Page 211
Scanner Parameters
Output Mode Sets the condition in which the discrete output is de-activated.
Pulse This is the default mode of operation in which the programmable output is activated when the Output On condition has been met and held active for the duration of the selected pulse width.
Latch Mode 1 (Unlatch Input # 1 Pin) The programmable output is activated when the Output On condition has been met and held active until the Input # 1 Pin. Note: Input 1 must be set to Unlatch Output for Latch Mode 1 to function. If the Output Condition is set to Read Cycle Data Valid, then the read cycle will wait for Input 1 to unlatch the output before continuing on. This is to provide system handshake ability despite communication channel. The read cycle data must leave all channels before Read Cycle Data Valid will output.
Latch Mode 2 (Unlatch Opposite Condition) The programmable output is activated when the Output On condition has been met and held active until the opposite condition selected under Output On has been met. For example, if No Read is enabled under Output On, the programmable output will go active on a No Read and remain active until the opposite condition, a good read, occurs. If the Output Condition is set to Read Cycle Data Valid, then the read cycle will continue but every new Read Cycle Data Valid event causes the output to change state to the opposite condition. This provides a toggle event per every read cycle output. The only known outout state will be the on a power-on or reset. After reading begins, the state becomes undetermined. Only the state change itself has meaning - not the absolute value.
QX-870 Industrial Raster Scanner User Manual
5-145
Page 212
I/O Parameters
Latch Mode 3 (Unlatch Re-enter Read Cycle) The programmable output is activated when the Output On condition has been met and held active until a new read cycle begins. Note: All of the Output On modes are inhibited when any Diagnostic Warning is active for Output 2.
Trend Analysis Note: Output On under Output 2 Parameters must be set to Trend Analysis for this output to function. Under Output 2 Parameters, expand the Trend Analysis tree. Useful in cases where the user doesn’t want to shut down for one condition but wants to monitor quality and read conditions. Applies Trend Analysis settings to Output 2. With Trend Analysis, the user can track the occurrences and frequency of mismatches, No Reads, and the number of reads per trigger, and output the results to any of three outputs. Trend Analysis Mode = No Read Trigger Evaluation Period = 25 triggers (read cycles) Number to Output On = 4 In this example, the scanner will activate an output when 4 No Reads occur within a period of 25 triggers (read cycles).
5-146
QX-870 Industrial Raster Scanner User Manual
Page 213
Scanner Parameters
Trend Analysis Mode Sets the trend condition (Mismatch, No Read, Decodes per Trigger, Bad Symbol, or No Symbol) that will activate the output.
Mismatch Output will be activated when the number of mismatches equals the value entered for Number to Output On within the trigger window selected in Number of Triggers. No Read Output will be activated when the number of No Reads equals the value entered for Number to Output On within the trigger window selected in Number of Triggers. Decodes per Trigger Output will be activated when the number of decodes equals the value entered for Number to Output On within the trigger window selected in Number of Triggers. Bad Symbol Output will be activated when the number of Bad Symbol occurrences equals the value entered for Number to Output On within the trigger window selected in Number of Triggers. No Symbol Output will be activated when the number of No Symbol occurrences equals the value entered for Number to Output On within the trigger window selected in Number of Triggers.
QX-870 Industrial Raster Scanner User Manual
5-147
Page 214
I/O Parameters
Number of Triggers The number of triggers to examine for the trend analysis condition.
Number to Output On Example: If Number to Output On is set to 3 and Trend Analysis Mode is set to No Read, then the output will not be activated until 3 No Reads have occurred. Sets the number of Trend Analysis Mode events (mismatches, No Reads, or reads/trigger as configured by Trend Analysis Mode) to occur within the trigger evaluation period before activating the associated output.
5-148
QX-870 Industrial Raster Scanner User Manual
Page 215
Scanner Parameters
Decodes per Trigger When set to this mode, and when the appropriate output is set to output on trend analysis, the scanner will function in a Decodes per Trigger mode during the read cycle and the trend analysis operation. Output will be activated based on whether or not the symbol decode count at the end of the read cycle is less than the decodes per trigger threshold. Note: Although this setup causes the scanner to function in a Decodes per Trigger mode, the decode count will only be appended to the symbol data if the status of the Decodes per Trigger command is enabled.
Example: Decodes per Trigger threshold: 100 100 or more decodes = No output Fewer than 100 decodes = Output fires
QX-870 Industrial Raster Scanner User Manual
5-149
Page 216
I/O Parameters
Diagnostics Note: Output On under Output 2 Parameters must be set to Diagnostic Warning for this output to function. Under Output 2 Parameters, expand the Diagnostics tree. When Diagnostic Warning is enabled, the Output On configuration has no effect. The output will remain active as long as one of the diagnostic warning conditions is met. The output will become inactive once it detects that there are no diagnostic warning conditions.
High Temperature Activates output when the temperature exceeds factory-defined upper limits.
5-150
QX-870 Industrial Raster Scanner User Manual
Page 217
Scanner Parameters
Service Unit Allows the user to set up the output to toggle to active when the service timer has expired. This condition will only be held for one service timer click. Note: This feature cannot be used if the scanner is in Continuous Read. When Service Unit is enabled, a message of up to 10 ASCII characters is sent whenever the system detects that the service timer’s limit has been reached. The service timer is reset at power-on, meaning that the service timer’s limit is the amount of time since last reset. Service timer increments can be set in seconds or minutes.
Laser Current High Activates output when the laser current exceeds factory-defined upper limits.
QX-870 Industrial Raster Scanner User Manual
5-151
Page 218
I/O Parameters
Laser Current Low Activates output when the laser current drops below factory-defined lower limits.
Low Temperature Activates output when the temperature drops below factory-defined lower limits.
5-152
QX-870 Industrial Raster Scanner User Manual
Page 219
Scanner Parameters
Output 3 Parameters Output 3 has the same parameters and default settings as Output 1 and Output 2.
Output On Output On provides discrete signalling to host software to control external devices such as PLCs and relays. It is useful for routing, sorting, and to prevent mis-packaging and mis-routing. Sets the discrete output functions for specific user-selected conditions. Allows the user to set the conditions under which an output (or outputs) will be activated. Note: If Output On is set to Match or Mismatch, a transition (switching) will not occur unless Matchcode Type is enabled and a master symbol is loaded into memory.
QX-870 Industrial Raster Scanner User Manual
5-153
Page 220
I/O Parameters
Mismatch or No Read Activates discrete output when the data does not match that of the master symbol or the symbol has not been decoded before the end of the read cycle.
Good Read / Match Activates a discrete output when the symbol data matches the master symbol. Note: To output on Good Read when Matchcode is not enabled, enable any output for Match.
Mismatch Activates a discrete output whenever the symbol data does not match that of the master symbol.
No Read Activates a discrete output whenever the symbol data is not decoded before the end of the read cycle.
Trend Analysis Typically used when successful decodes are occurring but a discrete output is needed to flag a trend in quality issues. Activates discrete output when a trend analysis condition is met, depending on the trend analysis option enabled.
Diagnostic Warning Typically used when a discrete indication of a diagnostic condition is needed. Activates discrete output when a diagnostic warning condition is met, depending on the diagnostic option enabled.
In Read Cycle Activates a discrete output when the scanner is in a read cycle.
Read Cycle Data Valid Activates discrete output when all the data generated in the read cycle has left the scanner.