Page 46
Leuze electronic
Online commands
11
Online commands
11.1
Overview of Commands and Parameters Online commands can be used to send commands directly to the device for control and configuration. For this, the BCL 8 has to be connected to a computer via the serial interface. For information on the transmission protocol, please see chapter 7.3.2. Using the "Online" commands you can: • • • • • • •
Control/decode the reading gate. Read/write/copy parameters. Carry out an automatic configuration. Teach/set a reference code. Call up error messages. Call up statistical device information. Carry out a software reset in order to reinitialise the device.
Syntax "Online" commands consist of one or two ASCII characters followed by command parameters. No separation characters may be entered between the command and the command parameter(s). Both small and capitalised letters may be used. Example: Command ’CA’:
autoConfig function
Parameter ’+’:
Activation
Transmitted is:
’CA+’
Notation Commands, command parameters and returned data are enclosed between single quotation marks ’ ’. Most "online" commands are acknowledged by the BCL 8 and any requested data returned. For commands that are not acknowledged, command execution can be observed or monitored directly on the device.
44
BCL 8
Leuze electronic
Page 47
Leuze electronic
Online commands
11.1.1 General "Online" Commands Software version number Command
’V’
Description
Requests device version information
Parameter no
Acknowledgement
Ex.: ’BCL 8 V 01.00 08.01.2003’ The device type appears in the first line followed by the devices version number and date. The data which are actually displayed may vary from the values given here.
Notice! You can use this command to check whether the communication to the connected computer is functional. If you do not receive an acknowledgement, please check the interface connections, or the protocol.
Software reset Command
’H’
Description
Carries out a software reset. The device is restarted and reinitialised, leaving it in the same state as when the supply voltage is switched on.
Parameter no
TNT 35/7-24V
Acknowledgement ’S’ (start signal)
Leuze electronic
BCL 8
45
Page 48
Leuze electronic
Online commands autoConfig Command
’CA’
Description
Activates or deactivates the ’autoConfig’ function. Certain label reading parameters are programmed automatically in the setup by the labels which are read while the "autoConfig" function is active.
Parameter
’+’ ’/’ ’-’ activates ’autoConfig’ rejects the last code read deactivates ’autoConfig’ and stores the decoded data in the current parameter set
’CSx’ x: status ’0’ valid ’CA’ command ’1’ invalid command Acknowledgement ’2’ autoConfig could not be activated ’3’ autoConfig could not be deactivated ’4’ Result could not be deleted
Description
46
’xx yy zzzzzz’ xx: Code type of the read code ’01’ 2/5 Interleaved ’02’ Code 39 ’06’ UPC (A, E) ’07’ EAN ’08’ Code 128, EAN 128 ’10’ EAN/UPC ’11’ Codabar yy Number of digits of the code detected zzzzzz Contents of the decoded label. The ’ appears if the label was not correctly read.
BCL 8
Leuze electronic
Page 49
Leuze electronic
Online commands
Manual definition of the reference code Command
RS
Description
This command can be used to define a new reference code in the BCL 8 by means of direct entry via the serial interface. The data are saved in the parameter set according to their input under reference code 1 or 2 and stored in the working buffer for further processing.
Parameter
’RSyvxxzzzzzzzz’ y, v, x and z are placeholders (variables) for the actual input. y: def. reference code No ’1’ (Code 1) ’2’ (Code 2) v Storage location for reference code: ’0’ RAM+EEPROM ’3’ only RAM xx def. Code type (see Command ’CA’) z def. Code information (1 … 63 characters)
’RSx’ x: status ’0’ valid ’Rx’ command ’1’ invalid command Acknowledgement ’2’ insufficient memory for reference code ’3’ reference code has not been saved ’4’ reference code invalid Input = ’RS130678654331’ (Code 1 (1), only RAM (3), UPC (06), code information) TNT 35/7-24V
Example
Leuze electronic
BCL 8
47
Page 50
Leuze electronic
Online commands Teach-In Command
’RT’
Description
This command enables a reference code to be defined quickly by reading an example label.
Parameter
’RTy’ y: function ’1’ defines reference code 1 ’2’ defines reference code 2 ’+’ activates the definition of reference code 1 or 2 ’-’ exit the Teach-In process
The BCL 8 first responds with the command ’RS’ and corresponding status (see Command RS). After a barcode has been read, it sends the result in the following format: ’RCyvxxzzzzz’ y, v, x and z are placeholders (variables) for the actual input. y: def. reference code No ’1’ (Code 1) Acknowledgement ’2’ (Code 2) v: Storage location for the reference code ’0’ RAM+EEPROM ’3’ only RAM xx def. Code type (see Command ’CA’) z def. Code information (1 … 63 characters) Notice! With this function, only code types are recognised that are identified using the autoConfig function or which were set in the set-up. © After each reading via an ’RTy’ command, explicitly switch off the function again since failure to do so will interfere with other commands as well as prevent execution of a new ’RTy’ command.
48
BCL 8
Leuze electronic
Page 51
Leuze electronic
Online commands
Reading a reference code Command
’RR’
Description
The command reads out the reference code defined in the BCL 8. If no parameters are specified, all defined codes are output.
Parameter
<Reference code number> ’1’ reference code 1 ’2’ reference code 2
TNT 35/7-24V
If no reference codes are defined, the BCL 8 responds with the ’RS’ command and corresponding status (see Command RS) .For valid codes, the output corresponds to the following format: RCyvxxzzzzzz y, v, x and z are placeholders (variables) for the actual input. y: def. reference code No ’1’ (Code 1) Acknowledgement ’2’ (Code 2) v: Storage location for the reference code ’0’ RAM+EEPROM ’3’ only RAM xx def. Code type (see Command ’CA’) z def. Code information (1 … 63 characters)
Leuze electronic
BCL 8
49
Page 52
Leuze electronic
Online commands 11.1.2
’Online’ Commands for System Control Activate sensor input Command
’+’
Description
The command activates decoding.
Parameter no
Acknowledgement no
Deactivate sensor input Command
’-’
Description
The command deactivates decoding.
Parameter no
Acknowledgement no
Activate switching output ’OA’
Command Description
The command activates a selected switching output.
Parameter
’OAx’: Activate switching output x: Switching output No ’1’ (Output 1)
Acknowledgement no
Deactivate switching output Command
’OD’
Description
The command deactivates a selected switching output.
Parameter
’ODx’: Deactivate switching output x: Switching output No ’1’ (Output 1)
Acknowledgement no
50
BCL 8
Leuze electronic
Page 53
Leuze electronic
Online commands
11.1.3 ’Online’ Commands for Parameter Set Operations Definitions • <BCC type> type of the checksum calculation. ’0’: no checksum ’3’: XOR checksum (mode 3) • <PS type> type of the parameter set ’0’: current parameter set (data stored in the EEPROM non-volatile) ’1’: reserved ’2’: standard parameter set (not changeable) ’3’: operating values (data in the RAM, will be lost after reset) • <Status> mode of the parameter processing '0': does not perform a reset following the write operation; no other parameters follow. '1': does not perform a reset following the write operation; other parameters follow. '2': subsequently performs a reset, no other parameters follow. • <Start address> Relative address of the parameter within the parameter set
Decimal
HEX
Transmission
4660
0x1234
’1’ ’2’ ’3’ ’4’ = 31h 32h 33h 34h
• Para0H = 31h, Para0L = 32h, Para1H = 33h, Para1L = 34h Taking into consideration the maximum message length and the remaining command parameters, a maximum of 123 bytes of parameter data (246 bytes of message data) can be transmitted at one time. valid values: '0' … '9', 'A' … 'F' • <Acknowledgement>: Acknowledgement of the transmitted message ’0’ valid transmission ’1’ invalid message ’2’ invalid length of message ’3’ invalid block check type ’4’ invalid block check checksum ’5’ invalid data length ’6’ invalid message data ’7’ invalid start address ’8’ invalid parameter set ’9’ invalid parameter type Leuze electronic
BCL 8
51
TNT 35/7-24V
• <Para0L> <Para0H>… <Para122L> <Para122H>: Parameter-set data of the message. The sequence of the data is arranged identically to the BCL 8, i.e. when a word is transmitted, first the low byte is sent then the high byte. The parameter-set data are converted for transmission from HEX format to a 2byte-ASCII format. In the conversion two ASCII characters - representing the lower and higher nibbles - are created for each HEX value. Example:
Page 54
Leuze electronic
Online commands Copy parameter set Command
’PC’
Description
The command copies complete parameter sets.
Parameter
’03’ copy parameters from the EEPROM into the RAM and initialise all associated functions '20' copy standard parameters from the FLASH into the EEPROM and RAM and initialise all relevant functions ’30’ copy parameters from the RAM into the EEPROM
’PSx’ x: status '0' valid transmission '1' invalid message '2' invalid message length '3' invalid block check type Acknowledgement '4' invalid block check checksum '5' invalid data length '6' invalid message data '7' invalid start address '8' invalid parameter set '9' invalid parameter type
Request parameter set from the BCL 8 Command
’PR’
Description
The command requests parameter data from the BCL 8. The parameter <PS-Type> indicates from which parameter set the data are to be transmitted
Parameter
<BCC type> <PS type> <Start address> <Data length>
’PSx’ x: status '0' valid transmission '1' invalid message '2' invalid message length '3' invalid block check type Acknowledgement '4' invalid block check checksum '5' invalid data length '6' invalid message data '7' invalid start address '8' invalid parameter set '9' invalid parameter type
52
BCL 8
Leuze electronic
Page 55
Leuze electronic
Online commands
Acknowledge parameter message Command
’PS’
Description
The command acknowledges the received message and delivers an acknowledgement status which indicates whether the message was valid or invalid.
Parameter
’PSx’ x: status '0' valid transmission '1' invalid message '2' invalid message length '3' invalid block check type '4' invalid block check checksum '5' invalid data length '6' invalid message data '7' invalid start address '8' invalid parameter set '9' invalid parameter type
Command
’PT’
Description
The command transmits parameter data from the specified address and stores them in an intermediate buffer. If the status indicates that additional messages follow, they are also stored in the intermediate buffer before being stored under the appropriate parameter-set type in the EEPROM. The transmission can optionally take place with a block-check test of the message data
Parameter
<BCC type> <PS type> <Status> <Start address> <Para0L> <Para0H> [… <Para122L>][<BCC>]
’PSx’ x: status '0' valid transmission '1' invalid message '2' invalid message length '3' invalid block check type Acknowledgement '4' invalid block check checksum '5' invalid data length '6' invalid message data '7' invalid start address '8' invalid parameter set '9' invalid parameter type
Leuze electronic
BCL 8
53
TNT 35/7-24V
Transmit parameters