The text of a manual · part 3 of 7

MS-Connect 210 User Manual, pages 21 to 30

Pages 21 to 30 of 65

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Microscan MS-Connect 210

Page 21

Configure Output Settings

Configure Output Settings Outputs are configured by manipulating the dip switches and jumpers on the board. Switches at SW5

Configuring the Outputs and Beeper The switches for controlling outputs 1, 2, and 3 and the beeper are located at SW5. Reader Output

Reader Output State / Polarity

Beeper

Output 1

POS 1 (Up = Normally Open)

POS 4 (Up = Off)

Output 2

POS 2 (Up = Normally Open)

POS 5 (Up = Off)

Output 3

POS 3 (Up = Normally Open)

POS 6 (Up = Off)

The switches at SW5 on the board control polarity and beeper activity for outputs 1, 2, and 3. Switches 1, 2, and 3 control polarity for outputs 1-3. Switches 4, 5, and 6 control the beeper for outpus 1-3.

Polarity

Beeper

Output 1

2

Output 3

1

2

Normally Open / Negative

3

OFF ON

Normally Closed / Positive Switches at SW5

1-14

MS-Connect 210 User’s Manual

Page 22

Setup and Operation

Beeper Characteristics at Power-On The MS-Connect 210 will beep at power-on for most readers. The duration of the beep depends upon which reader is connected. The table below shows which readers cause the MS-Connect 210 to beep at which durations. MS-3 MS-4 MS-9 MS-890 Quadrus MINI Quadrus MINI 3 Quadrus MINI Velocity

MS-Connect 210 Beep Duration* No beep at power-on < 3 seconds < 3 seconds ~ 3 seconds < 3 seconds < 3 seconds < 3 seconds

* Beep duration may vary depending on reader and firmware.

MS-Connect 210 User’s Manual

1-15

Page 23

Configure Output Settings

Configuring the Relays The MS-Connect 210’s three pluggable relay modules and three jumpers for controlling the relays are outlined below.

Relay Module Options K1 - K3 The two possible jumper configurations for JP1, JP2, and JP3 are shown below. Config A passes through the reader’s opto-isolated relays to the terminal block. Config B inserts the relay module between the reader’s output and the terminal block. Config A 5

3

1

6

4

2

Pass Through (Default)

JP1 JP2 JP3

Config B 5

3

1

6

4

2

Relay Module K1, K2, K3

1-16

MS-Connect 210 User’s Manual

Page 24

Setup and Operation

Using the 9-pin Configuration Port In applications without a communication cable wired to the host connector, you can use the 9-pin configuration port at J26 on the board to program the connected reader. Configuration port pinouts are on the reinforced paper insert inside the MS-Connect 210.

MS-Connect 210 User’s Manual

1-17

Page 25

Configure Output Settings

Using the Trigger and New Master Lockouts The Trigger and New Master lockouts allow you to disable the buttons on the front panel of the MS-Connect 210. When JP10 (New Master Lockout) and JP11 (Trigger Lockout) are in their Config B positions, the Trigger and New Master buttons on the front panel will be disabled.

The two possible jumper configurations for JP10 and JP11 are shown below. 1

2

3

1

2

3

1

2

3

1

2

3

Enabled (Default)

JP10 JP11 Lockout (Disabled)

1-18

MS-Connect 210 User’s Manual

Page 26

Setup and Operation

Power-On the MS-Connect 210 Once your reader is connected to the MS-Connect 210 and all other cabling is connected and secured, it is safe to turn on the system.

Note: If the polarity of your power connection is incorrect when you turn on the MS-Connect 210, the Power LED will illuminate as RED. If polarity is correct, the Power LED will illuminate as GREEN. The MS-Connect 210 has reverse-voltage circuit protection up to 30V to prevent damage to the wiring box and attached equipment. If the Power LED illuminates as RED, no power will be sent to the wiring box. Power will still be provided to the large green power terminals, but not to the smaller black terminals. Note: The power input terminal inside the wiring box (J1) is always powered-on, regardless of the power switch position.

MS-Connect 210 User’s Manual

1-19

Page 27

Install ESP

Install ESP Easy Setup Program (ESP) is Microscan’s proprietary setup and testing application. The purpose of ESP is to provide a quick and easy way to set up and configure Microscan products. When the MS-Connect 210 is connected to a host computer (Windows Vista, XP, or 2000), ESP can be used to configure Ethernet settings and to set up communications between the MS-Connect 210 and a host or network.

If installing from the Microscan Tools Drive:

1. Insert the Microscan Tools Drive into a USB port on your computer. 2. Select ESP Software from the navigation bar at the left of the screen. 3. Click on ESP Software under the Current Version heading. 4. Click the Run button and follow the prompts in the ESP Setup Wizard. Note: During installation, you may see an Internet Explorer Security Warning that states: “The publisher could not be verified.” If you see this warning, click Run to continue installation.

If downloading from the web: 1. Go to the Download Center at www.microscan.com. 2. Create a new member account or, if you are already a member, enter your user name and password. 3. Navigate to the “Microscan Software” section of the Download Center (near the top of the page). 4. Click on the link showing the latest version of ESP. Extract the ESP installation files to a location of your choice on the host computer. Note where your ESP.exe file is stored on your hard drive. 5. At the end of the installation process, the following icon will appear on your desktop:

6. Click the ESP icon to start the program.

System Requirements for ESP • 166 MHz Pentium processor (recommended) • Windows Vista, XP, or 2000 operating system • Internet Explorer 5.0 or higher • 64 MB minimum RAM • 40 MB minimum disk space • 800 x 600 pixel minimum 256 color display

1-20

MS-Connect 210 User’s Manual

Page 28

Setup and Operation

Select and Identify the MS-Connect 210 When you start ESP, you will see this menu:

Click the button showing the MS-Connect 210.

The following view will appear: Click Search to find the MS-Connect 210, then configure Ethernet and serial port settings in the interface shown below.

See Chapter 2, Using Ethernet, for information about getting the MS-Connect 210 ready for Ethernet TCP/IP or EtherNet/IP operation.

MS-Connect 210 User’s Manual

Click here to communicate with readers via a TCP/IP connection. Note: This option can also be configured in the ESP Preferences dialog.

1-21

Page 29

Select and Identify the MS-Connect 210

1-22

MS-Connect 210 User’s Manual

Page 30

2 Using Ethernet Contents Power-On the System................................................................................................................... 2-2 Select and Identify the MS-Connect 210 ...................................................................................... 2-3 Set Network Parameters............................................................................................................... 2-4 Set COM Port Parameters ............................................................................................................ 2-6 Select Reader Model and Connect ............................................................................................... 2-7 Configure the Connected Reader ................................................................................................. 2-8 Configuring the Ethernet Port ....................................................................................................... 2-9 Ethernet Port Custom Features .................................................................................................. 2-11 Ethernet Port Operation .............................................................................................................. 2-14 EtherNet/IP Serial Interface (Class 0x68) ................................................................................... 2-15 Input (T –>O) Assembly Object (Class 0x04, Instance 0x64) .................................................... 2-18 Output (O –>T) Assembly Object (Class 0x04, Instance 0x65) ................................................. 2-18 Configuration Assembly Object (Class 0x04, Instance 0x80) ..................................................... 2-18 Service-Object Summary ............................................................................................................ 2-18 RSLogix Examples...................................................................................................................... 2-19 EIPScan Examples ..................................................................................................................... 2-21 TFTP Services ............................................................................................................................ 2-22

The MS-Connect 210 supports EtherNet/IP™, an industrial communications protocol based on the Common Industrial Protocol (CIP™). EtherNet/IP can handle large amounts of data at high speeds, and it typically employs a star topology, making it easy to set up and maintain network communication over a wide area. An EtherNet/IP network can support several kinds of communication nodes, including mainframes, PCs, I/O devices and adapters, robots, and PLCs. This section describes how to configure the MS-Connect 210 for use with EtherNet/IP, as well as Ethernet TCP/IP.

MS-Connect 210 User’s Manual

2-1