Page 41

SECTION 4

Use

"

Configuration

To

Read The RC4030E Gateway’s configuration is stored in (Continued) EEPROM. You reprogram the EEPROM whenever you change the configuration, write (save) the new configuration to EEPROM, and reboot the RC4030E Gateway. Write

Reboot

Write (save) a new configuration to EEPROM. This command overwrites the previous configuration. You must write the new configuration to EEPROM and reboot the RC4030E Gateway for any changes to take effect. Reboot the RC4030E Gateway. You must reboot the gateway for any changes you made to the configuration to take effect.

Exit

Quit the configuration program. If you exit a new configuration without writing it to EEPROM, any changes you made are not saved.

?

Display online help for a command, option, or setting.

Using the View Command To view or modify the RC4030E Gateway’s configuration, type View at the command prompt. The Main Options Menu appears: [Gateway] [Tcpip] [Security]

RC4030E Gateway User’s Guide

4-9

Page 42

SECTION 4

"

Configuration

The following chart describes how to use the options. Use

To

[Gateway] Page 4-11

Set communications from the RC4030E Gateway to the wireless stations and to the host.

[Tcpip] Page 4-26

Set options necessary for communications with the RC4030E Gateway. The options apply to all TCP/IP ports. Telnet, SNMP, and HTTP communications are supported.

[Security] Page 4-33

Set the configuration program’s top-level and service passwords.

The following chart shows how to navigate the View command’s menus and edit data.

4-10

Press

To

[-] or [--]

Scroll up through items in a list.

[¯], [+], [=], or [Tab]

Scroll down through items in a list.

[®], [Enter], or [Spacebar]

Display an option’s settings or prompt after you highlight the option. Also use these keys to select the desired setting.

[¬], [Esc], or [Backspace]

Exit a menu or prompt.

[Esc]

Cancel editing.

[Enter]

Complete editing.

RC4030E Gateway User’s Guide

Page 43

SECTION 4

"

Configuration

Gateway Options Use [Gateway] to set up communications from the RC4030E Gateway to the wireless stations and to the host. Options and their default settings are: Name Gateway.Compression Host Type [Async Parms]

" NOTE:

“HOST” <Disabled> <Async>

[Async Parms] appears on the menu if Host Type is set to Async. [Sync Parms] appears if Host Type is set to 3270, 5294, or 5394.

Name The Name option is an arbitrary name that identifies this RC4030E Gateway. Wireless stations use the arbitrary name to connect to this RC4030E Gateway. Note that Name is not your application’s host server name. The setting for Name must match the host name specified for each wireless station communicating with the host through this RC4030E Gateway. The names must match so that the wireless stations can communicate with the host. Refer to the wireless station’s user’s guide for more information about specifying host names. The setting for Name is case sensitive. For example, if the host name specified for the wireless stations is typed in all uppercase, the name for the RC4030E Gateway must also be typed in all uppercase. Figure 4-3 shows an example of how host name HOST1 is set on an RC4030E Gateway and wireless station.

RC4030E Gateway User’s Guide

4-11

Page 44

SECTION 4

"

Configuration

RS-232 or V.35

Host (5250 SNA/SDLC)

RC4030E Gateway Host Type: 5294 Name: HOST1

6710 Access Point

RT1100 Radio Terminal Firmware: 5250 Hostname: HOST1

Figure 4-3 Host Names

The prompt for Name is: Range is: 16 chars

Type 16 or fewer alphanumeric characters for the name. The program inserts quotation marks around your entry.

4-12

RC4030E Gateway User’s Guide

Page 45

SECTION 4

"

Configuration

Gateway.Compression Gateway.Compression uses a general data compression algorithm to reduce the size of data sent to a wireless station. Settings are: Enabled Disabled

Setting

Description

Enabled

Compresses most outbound data from the RC4030E Gateway to the wireless stations. Inbound data sent from the wireless station is not compressed. Compression takes place on a client-by-client basis as allowed by each client. Does not compress data.

Disabled (default)

On most systems, compression reduces the RF (radio frequency) load by compressing most of the outbound data from the host to the wireless station. It is strongly recommended that you enable Gateway.Compression. Compression does not significantly increase wireless station counts or supported transaction rates. It does improve response time consistency in applications where the same data or screens are frequently repeated. The effectiveness of compression varies with the size and number of unique screens. While compression may reduce the amount of data being sent through the RF system, it increases the RC4030E Gateway’s processing load. Therefore, it may be beneficial to disable compression for some systems.

RC4030E Gateway User’s Guide

4-13

Page 46

SECTION 4

"

Configuration

Host Type Use Host Type to set the type of communication the host uses. Options are: Async 3270 5294 5394

Setting

Description

Async (default)

Sets host type to asynchronous. One host is connected via RS-232 and uses a proprietary protocol to multiplex all wireless stations. Use Async for 3270 asynchronous, 5250 asynchronous, and NORANDR Native communications. Options start on page 4-14. Sets host type to IBM 3270 SNA/SDLC emulation. Options start on page 4-19.

3270 5294

Sets host type to IBM 5294 Control Unit (5250 SNA/SDLC) emulation. Options start on page 4-19.

5394

Sets host type to IBM 5394 Control Unit (5250 SNA/SDLC) emulation. Options start on page 4-19.

[Async Parms] Use [Async Parms] to configure RS-232 options for the asynchronous multiplexing protocol. Options and their default settings are:

4-14

RC4030E Gateway User’s Guide

Page 47

SECTION 4

Baud Rate Stop Bits Parity Data Bits Host Timeout Address Type Enhanced R Polling Multiple Buffering Full Duplex

"

Configuration

<19200> <1> <None> <8> 0 <Normal> <Disabled> <Disabled> <Disabled>

Baud Rate Baud Rate is the serial communications speed in bits per second. Settings are: 300, 1200, 2400, 4800, 9600, 19200 (default), 38400, and 57600.

Stop Bits Use this option to set the number of stop bits to be sent with each character: 1 2

The default is 1 stop bit.

Parity Parity options are: None Odd Even

The default is None.

RC4030E Gateway User’s Guide

4-15

Page 48

SECTION 4

"

Configuration

Data Bits Use this option to set the number of data bits per character: 7 8

The default is 8 data bits.

Host Timeout Host Timeout is the number of seconds of host inactivity before the host is considered down. The prompt is: Range is: 0..255

The range is zero (default) to 255. A setting of zero means the RC4030E Gateway never assumes that the host has timed out. Intermec recommends 10 or more seconds. The default of zero means the RC4030E Gateway never times out the host. Ten or more seconds is recommended. Do not set Host Timeout to zero if the wireless station is configured to communicate with up to three hosts through the wireless station’s Advanced Setup firmware option. After the host timeout value has been exceeded, the wireless station displays “Host is Down.” The user can then reboot the wireless station. The RC4030E Gateway tries to connect with the next host defined for the wireless station.

Address Type For each frame sent to the host, the originating station can be fixed at one or three characters. Settings are:

4-16

RC4030E Gateway User’s Guide

Page 49

SECTION 4

"

Configuration

Normal Old

Setting

Description

Normal (default)

Wireless station addresses consist of three octets.

Old

RC4030E Gateway is backward compatible to the INTERMECR RM2216 series of multiplexers. Wireless station addresses consist of one octet instead of three, and RC4030E Gateway responses are in the MUX (RM2216-compatible) response format.

Enhanced R Polling Enhanced R Polling determines how the RC4030E Gateway responds to host commands with data (if available). Settings are: Enabled Disabled

Setting

Description

Enabled

RC4030E Gateway responds to host commands with data without sending acknowledgments (the wireless station response is the acknowledgment). This reduces the number of polls generated by the host.

Disabled (default)

RC4030E Gateway responds to host commands with data by sending acknowledgments.

RC4030E Gateway User’s Guide

4-17

Page 50

SECTION 4

"

Configuration

Multiple Buffering Multiple Buffering determines how the RC4030E Gateway stores messages. Settings are: Enabled Disabled

Setting

Description

Enabled

RC4030E Gateway stores more than one wireless station message from the host while it sends previous messages to the wireless station.

Disabled (default)

RC4030E Gateway buffers only one wireless station message from the host.

Full Duplex Full Duplex is a communications method where messages flow in two directions at the same time. The host application must be written to specifically support full duplex. Enabled Disabled

4-18

Setting

Description

Enabled

RC4030E Gateway and host transmit and receive at the same time.

Disabled (default)

Either the RC4030E Gateway or the host transmits or receives at one time (half duplex).

RC4030E Gateway User’s Guide