Page 46
Leuze electronic
Installation RS 485 interface
Host interface module Shield 485A
485A
485B
485B
GND
GND
R S48 5 1 2 3 4 5 6
Host
Shield
485A 485A 485B 485B GND GND
1 2 3 4 5
6 up to 1200m
Figure 6.13: Connecting the MA 10 to a RS 485 Host
RS 232 interface
Host interface module RS232 1 2 3 4 5 6
Host
RXD TXD CT S RT S GND
Shield
R XD TX D C TS R TS GN D
1
2 3 4 5 6 up to 10m
Figure 6.14: Connecting the MA 10 to a RS 232 Host Notice for connecting the RS 232 interface: The wiring for RTS and CTS must only be connected, if RTS/CTS hardware-handshake is used.
44
BCL 40
Leuze electronic
Page 47
Leuze electronic
Installation
TTY interface MA 10 active / Host passive
Host interface module
Shield Shield
Ground (shield)
up to 1000m Jumper position active
Figure 6.15: Connecting the MA 10 as active subscriber to a TTY Host MA 10 passive / Host active
Shield
Host interface module Shield
TNT 35/7-24V
Jumper
Jumper Ground (shield)
up to 1000m Jumper position passive
Figure 6.16: Connecting the MA 10 as passive subscriber to a TTY Host Hints for connecting the TTY interface: The active subscriber is the one which supplies the current (20mA). Switching between active/passive on the host interface card is carried out using two jumper pairs, independent for transmit (Tx) and for receive (Rx).
Leuze electronic
BCL 40
45
Page 48
Leuze electronic
Installation
The jumpers for active/passive switching must always be changed in pairs (upper and lower jumpers in the same position). This switches the MA 10 host interface module power source and GND internally. Mixed operation is possible (transmit active/receive passive or the opposite). When switching from active to passive operation or the reverse, the wiring of the connection cable (pin order) changes.
RS 422 Interface
Host interface module R S 422
1 2 3 4 5 6
Host
R x+ R xTx+ TxG ND
TX + 1 TX - 2 RX+ 3 RX- 4 5 GND 6
Shield up to 1200m
Figure 6.17: Connecting the MA 10 to a RS 422 Host The additional pins are uniformly assigned for all MA 10 models and are described below.
Switching inputs 1 and 2 Switching inputs The MA 10 has two galvanically isolated switching inputs SE1 and SE2. • Input voltage: 12 … 36VDC/AC. • Insulation voltage: 500V Each switching input is supplied with bi-directional optical couplers and protective resistors. The switching voltage and GND can be externally applied or taken from the operating voltage VDD_SE and GND_SE.
46
BCL 40
Leuze electronic
Page 49
Leuze electronic
Installation
Terminal
Signal
Function
7
SE2_A switching input 2, connection A
8
SE2_B switching input 2, connection B
9
SE1_A switching input 1, connection A
10
SE1_B switching input 1, connection B
11
VDD_SE supply voltage, switching input, equal to V_IN device
12
GND_SE supply voltage, switching input, equal to GND_IN device
Supply voltage MA 10 / BCL 40: 18 … 36V
MA 10 External switching voltage
Optically coupled switched input to processor
TNT 35/7-24V
Figure 6.18: Connection of the switching input with an external switching voltage
Sensor/ optical sensor
Supply voltage MA 10 / BCL 40: 18 … 36V
MA 10 Optically coupled switched input to processor
Figure 6.19: Connection of the switching input without an external switching voltage
Leuze electronic
BCL 40
47
Page 50
Leuze electronic
Installation Switching outputs 1 and 2 Switching outputs
The MA 10 comes standard with two switching outputs (SA1 and SA2) that can be programmed for various switching functions using the BCL software. • Output voltage: 5 … 48VDC • Insulation voltage: 250V (only in combination with connection type b)) • Output current: Imax = 500mA (at VDD_SA = 5 … 32V) Imax = 300mA (at VDD_SA = 32 … 48V) The switching voltage can be connected in two different ways: • The operating voltage V_IN is used as the switching voltage VDD_SA (factory setting): VDD_SA = V_IN GND_SA = GND_IN • An external voltage is connected as switching voltage (galv. decoupled) VDD_SA V_IN GND_SA GND_IN Terminal
Signal
Function
13
SA2
Switching output 2
14
SA1
Switch 1
15
VDD_SA external voltage supply for switched output 5 … 48VDC
16
GND_SA external voltage supply for switched output 0VDC
Switching outputs
JL6
JL5
GND_SA
SA2 SA1
Scratch through here
VDD_SA
13 14 15 16
Scratch through here
Galvanic decoupling of the switched output Galvanic decoupling is achieved by carefully scratching through the two solder jumpers JL5 and JL6 so that there is no longer an electrical connection. The switched output is then galvanically decoupled from the operating voltage. The solder jumpers are located on the circuit board of the MA 10 directly across from the connection terminals VDD_SA and GND_SA.
Figure 6.20: Position of the solder jumpers JL5 and JL6
48
BCL 40
Leuze electronic
Page 51
Leuze electronic
Installation
V_IN JL6 solder jumper Optically coupled switched input
VDD_SA from processor
SA1/2
RL
GND_SA JL5 solder jumper GND_IN
MA 10
Figure 6.21: Operating voltage used as the switching voltage
V_IN
JL6 solder jumper open Optically coupled switched input
VDD_SA
U from processor
SA1/2 GND_SA
TNT 35/7-24V
RL
JL5 solder jumper open GND_IN
MA 10 Figure 6.22: Switching voltage connected externally (galvanically decoupled)
Controlling the function of the switching outputs The function of the switching outputs can be controlled by removing the cover to the MA 10. Sitting directly next to the connection terminals for the switching outputs are red SMD-LEDs that illuminate when the respective switching output is in the HI state (log.1). Please note that the event which sets the switching outputs must be set and activated in the software setup of the BCL 40.
Leuze electronic
BCL 40
49
Page 52
Leuze electronic
Installation Supply voltage
6.3.3
Terminal
Signal
Function
17
V_IN
Operating voltage +18 … 36VDC
18
V_IN
Operating voltage +18 … 36VDC
19
GND_IN
Operating voltage 0VDC
20
GND_IN
Operating voltage 0VDC
21
PE
Protective earth, grounding
22
PE
Protective earth, grounding
Wire Lengths and Shielding The following maximum lengths for wires and the type of shielding to be used must be observed: Connection
Max. wire length
Shielding
BCL 40 - MA 10 RS 232 / RS 485
10m absolutely required, shield meshing
BCL 40 - Host
RS 232 / RS 485
10m absolutely required, shield meshing
MA 10 - Host
RS 485
1200m absolutely required, flexible leads as twisted pairs
MA 10 - Host
RS 422
1200m absolutely required, flexible leads as twisted pairs
MA 10 - Host
RS 232
10m absolutely required, flexible leads as twisted pairs
MA 10 - Host
TTY
1000m not required loop resistance < 100
Switching inputs
10m not necessary
Switching outputs
10m not necessary
Table 6.2:
6.4
Interface
Wire Lengths and Shielding
Disassembling, Packing, Disposing Repacking For later re-use, the device is to be packed so that it is protected against shocks and dampness. Optimal protection is achieved when using the original packaging. Notice! Electrical scrap is a special waste product!Observe the locally applicable regulations regarding disposal of the product.
50
BCL 40