Page 34

Leuze electronic

Installation 6.4.2 Connecting the BCL 80 with the Connector Unit MA 10 Connection of the BCL 80 is considerably easier when using the MA 10.

Sensor, Button

Voltage supply Switching output

BCL 80

MA 10

Host interface RS 232, RS 485 RS 422 or TTY

Connection cable BCL / MA 10 Figure 6.10: Connecting the BCL 80 with the connector unit MA 10

Open the MA 10 housing • Loosen the four Phillips screws on the back side of the MA 10 and carefully lift off the part with the electronics on it. The two halves of the housing are now connected to each other only by the ribbon cable. You can now disconnect the ribbon cable from the electronic circuit board for better access, as shown in Figure 6.11.

Figure 6.11: Disconnecting the ribbon cable inside the MA 10 • To disconnect the ribbon cable, carefully press down the two latches of the ribbon cable plug at the same time, as shown in of Figure 6.11.

ó

€

The cable is now free ( in Figure 6.11) and the half with the electronics and the connection terminal can be removed for unhindered connection. • To reconnect the ribbon cable, insert the ribbon cable plug back into its socket, observing the correct orientation, until it securely latches.

32

Technical Description BCL 80

Leuze electronic

Page 35

Leuze electronic

Installation

Note! All electrical connections can be carried out on the terminal strip quickly and without screwing down or soldering. Wires with ferruled ends can be inserted directly into the terminal without depressing the clamping lever.

The clamp is opened by depressing the orange coloured clamping lever. The wire can then be inserted into the terminal. By releasing the clamping lever, the wire is fixed into the terminal.

Figure 6.12: Wiring to the terminal strip without screwing down or soldering

TNT 35/7-24V

Attention! The pin assignment of the connection terminals depends on the inserted interface module. Leuze offers four modules which can be used with the serial interfaces RS 485, RS 232, TTY or RS 422. The terminal designations are printed on the module.

Attached label with the pin assignments of the interface

Terminal strip Attached label with the terminal names Cable screw glands PG9 and PG11 Figure 6.13: Position of the connections for the MA 10

Leuze electronic

Technical Description BCL 80

33

Page 36

Leuze electronic

Installation Type overview

The following table lists the MA 10 device types and which interface is installed. MA 10 100 MA 10 110 MA 10 120 MA 10 130

RS 485 interface RS 232 interface TTY interface RS 422 interface

• Make the connections to the terminal strip as described below.

Wiring description Terminals 1 through 6 are used depending on the type of interface: RS 232 Terminal 1 2 3 4 5 6

Signal RXD TXD CTS RTS not used GND

RS 422 Terminal 1 2 3 4 5 6

Signal TX+ TXRX+ RXnot used GND

RS 485 Terminal 1 2 3 4 5 6

Signal 485A 485A 485B 485B GND GND

TTY Terminal 1 2 3 4 5 6

Signal TX+ TXRX+ RXnot used GND shield shield

RS 485 Interface Host interface module max. 1200m Figure 6.14: Connecting the MA 10 to a RS 485 Host

34

Technical Description BCL 80

Leuze electronic

Page 37

Leuze electronic

Installation

RS 232 Interface Host interface module RS 232 shield max. 10m Figure 6.15: Connecting the MA 10 to a RS 232 Host

Notice for connecting the RS 232 interface! The wiring for RTS and CTS must only be connected, if RTS/CTS hardware-handshake is used. TTY interface MA 10 active / Host passive shield

Host interface module

TNT 35/7-24V shield

Ground (shield)

max. 1000m Jumper position active

Figure 6.16: Connecting the MA 10 as active subscriber to a TTY Host MA 10 passive / Host active shield

Host interface module shield

Jumper

Jumper Ground (shield)

max. 1000m Jumper position passive

Figure 6.17: Connecting the MA 10 as passive subscriber to a TTY Host

Leuze electronic

Technical Description BCL 80

35

Page 38

Leuze electronic

Installation

Remarks for connecting the TTY interface! • The active subscriber is the one which supplies the current (20 mA). • Switching between active/passive on the host interface card is carried out using two jumper pairs, independent for transmit (Tx) and for receive (Rx). • The jumpers for active/passive switching must always be changed in pairs (upper and lower jumpers in the same position). This switches the MA 10 host interface module power source and GND internally. • Mixed operation is possible (transmit active/receive passive or the opposite). • When switching from active to passive operation or the reverse, the wiring of the connection cable (pin order) changes. RS 422 Interface Host interface module shield max. 1200m

Figure 6.18: Connecting the MA 10 to a RS 422 Host The additional pins are uniformly assigned for all MA 10 models and are described below.

Switching inputs The MA 10 has two galvanically isolated switching inputs SE1 and SE2. • Input voltage: 12 … 36 V DC / AC. • Insulation voltage: 500 V Each switching input has an optical coupler and is wired with a protection resistor. The switching voltage and GND can be externally applied or taken from the operating voltage VDD_SE and GND_SE. Terminal 7 8 9 10 11 12

36

Signal SE2_A SE2_B SE1_A SE1_B VDD_SE GND_SE

Function switching input 2, connection A switching input 2, connection B switching input 1, connection A switching input 1, connection B supply voltage, switching input, equal to V_IN device supply voltage, switching input, equal to GND_IN device

Technical Description BCL 80

Leuze electronic

Page 39

Leuze electronic

Installation

Supply voltage MA 10 / BCL 80 18 … 36 V

MA 10 External switching voltage

Optically coupled switched input to processor

Figure 6.19: Connection of the switching input with an external switching voltage

Sensor/ optical sensor

Supply voltage MA 10 / BCL 80 18 … 36 V

MA 10 Optically coupled switched input

Figure 6.20: Connection of the switching input without an external switching voltage

Switching outputs The MA 10 comes standard with two switching outputs (SA1 and SA2) that can be programmed for various switching functions using the BCL software. • Output voltage: 5 … 48 V DC • Insulation voltage: 250 V (only in combination with connection type b) • Output current: Imax = 500 mA (at VDD_SA = 5 … 32 V) Imax = 300 mA (at VDD_SA = 32 … 48 V) The switching voltage can be connected in two different ways: a

The operating voltage V_IN is used as the switching voltage VDD_SA (factory setting): VDD_SA = V_IN GND_SA = GND_IN b

An external voltage is connected as the switching voltage (galv. decoupled) VDD_SA ≠ V_IN GND_SA ≠ GND_IN

Leuze electronic

Technical Description BCL 80

37

TNT 35/7-24V to processor

Page 40

Leuze electronic

Installation Terminal 13 14 15 16

Signal SA2 SA1 VDD_SA GND_SA

Function Switching output 2 switching output 1 external voltage supply for switched output 5 … 48 V DC external voltage supply for switched output 0 V DC

Switching outputs

JL6

JL5

GND_SA

SA2 SA1

Scratch through here

VDD_SA

13 14 15 16

Scratch through here

Galvanic decoupling of the switched output Galvanic decoupling is achieved by carefully scratching through the two solder jumpers JL5 and JL6 so that there is no longer an electrical connection. The switched output is then galvanically decoupled from the operating voltage. The solder jumpers are located on the circuit board of the MA 10 directly across from the connection terminals VDD_SA and GND_SA.

Figure 6.21: Position of the solder jumpers JL5 and JL6

V_IN JL6 solder jumper

Optically coupled switched input VDD_SA SA1/2

RL

GND_SA from processor JL5 solder jumper

GND_IN

MA 10

Figure 6.22: Operating voltage used as the switching voltage

V_IN

JL6 solder jumper open

Optically coupled switched input VDD_SA

U

SA1/2

RL

GND_SA from processor JL5 solder jumper open

GND_IN

MA 10 Figure 6.23: Switching voltage connected externally (galvanically decoupled)

38

Technical Description BCL 80

Leuze electronic

Page 41

Leuze electronic

Installation

Controlling the function of the switching outputs The function of the switching outputs can be controlled by removing the cover to the MA 10. Sitting directly next to the connection terminals for the switching outputs are red SMD-LEDs that illuminate when the respective switching output is in the HI state (log.1). Please note that the event which sets the switching outputs must be set and activated in the software setup of the BCL 80.

Supply voltage Terminal 17 18 19 20 21 22

Signal V_IN V_IN GND_IN GND_IN PE PE

Function Operating voltage +18 … 36 V DC Operating voltage +18 … 36 V DC Operating voltage 0 V DC Operating voltage 0 V DC Protective earth, grounding Protective earth, grounding

6.4.3 Wire Lengths and Shielding

Connection BCL 80 - MA 10

Interface RS 232 / RS 485

Max. wire length 10 m

BCL 80 - Host

RS 232 / RS 485

10 m

MA 10 - Host

RS 485

1200 m

MA 10 - Host

RS 422

1200 m

MA 10 - Host

RS 232

10 m

MA 10 - Host

TTY

1000 m

Switched inputs Switched outputs

10 m 10 m

Shielding absolutely required, braided shielding absolutely required, braided shielding absolutely required, flexible leads as twisted pairs absolutely required, flexible leads as twisted pairs absolutely required, flexible leads as twisted pairs not required loop resistance < 100 Ω not necessary not necessary

6.4.4 Disassembling, Packing, Disposing Repacking For later reuse, the device is to be packed so that it is protected against shocks and dampness. Optimal protection is achieved when using the original packaging.

Note! Electrical scrap is a special waste product! Observe the locally applicable regulations regarding disposal of the product.

Leuze electronic

Technical Description BCL 80

39

TNT 35/7-24V

The following maximum lengths for wires and the type of shielding to be used must be observed: