Page 37
Inner Boards
Absolute Encoder Interface Board CQM1H-ABB21
Absolute Encoder Interface Board
CQM1H-ABB21 The Absolute Encoder Interface Board is an Inner Board that allows position data to be directly input from absolute rotary encoders.
Absolute High-speed Counter The Absolute Encoder Interface Board reads binary gray codes (inverted binary codes) input from an absolute encoder at a maximum counting rate of 4 kHz, and can perform interrupt processing according to the input values.
Interrupts An interrupt subroutine can be executed when the PV (present value) of the absolute high-speed counter matches a specified target value (target value comparison) or falls within a specified comparison range (range comparison.) Note: When an absolute encoder is used the position data can be retained even during power interrupts, so it isn’t necessary to perform an origin return when power is returned. In addition, the origin compensation function allows the user to specify any position as the origin.
Example System Configuration Absolute Encoder Interface Board Workpieces
Processing table
Absolute Encoder
Detects angle of rotation and controls processing table.
40
Motor
Motor driver (Inverter)
Page 38
Inner Boards
Absolute Encoder Interface Board CQM1H-ABB21
Specifications Item
Specifications
Name
Absolute Encoder Interface Board
Model number
CQM1H-ABB21
Applicable CPU Units
CQM1H-CPU51/61
Unit classification
CQM1H-series Inner Board
Mounting locations and number of Boards
1 Board can be mounted in slot 2.
Absolute Encoder inputs
2 inputs
Current consumption (Supplied from Power Supply Unit)
5 V DC, 150 mA max.
Dimensions
25 × 110 × 107 mm (W × H × D)
Weight
90 g max.
Standard accessories
Plugs:XM2D-1501 (OMRON) x 2 Hoods:XM2S-1511 (OMRON) x 2
■ Absolute Encoder Input Specifications Item
Specifications
Number of inputs
Two inputs
Input code
Binary gray code
Operating modes
BCD Mode or 360° Mode (Set in PLC Setup.)
Resolutions
8-bit, 10-bit, or 12-bit (Set in PLC Setup.)
Origin compensation
Supported. (Current position can be designated as origin). Compensation is set in PLC Setup.
Counting rate
4 kHz max.
Control methods
Target value comparison
Register up to 48 target values and interrupt subroutine numbers.
Range comparison
Register up to 8 upper limits, lower limits, and interrupt subroutine numbers.
■ Pulse Inputs Item Input voltage
Specifications 24 V DC +10%, –15%
Input impedance
5.4 kΩ
Input current
4 mA typical
ON voltage
16.8 V DC min.
OFF voltage
3.0 V DC max.
41
Page 39
Inner Boards
Serial Communications Board CQM1H-SCB41
Serial Communications Board
CQM1H-SCB41 The Serial Communications Board is an Inner Board equipped with 2 ports that can be used to connect host computers, Programmable Terminals, external serial devices, or Programming Devices other than a Programming Console. • Unlike the CPU Unit’s built-in ports, the Serial Communications Board supports the protocol macro function which can improve communications between the CQM1H and external serial devices. • The Serial Communications Board has 2 ports: an RS-232C port and an RS-422A/485 port. The RS-422A/485 port supports 1:N connections (protocol macro or NT Link in 1:N mode) without an adapter.
System Configuration Serial Communications Board
RS-232C
RS-422A/485
OR Bar code reader
Dedicated controller
Temperature controller Standard external devices with an RS-232C or RS-422A/485 port
Communications Modes The following 6 communications modes can be set independently for the two Serial Communications Board ports. • Host Link: • No-protocol: • Protocol macro: • 1:1 Data Link: • NT Link in 1:N mode: • NT Link in 1:1 mod:
42
Communications with a host computer, Programming Device, or Programmable Terminal No-protocol communications (TXD and RXD) with standard external devices Communications according to the external device’s communications specifications Data link with a CQM1H, CQM1, or other C-series PLC One-to-one or one-to-N communications with Programmable Terminals One-to-one communications with Programmable Terminal
Page 40
Inner Boards
Serial Communications Board CQM1H-SCB41
■ Communications Ports and Serial Communications Modes Serial communications protocol
CQM1H-SCB41 Serial Communications Board RS-232C port (port 1)
RS-422A/485 port (port 2)
Peripheral bus or Programming Console bus
No
No
Host Link (SYSMAC WAY)
YES
YES1
Protocol macro
YES
YES
No-protocol
YES
YES1
1:1 Data Link
YES
YES1
NT Link in 1:1 mode
YES2
YES2
NT Link in 1:N mode
2
YES2
YES
Note: 1. The 4-wire method must be used if the RS-422A/485 port is used in Host Link, No-protocol, or 1:1 Data Link mode. 2. A Programmable Terminal’s Programming Console function cannot be used.
Serial Communications Board Specifications Item Model
Specification CQM1H-SCB41
Unit classification
CQM1H-series Inner Board
Applicable CPU Units
CQM1H-CPU61/51
Mounting locations and number of Boards
1 Board can be mounted in slot 1.
Serial Communications ports
Port 1
RS-232C: 19.2 kbps max., 15 m max.
Port 2
RS-422A/485: 19.2 kbps max., 500 m max.
Protocols
Port 1
Each port can be set independently to Host Link, No-protocol, Protocol macro, 1:1 Data Link, NT Link in 1:N mode, or NT Link in 1:1 mode.
Port 2 Current consumption
5 VDC, 200 mA max.
Dimensions
25 × 110 × 107 mm (W × H × D)
Weight
90 g max.
Standard accessories
Plugs: XM2SA-0901 (OMRON) x 2 Hoods: XM2SA-0911 (OMRON) x 2 (ESD)
Protocol Macros Protocol macros provide a way to create data communications protocols for the communications specifications of external devices with serial communications ports (half-duplex, start-stop sync only). The protocol macros are made on the CX-Protocol Support Software and then recorded in the Serial Communications Board, where they can be executed at any time using the PMCR instruction in the CPU Unit’s ladder program. Standard system protocols are also provided with the CX-Protocol and Serial Communications Board for easy communications with OMRON components, such as Temperature Controllers, Intelligent Signal Processors, Bar Code Readers, and Modems. The standard system protocols can also be modified for specific applications using the CX-Protocol.
PMCR instruction Serial Communications Board CQM1H
Device with serial port RS-232C Message Set in the protocol macro for the required communications specifications.
43