For the Leuze BCL-40
Page 39
Leuze electronic 6.3
Installation
Connection Attention! Never open the device yourself, as this may compromise protection class IP 65. Before connecting the device, be sure that the supply voltage agrees with the value printed on the nameplate. Connection of the device and maintenance work while under voltage must only be carried out by a qualified electrician. The power supply unit used to power the BCL 40 and MA 10 must have protected electrical separation by way of a safety transformer with double insulation according to DIN VDE 0551 (IEC 742). Be sure that the earthing conductor is connected correctly. Error-free operation is only guaranteed when the device is properly earthed.
TNT 35/7-24V
If faults cannot be corrected, the device should be removed from operation and protected against possible use.
Leuze electronic
BCL 40
37
Page 40
Leuze electronic
Installation 6.3.1
Connecting the BCL 40 for "Stand Alone" Operation If you would like to connect the BCL 40 for "stand alone" operation, you must make a corresponding connector cable with a 15 pin Sub D plug (female) for the following connections: • power supply of 18 … 36VDC, 5W max. power • host RS 232 interface, or RS 485 when operating as a "multiNet slave" • a sensor connection for triggering a read process
Sensor connection (photoelec. sensor, key) for trigVoltage supply gering a read 18 … 36VDC process
Interface Host RS 485 / RS 232 RS 232 Terminal interface for commissioning and service
15 pin Sub D female connector
Figure 6.7:
Connecting the BCL 40 for "Stand Alone" Operation
Attention! When using a normal 15 pin Sub D plug, the device only has a protection class of IP 54 instead of IP 65! Therefore, use the original Leuze cable from the accessories list. These cables are fitted with a seal so that protection class IP 65 is maintained.
Switching inputs A read process can be triggered by applying a voltage of 12 … 36VDC to the switched input connections "Sensor 1A" and "Sensor 1B". The switched input maintains an electrical separation of up to max. 250V.
38
BCL 40
Leuze electronic
Page 41
Leuze electronic
Installation
BCL 40 Sub D pin assignments
1 2 3 4 5 6 7 8
GND Sensor 1A CTS (Host) RTS (Host) TXT Service MODE-F reserved V_IN
9 10 11 12 13 14 15
Sensor 1B NC RXD (Host) TXD (Host) RXD Service MODE-S GND_IN
15 pin Sub D type connector (male) Insert a resistor R = 220 W / 0.25W here, if the device is the last subscriber on the RS 485 data line. Do not use a resistor, if the RS 485 line continues.
Operating mode
Figure 6.8:
Leuze electronic
TNT 35/7-24V
4
Connection diagram for the Sub D connector plug
BCL 40
39
Page 42
Leuze electronic
Installation Wiring description
6.3.2
Pin 1
GND
0V signal reference potential (RS 232 / RS 485)
Pin 2
Sensor 1A switched input 1A, 12 … 36VDC, see figure 6.18 and figure 6.19 for wiring
Pin 3
CTS (Host)
Pin 4
RTS (Host)
RTS signal, host interface RS 232 / RS 485 B
Pin 5
TXD Service used when MA 10 is connected / without MA 10: service interface, standard protocol
Pin 6
MODE_F
RS 232: open; RS 485: connect with MODE_S
Pin 7 reserved must not be used
Pin 8
V_IN supply voltage +18 … 36VDC
Pin 9
Sensor 1B switched input 1B, 12 … 36VDC, see figure 6.18 and figure 6.19 for wiring
CTS signal, host interface RS 232 / RS 485 B
Pin 10
NC not used
Pin 11
RXD (Host)
RXD signal, host interface RS 232 / RS 485 A
Pin 12
TXD (Host)
TXD signal, host interface RS 232 / RS 485 A
Pin 13
RXD service used when MA 10 is connected / without MA 10: service interface, standard protocol
Pin 14
MODE_S
RS 232: open; RS 485: connect with MODE_F
Pin 15
GND_IN supply voltage 0VDC
Table 6.1:
Wiring description BCL 40
Connecting the BCL 40 with the connector unit MA 10 Connection of the BCL 40 is considerably easier when using the MA 10. Sensor, Button
Power supply
Switching output host interface RS 232, RS485, RS422 or TTY
Connection cable BCL 40 / MA 10
Figure 6.9: 40
Connecting the BCL 40 with the connector unit MA 10 BCL 40
Leuze electronic
Page 43
Leuze electronic
Installation
Open the MA 10 housing © Loosen the four Phillips screws on the back side of the MA 10 and carefully lift off the part with the electronics on it. The two halves of the housing are now connected to each other only by the ribbon cable. You can now disconnect the ribbon cable from the electronic circuit board for better access, as shown in figure 6.10.
Figure 6.10: Disconnecting the ribbon cable inside the MA 10 © To disconnect the ribbon cable, carefully press down the two latches of the ribbon cable plug at the same time, as shown in figure 6.10 of €. The cable is now free (ó in figure 6.10) and the half with the electronics and the connection terminal can be removed for unhindered connection. © To reconnect the ribbon cable, insert the ribbon cable plug back into its socket, observing the correct orientation, until it securely latches.
All electrical connections can be carried out on the terminal strip quickly and without screwing down or soldering. Wires with ferruled ends can be inserted directly into the terminal without depressing the clamping lever.
Leuze electronic
BCL 40
41
TNT 35/7-24V
Notice!
Page 44
Leuze electronic
Installation
The clamp is opened by depressing the orange coloured clamping lever. The wire can then be inserted into the terminal. By releasing the clamping lever, the wire is fixed into the terminal.
Figure 6.11: Wiring to the terminal strip without screwing down or soldering Attention The pin assignment of the connection terminals depends on the inserted interface module. Leuze offers four modules which can be used with the serial interfaces RS 485, RS 232, TTY or RS 422. The terminal designations are printed on the module.
Attached label with the pin assignments of the interface
Terminal strip
Attached label with the terminal names
Cable screw glands PG9 and PG11
Figure 6.12: Position of the connections for the MA 10
42
BCL 40
Leuze electronic
Page 45
Leuze electronic
Installation
Type overview The following table lists the MA 10 device types and which interface is installed. MA 10 100
RS 485 interface
MA 10 110
RS 232 interface
MA 10 120
TTY interface
MA 10 130
RS 422 interface
© Make the connections to the terminal strip as described below.
Wiring description Terminals 1 through 6 are used depending on the type of interface:
RS 232
RS 422
Terminal
Signal
Terminal
Signal
1
RXD
1
TX+
2
TXD
2
TX-
3
CTS
3
RX+
4
RTS
4
RX-
5 not used
5 not used
6
GND
6
GND TTY
Terminal
Signal
Terminal
Signal
1
485A
1
TX+
2
485A
2
TX-
3
485B
3
RX+
4
485B
4
RX-
5
GND
5 not used
6
GND
6
GND
Leuze electronic
BCL 40
TNT 35/7-24V
RS 485
43