Page 101

Read Cycle

Multisymbol Usage: Definition: Conditions:

Multisymbol is commonly used in shipping applications where a shipping symbol contains individual symbols for part number, quantity, etc. This feature allows on trigger to pick up all the symbols. Multisymbol allows the user to define up to 100 symbols that can be read in a single read cycle. The following conditions apply: • Each symbol must be different to be read, unless in Rapid Capture Mode, configured for “triggered capture”. • The maximum number of characters in a read cycle is 3,000 for all symbols. • All No Read messages are posted at the end of the data string, unless output filtering is enabled. • If more than one symbol is within the field of view at the same time, symbol data may not be displayed in the order of appearance. • If Matchcode Type is set to Sequential or if Trigger is set to Continuous Read 1 Output, the Imager will behave as if Number of Symbols were set to 1, regardless of the user-defined configuration.

Number of Symbols Definition: Serial Cmd: Default: Options:

Number of Symbols is the number of different symbols that can be read in a single read cycle. <K222,number of symbols, multisymbol separator> 1 1 to 100

Multisymbol Separator Used to delimit or separate data fields with a user defined character. Any valid ASCII character, inserted between each symbol read when Multisymbol is set to any number greater than 1. Serial Cmd: <K222,number of symbols,multisymbol separator> Default: , (comma) Options: Any available ASCII character. Note: The ASCII characters <, >, and , can only be entered as hex pairs: For <: <K222h,,3C> For >: <K222h,,3E> For , : <K222h,,2C> See ASCII Character Entry Modifier on page 3-32 for a more detailed explanation of how to enter ASCII characters as hex values. Note: If No Read messages are disabled and there are No Reads occurring, separators will only be inserted between symbol data outputs. Usage: Definition:

MS-4 Imager User Manual

5-5

Page 102

Trigger Mode and Duration

Trigger Mode and Duration Trigger Definition:

The event that initiates the read cycle.

Note: When calibrating the Imager or testing read rate, the current trigger setting will be disregarded.

Trigger Mode Serial Cmd: Default: Options:

<K200,trigger mode,trigger filter duration> Continuous Read 0 = Continuous Read 1 = Continuous Read 1 Output 2 = External Level 3 = External Edge 4 = Serial Data 5 = Serial Data and External Edge

Continuous Read Usage: Definition:

Serial Cmd:

5-6

Continuous Read is useful in testing symbol readability or reader functions. It is not recommended for normal operations. In Continuous Read, trigger input options are disabled, the Imager is always in the read cycle, and it will attempt to decode and transmit every capture. If a single symbol stays within read range for multiple read cycles, its data will be transmitted repeatedly until it leaves the read range. The Imager sends replies to serial commands that require responses when symbol data is transmitted, or read cycle timeout is enabled and a timeout occurs and at least one captured image has been processed. Depending on the combination of enabled symbologies and the Threshold Mode setting, the Imager may take longer than the timeout to process a captured image. Note: When to Output and No Read options have no affect on Continuous Read. <K200,0>

MS-4 Imager User Manual

Page 103

Read Cycle

Continuous Read 1 Output Usage:

Definition:

Serial Cmd:

Continuous Read 1 Output can be useful in applications where it is not feasible to use a trigger and all succeeding symbols contain different information. It is also effective in applications where the objects are presented by hand. In Continuous Read 1 Output the Imager self-triggers whenever it decodes a new symbol or a timeout occurs. If End of Read Cycle is set to Timeout and the symbol doesn’t change, the output is repeated at the end of each timeout period. For example, if Timeout is set to one second, the Imager sends the symbol data immediately and repeats the output at intervals of one second for as long as it continues to capture the symbol. If End of Read Cycle is set to New Trigger, the Imager will send the current symbol data immediately, but only once. A new symbol appearing in the Imager’s range will be read and sent immediately, provided it is not identical to the previous symbol. <K200,1>

Caution: In automated environments, Continuous Read 1 Output is not recommended because there is typically no reliable way to verify that a symbol was missed. Note: If Trigger Mode is set to Continuous Read 1 Output, the Imager will behave as if Number of Symbols were set to 1, regardless of the user-defined configuration.

MS-4 Imager User Manual

5-7

Page 104

Trigger Mode and Duration

External Level Initiate Read Cycle: Object #1, moving in front of the detector beam, causes a change in the trigger state, which initiates the read cycle. End Read Cycle: The same object, moving out of the detector beam, causes another change in the trigger state, which ends the read cycle.

Usage:

Definition:

Serial Cmd:

This mode is effective in an application where the speeds of the conveying apparatus are variable and the time the Imager spends reading each object is not predictable. It also allows the user to determine if a No Read has occurred. External Level allows the read cycle (active state) to begin when a trigger (change of state) from an external sensing device is received. The read cycle persists until the object moves out of the sensor range and the active trigger state changes again. <K200,2>

Important: Level and Edge apply to the active logic state (Negative or Positive) that exists while the object is in a read cycle, between the rising edge and the falling edge. Rising edge is the trigger signal associated with the appearance of an object. Falling edge is the trigger signal associated with the subsequent disappearance of the object. This applies both to External Level and External Edge.

External Edge Initiate Read Cycle: Object # 1, moving in front of the detector beam, causes a change in the trigger state, which initiates the read cycle. Initiate Second Read Cycle: Object # 2, moving in front of the detector beam, causes another change in the trigger state. This signal initiates a new read cycle and ends the previous read cycle unless Timeout is enabled and a good read or timeout has not occured.

Usage: Definition:

Serial Cmd: 5-8

This mode is highly recommended in any application where conveying speed is constant, or if spacing, object size, or read cycle timeouts are consistent. External Edge, as with Level, allows the read cycle (active state) to begin when a trigger (change of state) from an external sensing device is received. However, the passing of an object out of sensor range does not end the read cycle. The read cycle ends with a good read output, or, depending on the End of Read Cycle setting, a timeout or new trigger occurs. <K200,3> MS-4 Imager User Manual

Page 105

Read Cycle

Serial Data Usage: Definition:

Serial Cmd:

Serial Data is effective in a highly controlled environment where the host knows precisely when the object is in the field of view. It is also useful in determining if a No Read has occurred. In Serial Data, the Imager accepts an ASCII character from the host or controlling device as a trigger to start a read cycle. A Serial Data trigger behaves the same as an External Edge trigger. Serial commands are entered inside angle brackets, as shown here: <t>. <K200,4>

Note: In Serial Data, sending a non-delimited start serial character will start a read cycle; however, a non-delimited stop serial character has no effect.

Serial Data or External Edge Usage:

Definition: Serial Cmd:

Serial Data or External Edge is seldom used but can be useful in an application that primarily uses an external sensing device but occasionally needs to be triggered manually. An auxiliary terminal can be connected to the auxiliary port so the user can send the serial trigger character through the Imager to the host. In this mode the Imager accepts either a serial ASCII character or an external trigger pulse to start the read cycle. <K200,5>

Note: In Serial Data, sending a non-delimited start serial character will start a read cycle; however, a non-delimited stop serial character has no effect.

MS-4 Imager User Manual

5-9

Page 106

Trigger Mode and Duration

Trigger Filter Duration Usage: Definition: Serial Cmd: Default: Options:

Trigger Filter Duration allows the Imager to disregard false trigger events. When Trigger Mode is set to either External Edge or External Level, the read cycle’s active state must be delayed until the specified filter duration has elapsed. The Imager will trigger at the end of that duration. <K200,trigger mode,trigger filter duration> 313 (x 32µs = 10.24mS) 1 to 65535 (corresponding with 32µs to 2.097seconds in 32µs steps)

Note: If Trigger Mode is set to External Edge, the Imager will trigger only after the active state has been delayed for the specified filter duration. Note: If Trigger Mode is set to External Level, the Imager will trigger once the active state has been delayed for the specified filter duration after the appearance of an object’s active edge. In addition, the active state must be delayed for the specified filter duration after the disappearance of the object’s falling edge for the trigger to be rendered inactive.

5-10

MS-4 Imager User Manual

Page 107

Read Cycle

External Trigger Polarity Usage: Definition: Serial Cmd: Default: Options:

Allows users to select the trigger polarity that will be used in their application. Determines the active state of the trigger signal applied to the cable input of the Imager. <K202,active state> Positive 0 = Negative 1 = Positive

MS-4 Imager User Manual

5-11

Page 108

Serial Trigger

Serial Trigger Usage: Definition:

Allows the user to define the trigger character and delimiters that start and stop the read cycle. A serial trigger is considered an online host command and requires the same command format as all host commands. It must be entered within angle bracket delimiters < > or, in the case of non-delimited triggers, it must define individual start and stop characters.

Serial Trigger Character (Delimited) Allows the user to define the trigger character that initiates the read cycle. A single ASCII host serial trigger character that initiates the read cycle. A delimited trigger character is one that either starts or ends the read cycle and is enclosed by delimiters such as < >. Serial Cmd: <K201,serial trigger character> Default: Space bar Options: Any single ASCII character, including control characters, except NUL (00 in hex), an existing host command character, or an on-line protocol character. Control characters entered on the command line are displayed in the menu as mnemonic characters. Note: Serial Data or Serial Data or External Edge triggering mode must be enabled for Serial Trigger Character to take effect. Usage: Definition:

Important: The ASCII characters <, >, and , can only be entered as hex pairs: For <: <K201h,3C> For >: <K201h,3E> For , : <K201h,2C> See ASCII Character Entry Modifier on page 3-32 for a detailed explanation of how to enter ASCII characters as hex values.

5-12

MS-4 Imager User Manual

Page 109

Read Cycle

Start Trigger Character (Non-Delimited) Usage: Definition:

Serial Cmd: Default: Options:

Useful in applications where different characters are required to start a read cycle. A single ASCII host serial trigger character that starts the read cycle and is not enclosed by delimiters such as < and >. Non-delimited Start characters can be defined and will function according to the trigger event. When defining Start trigger characters, the following rules apply: • In External Edge the Imager looks only for the Start trigger character and ignores any Stop trigger character that may be defined. • In External Level the Start trigger character begins the read cycle and the Stop trigger character ends it. Note that even after a symbol has been decoded and the symbol data transmitted, the Imager remains in External Level trigger read cycle until a Stop character is received. • In Serial Data or External Edge trigger mode, either a Start trigger character or a hardware trigger can start an edge trigger read cycle. <K229,start character> NUL (00 in hex) (disabled) Two hex digits representing any ASCII character.

Note: See ASCII Character Entry Modifier on page 3-32 for hex entry instructions.

Stop Trigger Character (Non-Delimited) Usage: Definition:

Serial Cmd: Default: Options:

Useful in applications where different characters are required to end a read cycle. A single ASCII host serial trigger character that ends the read cycle and is not enclosed by delimiters such as < and >. Non-delimited Stop characters can be defined and will function according to the trigger event. When defining Stop trigger characters, the following rules apply: • In External Edge the Imager looks only for the Start trigger character and ignores any Stop trigger character that may be defined. • In External Level the Start trigger character begins the read cycle and the Stop trigger character ends it. Note that even after a symbol has been decoded and the symbol data transmitted, the Imager remains in External Level trigger read cycle until a Stop character is received. • In Serial Data or External Edge trigger mode, either a Start trigger character or a hardware trigger can start an edge trigger read cycle. <K230,stop character> NUL (00 in hex) (disabled) Two hex digits representing any ASCII character.

Note: See ASCII Character Entry Modifier on page 3-32 for hex entry instructions. MS-4 Imager User Manual

5-13

Page 110

End of Read Cycle

End of Read Cycle Definition:

The read cycle is the time during which the Imager will attempt to capture and decode a symbol. A read cycle can be ended by a timeout, a new trigger, or by the last frame in a capture sequence or a combination of the above.

End of Read Cycle Mode

Note: When operating in Continuous Read or Continuous Read 1 Output, the Imager is always in the read cycle. Serial Cmd: Default: Options:

<K220,end of read cycle,read cycle timeout> Timeout 1 = New Trigger 0 = Timeout 3 = Last Frame 2 = Timeout or new Trigger 4 = Last Frame or New Trigger

Timeout Usage:

Definition:

5-14

Typically used with Serial Data or External Edge and Continuous Read 1 Output. It is effective in highly controlled applications when the maximum length of time between objects can be predicted. It assures that a read cycle ends before the next symbol appears, giving the system extra time to decode and transmit the data to the host. Timeout ends the read cycle, causing the reader to stop reading symbols and send the symbol data or No Read message when the time set in Timeout elapses (times out), if When to Output is set to End of Read Cycle. If in Continuous Read 1 Output, a timeout initiates a new read cycle and allows the same symbol to be read again. With External Edge, Serial Data, or Serial Data or External Edge enabled, a timeout ends the read cycle and symbol data or a No Read message is sent to the host. With External Level enabled, the read cycle does not end until the falling edge trigger occurs or a timeout occurs. The next read cycle does not begin until the next rising edge trigger.