Page 51
Planning the Physical Layout
Reader 150 Ft <+ - - Maximum . ) £ ) £ } f _) Satellite Wand Stations a) Daisy Chain Configuration 10. Ft Maximum 500 Ft <| - _ - Maximum Reader Trunk Line Length Dro ro Dro Dro Box Ox Box Box 50 Ft Maximum
| Oo
Satellite Wand Stations b) Drop Line Configuration
Figure 3-3 Satellite Wand Station
© 1987 INTERMEC Corporation Page 3-7
Page 52
DESIGNING A 9154 SYSTEM
Laying Muiti-Drop Cabling The two methods of installing the Multi-Drop cabling are:
1. Install the main trunk cable section-by-section. Lay a section of main trunk cable to the first device location. Add a drop cable, then add another piece of trunk cable to reach the next drop site, and so on.
2. Install the entire length of main trunk cable. Splice in drop cables at the appropriate locations, as required.
The choice of installation method is a matter of personal preference, but the second method, laying the entire length of main trunk cable, can be the quickest and easiest for new construction.
The Multi-Drop wiring is very flexible. You can add new sections of main trunk cable to the middle of an existing main trunk cable or to the end, provided the entire length does not exceed 2000 feet. The same flexibility applies to drop cables. You can cut the trunk cable anywhere and insert a new drop cable, provided that it is at least two feet to the nearest drop site.
Test System
If you are unfamiliar with Multi-Drop cabling, or CrossBar systems in general, consider setting up a test system before building an entire layout. The test system would familiarize you with the data communication interfaces and the wiring requirements of the Multi-Drop line. INTERMEC cables are available to aid in building a Multi-Drop test system.
Page 3-8 © 1987 INTERMEC Corporation
Page 53
Planning the Physical Layout
To build a test system, you will need the following:
* One reader a with bar code scanner compatible with the controller * Supervisory CRT
+ 9154 Controller
. Host Computer or a second CRT
Note: Using a CRT instead of a host computer allows you to test the host communication interface without having a host computer application program.
The following cabling is required:
. A short null modem cable to connect the controller to the host computer or CRT, INTERMEC Part No. 043206 (Male/Female) or 043207 (Male/Male)
° Main Trunk Test Cable, INTERMEC Part No. 047661 ’ Drop Cable, INTERMEC Part No. 047653 * Supervisory CRT cable, INTERMEC Part No. 041789
Construct the test system following the instructions in Section 4. If the small test system operates correctly with one reader, then set up a much larger system using the same data communication and hardware interface.
© 1987 INTERMEC Corporation Page 3-9
Page 54
DESIGNING A 9154 SYSTEM
SELECTING A COMMUNICATION INTERFACE BETWEEN THE HOST AND 9154
One of the important decisions you make in designing a controller-based CrossBar system is the choice of hardware communication interface between the host computer and the controller. This section provides guidelines for selecting an appropriate interface.
Available Interfaces A variety of communication interfaces can be connected to the host computer connector on the rear of the controller. The communication interfaces are:
° RS-232
* RS-422/485 ° Current Loop * Modem
The major factors effecting the choice of communication interfaces are:
¢ Distance between the controller and the host computer
. Amount of electrical interference in the work environment Whether the cable is shielded
. Communication baud rate
Section 4 explains how to install the various host to controller interfaces and gives recommendations for choosing an appropriate interface based on the distance between the controller and the host computer. Descriptions of each interface follow.
RS-232: RS-232 is designed for short distances and is generally not used for long data lines. Because RS-232 connects the two signal grounds of the units together, any ground noise is coupled directly to the units. When using long RS- 232 cables, noise problems can result, causing data transmission problems. However, RS-232 can be used successfully over longer distances if there is a “clean” electrical environment in the building.
Page 3-10 © 1987 INTERMEC Corporation
Page 55
Selecting a Communication Interface
RS-232 cable length is baud rate dependent. Table 3-1 shows the relationship between cable length and different baud rates.
Table 3-1 Allowable RS-232 Distances for Baud Rates
Baud Rate: Distances (feet): 19200 250
9600 500
4800 1000
2400 2000
Shorter distance than those in Table 3-1 will be required with high capacitance cables. Use modems for RS-232 operation at distances greater than those listed in Table 3-1.
RS-422/485: RS-422/485 standard cable length is 4000 feet with a maximum allowable signal loss of 6 dB. The line speed can be up to 19200 baud at the distance of 4000 feet.
Current Loop: An optically isolated 20 mA Current Loop interface to the host computer will work at distances of 100 to 500 feet at 9600 baud. The standard for current loop is 500 feet. When connecting equipment, give consideration to the interconnecting cable characteristics, cable termination resistance, and grounding requirements. Current loop requires that an external adapter be attached to the RS-232 interface.
Modems: installed at the cable ends for long-distance transmission, modems isolate the equipment grounds from the cable. The modem standard is RS-232. The cable should be terminated according to the modem manufacturer's instructions. The modem should have transformer coupling or optical isolation.
Communication between modems depends on the equipment chosen, but it is typically based on tones which are transformer isolated. Telephone company modems and leased lines can provide reliable communication over hundreds of miles.
© 1987 INTERMEC Corporation Page 3-11
Page 56
DESIGNING A 9154 SYSTEM
Comparing RS-232 and RS-422/485
RS-232 and RS-422/485 are two standard methods of data transmission which use totally different methods to signal mark and space states. A discussion and comparison of the two standards follows.
RS-232: RS-232 relies on measuring voltage relative to ground. Various voltage levels, representing mark and space states with respect to ground, are used to communicate data. For example, -5 Volts could be mark and +5 Volts space.
With RS-232, or any other signal which uses voltage-relative-to-ground communication, differences in ground potential between the transmitting and receiving stations becomes important. For example, if the transmitting station applies +5 volts to a line relative to a “ground” that is 10 volts “higher” than the ground at the transmitting station, the voltage on that line will appear to be -5 volts. The receiving station will interpret that as a mark.
The most common cause of ground potential differences is imbalances in the power distribution systems supplying the transmitting and receiving stations. The best way to avoid ground potential problems caused by power distribution imbalances is to power both the transmitting and receiving equipment from the same power distribution system. The following table lists the different power sources and their relative ability to minimize ground imbalances between transmitting and receiving stations.
Quality: Using the Same:
Ideal Outlet box
Almost Ideal Circuit breaker panel
Quite Good Step-down transformer/voltage distribution panel Fair Building distribution system
Risky Any other arrangement
While imbalances in the power distribution system is the most common cause of ground potential differences, the use of voltage interfaces between different buildings creates special problems during lightning storms; entire buildings will assume varying potentials, even if no direct lightning strikes occur to those buildings.
Page 3-12 © 1987 INTERMEC Corporation
Page 57
Selecting a Communication Interface
The problem of ground imbalances can also be partially alleviated by running a Signal Ground lead between the transmitting and receiving stations to provide a common ground reference. However, a common ground is not entirely adequate because if current flows through the Signal Ground wire, the resistance of the wire will permit a voltage difference between the two ends of the wire. Thus, one end of the signal ground will be at a higher voltage than the other end, just as if there was a problem with the power distribution system.
Current can be induced to flow through the Signal Ground wire by interference. Heavy machinery, welders, and switching equipment all can induce a current flow through the Signal Ground wire.
The need to eliminate interference to the ground signal is one of the reasons that shielding of RS-232 cabling is strongly recommended.
RS-422/485: A method of data transmission that is more satisfactory than the RS-232 voltage-relative-to-ground method is differential transmission used in an RS-422/485 interface. In this type of transmission, two conductors are used for each data path, and the information to be conveyed is expressed as the difference in voltage between the two conductors.
The ground potential difference is not important as long as it is not so high that it caused electric breakdown in the receiver circuitry. The receiver only needs to determine whether the relative voltage between conductor A and conductor B is positive or negative, which indicates whether the signal was in spacing or marking state.
Interfering signals are generally voltages relative to ground and will affect both conductors equally. Assume that noise voltage Vn is applied to two conductors, one carrying a +V and the other carrying a voltage -V. The resulting voltage will be +V +Vn and -V +Vn. However, the receiver will measure the difference between the two voltages, which is 2V, just as it was before the addition of noise. Noise of this kind is called “common mode” noise, and the differential capability of the receiver produce what is called “common mode rejection.” EIA Standard RS-422/485 is an excellent example of a differential transmission system.
© 1987 INTERMEC Corporation Page 3-13
Page 58
DESIGNING A 9154 SYSTEM
Data Line Considerations A data line is defined as a cable that connects units in order to transfer binary data. A long data cable has one or more of the following characteristics:
« Longer than 50 feet
. Interconnects equipment in two separate buildings
. Runs near large electrical equipment, such as large motors, welders, motor controllers, switch gear, etc.
To increase communication effectiveness and immunity to noise, you may use the following cabling procedures.
Cables that are run longer than 50 feet must be shielded. The use of shielded cables is also recommended in noisy environments, even if you use RS-422/485 or 20 mA Current Loop.
Shielded cable has a higher capacitance per foot than unshielded cable; therefore, when it is used with 20 mA current loop, you may have to lower the baud rate.
Using twisted pair cable can improve noise immunity and reduce crosstalk in a data cable.
GROUNDING CONSIDERATIONS
Proper grounding is required for safety, equipment protection, and low noise. The building(s) containing the controller system must be grounded directly to a nearby ground grid which includes the building steelwork and all circuits and junction boxes. Adequate building grounding will limit the voltage generated by fault currents, such as those caused by lightning or equipment failure. All equipment racks must be connected to the building ground.
The power and communication grounds are connected at the controller. It is important that the controller, through its grounding stud, has a good ground since this is the central ground for the controller system.
Page 3-14 © 1987 INTERMEC Corporation
Page 59
Grounding Considerations
Communication Interfaces and Grounding
The methods used to provide signal ground, and the negative effect of poor grounding, vary from one type of communication interface to the another. Specific grounding requirements for each type of interface follow.
RS-232: RS-232 is designed for short distances and is generally not used for long data lines. However, RS-232 can be used successfully over hundreds of feet if there is a “clean” electrical environment in the building and good grounding. Because RS-232 connects the two signal grounds of the units together, any ground noise is coupled directly into the units. If RS-232 is used, determine that there is a good earth ground, and that the controller system is properly connected to it.
RS-422/485: RS-422/485 uses a balanced transmission that is received with a differential receiver and a receiver signal ground that is not common with the cable. RS-422/485 is resistant to ground noise. RS-422/485 does not have voltage isolation like optically isolated current loop; however, RS-422/485 can be used at higher baud rates and over longer distances than current loop because of the inherent limitations of current based signals.
Current Loop: A 20 mA Current Loop with optical isolation at each end will isolate the grounds of each unit from the cable. If the equipment is set up in a star configuration, the central unit should be active for both transmit and receive loops.
Modems: Modems, which go at the end of the cable for long-distance transmission, isolate the equipment grounds from the cable. The cable should be terminated according to the modem manufacturer's instructions. The modem should have good isolation, such as transformer coupling or optical isolation.
Grounding Conductor
The protector ground conductor should have 30-mil rubber insulation, be covered by a fibrous material, and be no smaller than 14 AWG (gauge) copper or equivalent. The ground cables must be low impedance and bonded (see National Electrical Code and local building codes).
© 1987 INTERMEC Corporation Page 3-15
Page 60
DESIGNING A 9154 SYSTEM
Making a Good Ground Connection
Run the grounding conductor in as straight a line as possible to the grounding electrode. Isolating the grounds between equipment reduces noise and can prevent damage from voltage transients.
Choosing a Grounding Electrode: The grounding conductor should be connected to the best available grounding electrode as follows (in order from best to worst): WARNING
The grounding conductor should not be attached to steam or hot water pipes, lightning-rod conductors, or pipe or rod service electrodes that are not part of a multiground neutral power circuit.
*, To the nearest accessible location on the building or structure grounding electrode system
* To power-service conduit, service-equipment enclosure, or grounding electrode conductor, where the grounded conductor of the power service is connected to the grounding electrode system
*, To the grounding electrode, grounding electrode conductor, service conduit, or service equipment enclosure of the power service, if these are part of a multiground neutral power system
* To an effectively grounded metal structure
* To a continuous and extensive underground gas piping system
. To a ground rod pipe placed in permanently damp earth
Connection to a Pipe Electrode: The grounding electrode should be attached to a pipe electrode with a bolted clamp. Where a gas pipe electrode is used, make the connection between the gas meter and the street main. In either case, make the connection to the grounding electrode as close to the earth as possible.
Page 3-16 © 1987 INTERMEC Corporation