Page 161

Matchcode

Wild Card Character Usage:

For example, with Wild Card Character defined as the default asterisk, defining CR*34 as the master symbol will result in matches for CR134, CR234, but not CR2345. Entering the wild card at the end of the master symbol as in CR*** will result in matches for variable symbol lengths such as CR1, CR23, CR358, etc. provided that the number of wild card characters matches or exceeds the number of characters present.

Definition:

Wild Card Character allows a user to define a wild card character as part of the master symbol.

Serial Cmd:

<K223,matchcode type,sequential matching,match start position, match length,wild card character,sequence on No Read,sequence on mismatch>

Default:

* (asterisk)

Options:

Any valid ASCII character

MS-890 Industrial Automation Scanner User’s Manual

7-7

Page 162

Matchcode Type

Sequence On No Read Usage:

Sequence On No Read is useful when the scanner needs to stay in sequence even if no decode occurs.

Definition:

When Sequence On No Read is Enabled and Matchcode is set to Sequential, the scanner sequences the master symbol on every match or No Read. When disabled, it does not sequence on a No Read.

Serial Cmd:

<K223,matchcode type,sequential matching,match start position, match length,wild card character,sequence on No Read,sequence on mismatch>

Default:

Enabled

Options:

0 = Disabled

1 = Enabled

As an example of Sequence on No Read Enabled, consider the following series of decodes: Master symbol 001 002 003 004 005 006 007

Decoded symbol 001 002 No Read 004 No Read No Read 007

Master symbol after decode 002 003 004 (sequenced on No Read) 005 006 (sequenced on No Read) 007 (sequenced on No Read) 008

As an example of Sequence on No Read Disabled, consider the following series of decodes: Master symbol 001 002 003 003 004 004 004

7-8

Decoded symbol 001 002 No Read 003 No Read No Read 004

Master symbol after decode 002 003 003 (not sequenced) 004 004 (not sequenced) 004 (not sequenced) 005

MS-890 Industrial Automation Scanner User’s Manual

Page 163

Matchcode

Sequence On Mismatch Note: Matchcode must be set to Sequential for this command to function. Usage:

Enable this parameter if every trigger event should have a decode and more than one consecutive mismatch may occur. Disable this parameter if every trigger event should have a decode but no more than one consecutive mismatch may occur.

Definition:

When set to Enabled, the master symbol sequences on every decode, match or mismatch. When set to Disabled, the master symbol will not sequence whenever consecutive mismatches occur.

Serial Cmd:

<K223,matchcode type,sequential matching,match start position, match length,wild card character,sequence on No Read,sequence on mismatch>

Default:

Disabled

Options:

0 = Disabled

1 = Enabled

The scanner will sequence the master to one more/less than the decoded symbol. As an example of Sequence On Mismatch Enabled, consider the following decodes: Master symbol 001 002 003 004 005 006 007

Decoded symbol 001 002 abc 004 def ghi 007

Master symbol after decode 002 003 004 (sequenced on mismatch) 005 006 (sequenced on mismatch) 007 (sequenced on mismatch) 008

As an example of Sequence On Mismatch Disabled, consider the following decodes: Master symbol 001 002 003 004 005 005 005

Decoded symbol 001 002 abc 004 def ghi 005

Master symbol after decode 002 003 004 (sequenced because of previous match) 005 005 (sequenced because of previous match) 005 (not sequenced because of previous mismatch) 006

You can access Master Symbol operations from the Utilities menu.

MS-890 Industrial Automation Scanner User’s Manual

7-9

Page 164

Sequence Step

Sequence Step Usage:

Useful in applications in which it is desirable to count by intervals other than 1.

Definition:

Sequencing in Matchcode operations can occur in steps from 1 to 32,768. Sequencing performs like a mechanical counter by displaying positive integers and a specific number of digits after rollovers. For example, 000 – 3 = 997 (not –3) and 999 + 3 = 002 (not 1002).

Serial Cmd:

<K228,sequence step>

Default:

1

Options:

1 to 32768

Note: See <K223> (Matchcode Type on page 7-5) for more information. As an example of Sequence Step, if Sequence Step is set to 3 and Sequential Matching is set to Increment. Master Symbol 003 003 003 006 006 006

7-10

Decoded Symbol 001 002 003 004 005 006

Master Symbol After Decode 003 003 006 006 006 009

MS-890 Industrial Automation Scanner User’s Manual

Page 165

Matchcode

New Master Pin Usage:

Some applications require the line worker to change the master symbol. This can be done by installing a switch at the location of the scanner. It is very common to have a keyed switch so that accidental switching does not occur.

Definition:

After New Master Pin is enabled, a pulse can be received on the new master pin which will cause the scanner to record the next decoded symbol(s) as the new master symbol(s). It is important to note that the enabling New Master Pin does not in itself cause a master symbol to be recorded. The master pin must then be activated momentarily (for a minimum of 10 ms) before a master symbol can be scanned into memory.

Serial Cmd:

<K225,status>

Default:

Disabled

Options:

0 = Disabled

1 = Enabled

After New Master Pin has been enabled and the pin activated, decodes will be saved in the master database beginning with master symbol #1. If the scanner is configured for a multisymbol read cycle (Number of Symbols is greater than 1), the remaining decodes will be saved in each consecutive master symbol location. For example, if Number of Symbols is set to 3 and New Master Pin is then activated, at the end of the next read cycle, the decoded symbols will be saved as master symbols 1, 2, and 3.

MS-890 Industrial Automation Scanner User’s Manual

7-11

Page 166

Match Replace

Match Replace Usage: Definition: Serial Cmd: Default: Options:

Provides a convenient shortcut for applications that need to output a predefined text string whenever a symbol matches a master symbol. Outputs a user-defined data string whenever a match occurs and Matchcode is enabled. <K735,status,replacement string> Disabled 0 = Disabled 1 = Enabled

Replacement String Definition: Serial Cmd: Default: Options:

7-12

User-defined data string that, when enabled, replaces symbol data whenever a match occurs. <K735,status,replacement string> MATCH 1 to 128 ASCII characters

MS-890 Industrial Automation Scanner User’s Manual

Page 167

Matchcode

Mismatch Replace Usage: Definition: Serial Cmd: Default: Options:

Provides a convenient shortcut for applications that need to output a predefined text string whenever a symbol does not match a master symbol. Outputs a user-defined data string whenever a mismatch occurs and Matchcode is enabled. <K736,status,replacement string> Disabled 0 = Disabled 1 = Enabled

Replacement String Definition: Serial Cmd: Default: Options:

User-defined data string that, when enabled, replaces symbol data whenever a mismatch occurs. <K736,status,replacement string> MISMATCH 1 to 128 ASCII characters

MS-890 Industrial Automation Scanner User’s Manual

7-13

Page 168

Mismatch Replace

7-14

MS-890 Industrial Automation Scanner User’s Manual

Page 169

8 Diagnostics Contents Diagnostics by ESP.......................................................................................................................8-2 Diagnostics Serial Commands ......................................................................................................8-2 Counts...........................................................................................................................................8-3 Hours Since Last Reset ................................................................................................................8-4 Warning Messages .......................................................................................................................8-5 Laser Current Warning..................................................................................................................8-7 Present Operating Temperature (Deg. C).....................................................................................8-8 High Temperature Threshold ........................................................................................................8-9 Low Temperature Threshold .......................................................................................................8-10 Lifetime Hours .............................................................................................................................8-11 Service Message.........................................................................................................................8-12

This section describes warning and operating messages and their settings. Important: Since Warning Messages and NOVRAM Messages are not enabled by default, these messages will not be displayed. However, if you suspect that erroneous defaults are occurring, enable Warning Messages and NOVRAM Messages by sending <K”400,1,,,1>. Note: The characters NUL, <, >, and , can only be entered through embedded menus, not through ESP or serial commands.

MS-890 Industrial Automation Scanner User’s Manual

8-1

Page 170

Diagnostics by ESP

Diagnostics by ESP

Click this button to bring up the Diagnostics menu.

To open nested options, single-click the +.

To change a setting, double-click the setting and use your cursor to scroll through the options.

Diagnostics Serial Commands Command Title Warning Message Status Lifetime Hours High Temperature Warning Low Temperature Warning Power-On/Resets Counts Hours Since Last Reset Present Operating Temperature Service Message Laser Current Warning

8-2

Command Format <K400,warning message status,laser high status,laser low status, NOVRAM/reset warning status> <K401,hours x 10,message> <K402,status,message> <K403,status,message> <K406?> returns: <K406,power-ons,resets,parameter saves> (Read-Only) <K407?> returns: <K407,hours,minutes> (Read-Only) <K408?> returns: <K408,current operating temp.> (Read-Only) <K409,status,message,time,resolution> <K411,high current status,high current message,low current warning, low current message>

MS-890 Industrial Automation Scanner User’s Manual