The overall precision is the precision with respect to full scale. 4. The CQM1H-MAB42 Analog I/O Board, unlike the CQM1-AD041, does not have a hardware average processing function. If averaging of data is required, use the CPU Unit’s data averaging instruction (AVG).
Analog Outputs Item
Specifications
Output signals
Voltage outputs
Number of analog outputs
2 outputs
Output signal ranges 1
–10 to 10 V
D/A conversion time2
1.7 ms max./2 points
Current outputs 0 to 20 mA
Resolution
1/4,096
1/2,048
Set output data
12-bit binary data –10 to +10 V: F800 to 07FF Hex
11-bit binary data 0 to 20 mA: 0000 to 07FF Hex
2 KΩ min.
350 Ω max.
Allowable external output load resistance Overall precision3
23±2°C
±0.5% of FS
0 to 55°C
±1.0% of FS
Note: 1. Separate output signal ranges can be set for each output. 2. The D/A conversion time is the time taken for the output data set in memory to be converted to analog signals and output. At least one cycle is required to transfer the data in the CPU Unit to the Analog I/O Board. 3. The overall precision is the precision with respect to full scale.
45
Page 43
Inner Boards
Analog Setting Board CQM1H-AVB41
Analog Setting Board
CQM1H-AVB41 • The Analog Setting Board is an Inner Board that provides four variable resistor adjustments. The settings on the four adjustments are stored in the analog setting words. • By using the Analog Setting Board, an operator can, for example, set the value of a timer instruction using an analog adjustment, and thereby slightly speed up or slow down the speed or timing of a conveyor belt simply by turning an adjustment screw with a screwdriver, removing the need for a Programming Device.
Using the Analog Timer The following example shows the 4-digit BCD setting (0000 to 0200) stored in IR 220 to IR 223 being used as a timer setting. 00005 TIM000 220
The setting of TIM 000 is set externally in IR 220. (TIM 000 is executed using the SV set with analog adjustment 0.)
Specifications Item
Specifications
Name
Analog Setting Board
Model number
CQM1H-AVB41
Applicable CPU Units
CQM1H-CPU51/61
Unit classification
CQM1H-series Inner Board
Mounting locations and number of Boards
1 Board can be mounted in either slot 1 or slot 2.
Settings
4 analog (variable resistor) adjustment screws on front panel (Adjustable using Phillips screwdriver.) The settings of adjustments 0 to 3 are stored as 4-digit BCD values between 0000 and 0200 in IR 220 to IR 223 respectively.
Current consumption (Supplied from Power Supply Unit)
5 V DC, 10 mA max.
Note: Two Analog Setting Boards cannot be used at the same time.
Dimensions
25 × 110 × 107 mm (W × H × D)
Weight
60 g max.
46