For the Industrial Devices H3951
Page 31
5. | DPn
- INPUT/OUTPUT Location and Description’ .
Parameter: Display Mode Range: 1 or 2 Description: Defines the Run Mode Display n=1 RUN MODE DISPLAY 1 OUT 1 User Cylinder OUT2 programmable Position OUT 3 Outputs a Relay 1 Rela’ y _ lr Relay2 Outputs +000.000 000 00 4161414 «117111 User _IN1 J| [t REOT Programmable IN2 EEOT Limit Inputs Inputs HOME si System $l2 PRG3 Program Inputs sl4 PRG1 Inputs
LCD Display: Functional Description
Cylinder Position: Real-time position feedback report indicating cylinder position in inches. The displayed position range is +/- 000.000 to 999.999 inches (+ 000-999.999 centimeters when Metric Units (MU) entered). When the internal position counter is reset, the LCD position display sets itself to zero. This condition occurs upon power up, after a system reset, or completion of a successful homing routine.
INPUTS : LCD displays Input ON/OFF Status (0 or 1)
“0 = Input ACTIVATED (grounded low)
1 = Input OFF (open circuit high)
OUTPUTS: LCD displays Output ON/OFF Status (1 or 0) 1 = Output ON (Sinking to Ground)
0 = Output OFF (Open Circuit)
LCD displays Relay Output ON/OFF Status (1 or 0)
1 = Relay ENERGIZED (Contacts Active) 0 = Relay DE-ENERGIZED (Contacts in Normal State)
Input _ Connector Pin# Description INi J3 13 User Programmable Input #1 IN2 J3 12 User Programmable Input #2 si J1 44,43 System Definable Input #1 sl2 J1 42,41 System Definable Input #2 SI3 Ji 40,39 System Definable Input #3 Sl4 J1 38,37 System Definable Input #4 PRG1 J3 16 Program Select Input #1 (LSB): PRG2 J3 15 Program Select Input #2 PRG3 J3 14 Program select Input #3 (MSB) HOME J3 19 Home Limit input EEOT J3 18 Extend End of Travel Limit Input REOT J3 17 Retract End of Travel Limit Input Qutput Connector Pin# Description OUTi J3 11 User Programmable Output #1 OUT2 J3 10 User Programmable Output #2 OUT3 J3 09 User Programmable Output #3 Relay i J1 33 COM1 Common Terminal 32 NCi Normally Closed Terminal 31 NO1 Normally Open Terminal Relay 2 Jt 36 COM2 Common Terminal
35 NC2 Normally Closed Terminal 34 NO2 Normally Open Terminal n=2 RUN MODE DISPLAY 2
Program Number
Cylind yer Program Status
Position a +005.000 PRG15R CUR+10 TD0000.00
Current, - ] L_____ Time Delay
LCD Display: Functional Description
Cylinder Position: Real-time position feedback report indicating cylinder position in inches. The displayed position range is +/- 000.000 to 999.999 inches (+0-999.999 centimeters when Metric Units (MU) entered.) When the internal position counter is reset, the LCD position display sets itself to zero. This condition occurs upon power up, after a system reset, or completion of a successful homing routine.
Current: Specified percentage of peak current output to the motor (0 to 99%). (See CE & CR commands in System Parameters & CL command in Edit Mode List)
Program Number: Indicates the number of the program currently running or, if no program is running, the last program run.
Program Status: Flags indicate the status of the program running or, if none are running, the last program executed. Status Flags
R = Program RUNNING
E = Program ENDED, completed successfully
S = Program STOPPED by ESC key or System
Input activation(configured as Stop) F = Program terminated by a FAULT condition none = No program is running
Time Delay: Indicates real-time Time Delay Count. The display counts down time in seconds when the timer (TD or CT Commands) is active in a program.
’ System Parameter Display
Ex. Display Mode DP:1 (1 or 2)
Default 1
Control set for RUN MODE DISPLAY 1
Parameter: Echo Command
Range: 0 or 1
Description: Turns the RS232 Echo on or off where 0 is echo off and‘ is echo on. An echo is where the Hx951 retransmits the character it receives back to the host device (or the next device on a Daisy Chain link).
Note: ECHO ON is required for RS232 Daisy Chaining (Multiple controls along the RS232 Link)
System Parameter Display
Ex. Echo RS232 EC:1 1=0n/0=off
Default 1
RS232 Echo Set On ; Note: Hx951 denotes an H3951 or H4951 Control
29
Ae
Page 32
Cnapter +s ] vystein FAIGINISUGIS Wurm meee, ~~ ~-
7.
Parameter: Home Algorithm
Range: 0 or 1
Description: Defines the type of home limit switch to be used and which edge of the home switch to reference during the final go home move.
HA(mn) m=0 Retract Edge n=0 Normally Closed Switch m=1 ExtendEdge n=1 Normally Open Switch
Note: Homing profiles are determined by the Home Algorithm command in System Parameters, the edit mode Go Home command, and the final approach towards the home switch. :
System Parameter Display
Ex. Home Algorithm ©
HA(mn):01 Default 01
Home input activated by the retract edge of a Normally Open home switch.
Parameter: Home Offset
Range: 0 to 999.999 inches (0-999.999 centimeters with Metric Units)
Description: When the home reference position is established following a successful homing routine, this command sets the zero position counter to an offset value from the home reference position where "+" is the extend direction ahead of home and "-" is the retract direction behind home.
System Parameter Display
Ex. Home Offset
HO+001 .000
Default 000.000
When the unit finds the home reference position, the control sets the position counter to 1.0 inch. The Absolute Zero position is now located 1 inch behind the mechanical home. All absolute moves will be referenced from this position.
8 Z Ie | } Extension > Retraction < *An internal magnet moving proportionally with the thrust tube activates the limit switches. Home Home Switch} Homing RTR Switch = Ege, Reference-|Approach Edge Achact GH Retract Edge| Retract into Velocity Direction Home Switch | (%) | Go Home Velocity = GH+/-nn Final Home Low Speed Home Position = 1% speed Home Home Switch] Homing edoe Switch _, Reference - | Approach GH Extend Edge Retract Edge antens Velocity] into rection (%) |Home Switch Go Home Velocity - = GH+/-nn Final Home Low Speed Home Position = 1% speed Home EXT Home Switch] Homing RTR Switch Edge, Reference - |Approach Edge § +cat GH Extend Edge} Reiract into Velocity Direction Home Switch | (%) | Go Home Velocity = GH+/-nn Final Home Low Speed Home Position = 1% speed : ATR Home Home Switch} Homing Edge Switch, Reference - ] Approach GH Extend Extend Edge Extend Velocity into Direction (%) |Home Switch fey Go Home Velocity ~ - = GH+/-nn Final Home Low Speed Home Position = 1% speed
Normally Closed Home Switch
* Homing Profiles are the same for a Normally Open or
DAR AUADES
A se Garage ayy ox (| Linear Servo Gonire:s
Page 33
ce .
9. |.
Parameter: Jog Acceleration
Range: .05 sec to 15 sec
Description: Defines the time it takes the cylinder to ramp up from zero speed to the specified Jog Velocity(JVnn) when a Jog Input or Jog Key is activated.
Note: The time entered also specifies the deceleration time for the unit to go from the Jog Velocity to zero speed after a Jog Input or Jog Key is released.
System Parameter Display
Ex. Jog Accel time
JA:00.10 Default .1
Jog Acceleration & Deceleration Ramp Times are .1 second each.
Parameter: Jog Velocity
Range:1 to 99
Description: Defines the jog mode velocity used when. maintaining the Keyboard Jog Keys or Jog Inputs during Run Mode Operation. Where nn is 1 to 99% of the actuators Available Linear Speed.
Keyboard Jog Keys: ESC & Right Arrow Jog Extend
ESC &Left Arrow Jog Retract
Jog Inputs:.System inputs (SI Command) Configuration 1 Jog Extend Configuration 2 Jog Retract
Note: For fine positioning of the actuator, momentary activation of the Keyboard Jog Keys or Jog Inputs will move the actuator in .001 inch increments.
System Parameter Display
Ex. Jog Velocity
JV:30 Default 10
Jog Velocity set for 30% Speed
Parameter: Metric Units
Range: 0 or 1 Description: Defines the units of scale for position and velocity in terms of English or Metric units.
n=0 _ English Units, where distance is measured in "in" (inches) and velocity “in/s" (inches per second)
EX. DAi Absolute Distance of 1 inch n=1 Metric Units, where distance is measured in "cm" _ (centimeters) and velocity "cm/s" (centimeters per second)
EX. DA1 Absolute Distance of 1 centimeter
Note 1: Repeatability English Units +:.001 in
Repeatability Metric Units:+.003 cm
Note 2: Distance values already stored programs are not converted from English to Metric Units (or viceversa) when changing between units.
Note 3: Edit Mode Commands affected by MU: DA (Distance Absolute), Di (Distance Incremental), DC (Distance to a Change)
Note 4: System Parameter Commands affected by MU: MN (Model Number), DP (Display Mode), HO (Home Offset)
System Parameter Display
EX. Metric Units MU:0 1=0n/0=off
Default 0
Metric Units are Disabled, Using English Units
Parameter: Power-Up Mode
Range: 0 to 99
Description: This command will cause a single program to be executed on power up or system reset.
Note 1: For nn=00, no program will be executed on Power Up.
Note 2: If the scanning of the program select lines is also active (System Parameter Command XP:1), the unit will first execute the program designated by PU:nn on power up or after a system reset, and then will initiate the scanning operation of the program select lines.
System Parameter Display
EX. Power Up Mode
PU:13 Default 00
Program 13 is executed on Power Up
Page 34
Chapter 5 System rarameters Gunman srw www
Parameter: Stop Decel Time (100% Speed Decel Time)
Yange: .05 to 15 sec vescription: The time entered determines the DECELERATION RATE for your specific cylinder given any speed when the Stop on Input (STn command) is activated or when a Stop (S) command is issued via RS232.
1. Specifically, the time entered will represent the time your cylinder takes to ramp down from a maximum reference velocity of 100% to 0% speed.
2. The constant DECELERATION RATE can be determined from this knowing the change in velecity (1 00%) over the change in time(SD time entered).
3. Knowing the constant Deceleration rate, you can now determine the actual TIME TO STOP for any given linear speed when the stop on input is activated.
System Parameter Display
Ex. STn Decel time $D:01.00
Default 1.0
Time entered is 1 second
Example: Using a Model NH105 Cylinder and a Default SD time of 1 second.
14. Determine the Stop Decel Rate for the NH105 Cylinder 2. Calculate the "Time to Stop” for various Linear Velocities in which a Stop on Input may be used.
NOTE : For an NH105 cylinder the Available Linear Speed VE100% = 12 in/ sec.
1. DECEL = v(in/sec) = Available Linear Speed = 12in/sec = 12in/sec’2
2. The Time to Stop once the STn input is activated is a function of the SD time and the Linear Move Velocity of the cylinder at the time the STn input is activated.
Time to Stop = SD time (100% speed decel time)
Move Velocity 100% Velocity Time to Stop =SD Time * Move Velocity = (SDnn.nn)* (VEnn) 100% Velocity VE100% Veloci VE100% Time to Stop = (1 sec) * (100%) = 1sec *1=1.00sec 100% °
VE75% Time to Stop = (1 sec) * (75%) = 1sec * 75 = .75 sec 10
%o
VE50% Time to Stop = (1 sec) * (50%) = 1sec * 50 = .50 sec 100% co}
VE25% Time to Stop = (1 sec) * (25%) = 1sec * 25 = .25 sec 100%
Different Move Velocities Stop on Input 400% (12 in/sec) Activated 75% (9 in/sec) Decel Rat Velocity 50% (6 in/sec) 12 in/sec? 25% (3 in/sec) 0% (0 in/sec) L-, - - + _- - - 25 Seconds |_.50 75 1.00 Time to Stop
RATE t (sec) SD time sec Stop on Input l Stop on Input Available Linear Speed _ Stop on Input 75% Activated Activated ; 12 in/sec _ / Activated ° 100% ™ Decel Rate Velocity 50% Velocity | Né =AV = 12 in/sec’ (%) p50, (%) A+ 0% 0% | Time ° . SD Time (seconds) 5 sec 75 sec |_1 Second The Move Profile displays the Deceleration Ramps for the example NH105 cylinder if a Stop on Input is activated during move execution at the speeds of 50 or 75%.
Page 35
Parameter: System Inputs
Range: 0-8
Description: Defines the System Definable Inputs to be configured as follows, where:
m = System Input 1 (S!1) x = System Input 3 (S13)
n = System Input 2 (SI2) y = System Input 4 (Si4)
m orn defined as
0 Not Used
1 Jog + Extend (Same as ESC & Right Arrow Key) 2-Jog - Retract (Game as ESC & Left Arrow Key) 3 Kill Motion :
4 Disable Keyboard
5 Warm boot - System reset
6 Additional Program Select Inputs (PRG): Binary Format 7 Additional Program Select Inputs (PRG): BCD Format 8 Additional User Programmable Inputs (IN)
9 Interrupt
Note: Configuration 6 & 7 cannot be used simultaneously, it will result in undefined program selection.
System Parameter Display
Ex. System Inputs
Si(mnxy):6635 Default 8800
System Input 1 is used as an Additional Program Select Line (PRG4): Binary Format
System Input 2 is used as an Additional Program Select Line (PRGS5): Binary Format
System Input 3 is used to Kill Motion
_ System Input 4 is used to issue a System Reset
Reference: See Hardware Reference for Wiring and Specifications regarding System Inputs (SI1-SI4), High Level Inputs.
Note: Hx951 denotes an H3951 or H4951 Control.
Jog + Extend: When activaied the cylinder will Jog in the extend direction at a velocity determined by the JV System Parameters Command. When the input is released, motion stop. (Same as Run Mode: ESC & Right Arrow Key)
Jog - Retract: When activated the cylinder will Jog in the retract direction at a velocity determined by the JV System Parameters Command. When the input is released, motion stops. (Same as Run Mode: ESC & Left Arrow Key)
Kiil Motion: When activated, any program execution or ° functional operation is immediately stopped. This includes any motion, time delays, loops, faults, and scanning of the Program Select/User Programmable Inputs.
Disable Keypad: When activated, keypad is disabled allowing NO user access. Keypad resumes normai operation when input released.
Warm Boot - System Reset: When activated, resets the Hx951 software, clearing the RAM Buffer, and resetting the control to its power up state. (Programs & Parameters are NOT ERASED). This is typically used to restart system when a fault condition occurs.
Additional Program Select Inputs (PRG): Binary Format One to four additional program select lines may be added to ailow user to select more programs
System Input 1 = PRG4 Input
System Input 2 = PRGS5 Input
System Input 3 = PRG6 Input
System Input 4 = PRG7 Input
See Binary Decoding table on next page and System Parameters XP:n Command.
Additional Program Select Inputs (PRG): BCD Format One to four additional program select lines may be added to allow user to select more programs
System Input 1 = PRG4 Input
System Input 2 = PRG5d Input
System Input 3 = PRG6 Input
System Input 4 = PRG7 Input
See BCD (Binary to Decimal) decoding table on next page and System Parameters XP:n Command.
Additional User Programmable Inputs (IN)
One to two additional user programmable inputs may be added io allow user more 1/O Logic interaction within a program. "IN" inputs are used with the Edit Mode Commands WT (Wait On Input), IF (If-Then), GOn (Go on Input), & ST (Stop on Input). The first additional input defined is IN3 and the second is IN4.
Interrupt -
When activated, any executing program or functional operation is terminated and PROGRAM 98 (interrupt _ program) is immediately executed. After Program 98 is complete, the unit resumes scanning of the program select lines.
Note 1: Ifa move is executing when the interrupt is activated, the move is terminated (decelled at a rate determined by the SD command in System Parameters).
Note 2: if no commands are listed in program 98, the unit will go to Run mode and immediately begin scanning program select lines. The XP Command must be active for the Program Select Lines to be scanned.
33
Page 36
wrenenpoews Sy wee rt - .
eg ae a CALAN Addition Program Select Lines: Binary Format System Inputs (S!1-SI4) Configuration # of programs allowed The System Parameter XP:n Command must be enabled to SI RK ‘5 initialize the program select lines in order for the system inputs S166 XX 31 to be used as additional program select lines. XP=External SI666X 63 Program Select SI6666 99 Binary Decoding Table: X = Any other System Input Configuration MSB LSB MSB LSB Program #1 Si4 ]_Si3 [ Sl2 | Sit IPRG3 | PRG2| PRG1 Program #}_ Si4 J Si3 | Si2 | Si |PRG3{ PRG2| PRG1 0 1 1 1 1 1 1 1 51 1 ) 0 1 1 0 0 1 1 1 1 1 1 1 0 52 1 0 0 1 0 1 1 2 1 1 1 4 1 0 1 - 58 1 0 0 1 0 1 0 3 1 1 1 1 1 0 0 54 1 0 0 1 0 0 1 4 1 1 1 1 0 1 1 55 1 0 0 1 0 0 0 5 1 1 1 1 0 1 -0 56 1 0 0 0 0 1 1 6 1 1 1 1 0 0 1 57 1 0 0 0 1 1 0 7 1 1 1 1 0 0 0 58 1 0 0 ) 1 0 1 8 1 1 1 0 7 i i] 59 1 0 0 ) 1 -{ 0. 0 9 1 1 1 0 1 1 0 60 1 i) fy Oo | 0 1 1 10 1 1 1 0 1 0 1 61 1 0 i) 0 0 1 0 11 1 1 1 0 1 0 0 62 1 0 0 0 0 0 1 12 1 1 1 0 0 1 1 63 1 0 0 ) 0 0 0 13 1 1 1 0 0 1 0 64 0 1 1 1 1 1 1 14 4 1 1 0 0 ) 1 65 ) 1 1 1 1 1 0 15 1 1 1 0 0 0 0 66 0 1 1 1 1 0 1 16 1 1 0 1 1 1 1 67 0 1 1 1 1 0 0 17 1 1 0 1 1 1 0 68 0 1 1 1 0 1 1 18 1 1 0 1 1 0 1 69 0 1 1 1 0 1 0 19 1 1 0 1 1 0 0 70 0 1 1 1 0 0 1 20 1 1 0 1 0 1 1 71 0 1 1 1 0 0 () - 21 1 1 0 1 0 1 0 72 0 4 1 0 1 1 1 @® 22 1 1 0 1 0 0 1 73 0 1 1 0 1 1 0 23 1 1 0 1 0 0 0 74 0 1 1 0 1 0 1 24 1 1 0 ) 1 1 1 75 0 1} 1 0 1 0 0 25 1 1 0 0 1 1 0 76 0 1 1 ft) 0 1 1 26 1 1 0 0 1 0 1 77 0 1 1 0 0 1 0 27 1 1 0 0 1 0 0 78 0 1 1 0 0 0 1 28 1 1 0 0 0 1 1 79 0 1 1 0 0 0 0 29 1 1 0 0 0 1 0 80 0 1 0 1 1 1 1 30 1 1 0 0 0 0 1 81 0 1 0 1 1 1 0 31 1 1 0 0 0 0 0 82 0 1 0 1 1 0 1 32 1 0 1 1 1 1 1 83 0 1 0 1 1 0 1 33 1 0 1 1 1 1 0 84 0 1 0 1 0 1 1 34 1 0 1 1 1 0 1 85 0 1 0 1 0 1 0 35 1 0 1 1 1 0 0 86 0 1 ) 1 0 0 1 36 1 0 1 1 0 1 1 87 0 1 0 1 0 0 0 37 1 0 1 1 0 1 0 88 0 1 0 0 1 1 1 38 1 0 1 1 0 0 1 89 0 1 0 0 1 1 0 39 1 0 1 1 0 0 0 90 0 1 0 0 1 0 i 40 1 0 1 0 1 1 1 91 0 1 ‘0 0 1 0 0 41 1 0 1 0 1 1 0 92 0 1 0 0 0 1 1 42 1 0 1 0 1 0 1 93 0 1 ) 0 0 1 0 43 1 0 1 0 1 0 0 94 0 1 0 0 0 ) 1 44 1 0 1 0 0 1 1 95 0 1 0 0 0 0 ) 45 1 0 1 0 0 1 0 96 0 0 1 1 1 1 1 46 1 0 1 0 0 0 1 97 {| 0 0 1 1 1 1 0 47 1 0 1 0 0 0 0 98 0 | -0 1 1 1. 0 1 48 1 0 0 i 1 1 1 99 0 0 1 1 1 0 0 49 1 0 0 1 1 1 0 50 7 0 0 7 7 0 7 Note 1: For the configurations SIX666, SI6X66, SI66X6, SIG66X, SIG6XX, SIGX6X, SIGXX6, SIX66X, SIX6X6, SPn6 we SIGXXX, SIX6XX, SIXX6X, & SIXXX6 where X is any 0 1 = off (open circuit) 0 = on (grounded) configuration number, the missing Program Select Input in the above table defaults to a binary 1.
op a a, RO -> 34 H3951/H4951 Linear Servo Controls tad .
Page 37
The System Parameter XP:n Command must be enabied to initialize the program select lines in order for the system inputs ‘o be used as additional program select lines. XP=External
Program Select
BCD Decoding Table:
Addition Program Select Lines: BCD Format
Configuration # of programs allowed SIXXXX 7 SI7 XXX 9 SI77XX 19 SI777X 39 SI17777 79
X = Any other System Input Configuration
MSB LSB MSB LSB Program # | Sl4]_SI3 | Sl2 | Sli [PRG3 | PRG2{ PRG1 Program #] Si4{ SI3 |} Sl2| Sli |PRG3| PRG2|] PRG1 0 1 1 1 1 1 1 1 51 0 1 0 1 1 1 0 ~ 1 1 1 1 1 1 1 0 52 0 1 0 1 1 0 1. 2 1 1 1 1 1 0 1 53 0 1 0 1 1 0 0 3 1 1 1 1 1 0 0 54 0 1 0 1 0 1. 1 4 1 1 1 1 0 1 1 55 0 1 0 1 0. 1 0 5 1 1 1 1 0 1 0 56 | -0 1 0 1 0 0 1 6 1 1 1 1 0 0 1 57 0 1 0 1 0 0 0 7 1 1 1 1 0 0 0 58 0 1 0 0 1 1 1 8 1 1 1 0 1 1 1 59 0 1 0 0 1 1 Q. 9 |. 1 1 1 0 1 1 0 60 fF O 0 1 1 1 1 1 10 1 1 0 1 1 1 1 61 0 0 1 1° 1 1 ) 11 1 1 0 1 1 1 0 62 0 0 1 1 1 0 1 12 1 1 0 1 1 0 1 63 0 0 1 1 1 0 a) 13 1 1 0 1 1 0 0 64 ) 0 1 1 0 1 4 14 1 1 0 1 0 1 1 65 0 0 1 1 0 1 0 15 1 1 0 1 0 1 0 66 0 0 1 1 0 0 1 16 1 1 0 1 0 0 1 67 0 0 1 1 0 0 0 17 1 1 0 1 0 0 0 68 0 0 1 0 1 1 1 18 1 1 0 0 1 1 1 69 0 0 1 0 1 1 0 19 1 1 0 fe) 1 1 9) 70 ) 0 0 1 1 1 1 20 1 0 1 1 1 1 1 71 0 0 0 1 1 1 0 21 1 0 1 1 1 1 0 72 0 0) 0 1 1 0 1 22 1 0 1 1 1 9) 1 73 0 0 0 1 1 0 0 23 1 0 1 1 1 0 0 14 0 ) 0 1 0 1 1 24 1 0 1 1 0 1 1 15 9) 0 0 1 () 1 0 25 1 0 1 1 0 1 0 76 ) 0 0 1 0 0 1 26 1 0 1 1 0 0 1 77 ) 0 0 1 0 0 0 27 1 0 1 1 0 0 0 78 0 0 0 0 1 1 1 28 1 0 1 0 1 1 1 79 0 0 0 0 4 1 0 29 1 0 1 (¢) 1 1 0 30 1 0 0 1 1 1 1 31 1 0 0 1 1 i 0 32 1 0 0 1 1 9) 1 33 i 0 0 i i 0 0 Note 1: For the configurations SIX777, SI7X77, SI77X7, 34 1 0 0 1 0 1 1 S1777X, SI77XX, SI7X7X, SI7XX7, SIX77X, SIX7X7, SIXX77, 35 1 0 0 1 0 1 0 SI7XXX, SIX7XX, SIXX7X, & SIXXX7 where X is any other 36 1 0 0 1 0 0 1 configuration number, the missing Program Select Input in the 37 1 0 0 1 0 0 0 above table defaults to a binary 1. 38 1 Q 0 0 1 1 1 39 1 0 0 0 1 1 0 40 0 1 1 1 1 i 1 41 0 1 1 1 1 1 0 42 0 1 1 1 1 0 1 43 0 1 1 1 1 0 0 44 0 1 1 1 0 1 1 45 0 1 1 1 0 1 0 46 0 1 1 1 0 0 1 47 0 1 1 1 0 0 0 48 0 1 1 0 1 1 1 0 1 1 0 1 1 0 0 1 0 1 1 1 1
1 = off (open circuit) 0 = on (grounded)
35
»
Page 38
Parameter: System Outputs Parameter: Unit Number Range: 0-6 Range: 1 - 98 Description: Defines the function of the two System Definable Description: RS232 Device Address, used primarily for daisy-utputs; configured as follows where chain operation of multiple controls along the serial m = System Output 1 (SO7) communication link.
n = System Output 2 (SO2)
System Parameter Display morn 0 Not used ; Ex. Unit Number 1 Direction of Cylinder Motion UN:01 Default 01 Extending = Output Off (Open Collector High) Reference: Operating in RS232 Serial Communication
Retracting = Output On (Sinking to Ground)
Output remains set until the cylinder begins motion in the opposite direction.
Parameter: Execute Programs from External Program Select
2 Direction of Motion Lines Retracting = Output Off (Open Collector High) Range: 0 or 1 ‘Extending = Output On (Sinking to Ground) Description: Tells unit to scan the program selectinputs, __ ; PRG1, PRG2, and PRGS, and execute the program whose Output remains set until the cylinder begins motion in the binary number pattérn appears.
opposite direction. XP:1 Enables the scanning of the program select inputs at the
3 Brake Mode 1: . end of each program and executes the next program number Any Motion = Output On (Sinking to Ground) that appears. Power must be cycled or a system reset must be No cylinder Motion = Output Off (Open collector High) issued to begin scanning operation. 4 General Fault: Output set ON (Sinking to Ground) during XP:0 Disables the scanning operation, ignoring the program any fault condition. ; select inputs. Fault Conditions: "Amplifier Fault" PROGRAM MSB LSB "Current Overload” SELECT INPUTS _PRG3 PRG2 PRG1 "EEPROM Check Sum Error" 1 1 1 NO Program Executed "ENCODER Fault" 1 1 0 Execute Program 1 "ERROR finding Home" 1 0 1 Execute Program 2 "Hit A Limit” 0 =input grounded 1 0 0 Execute Program 3 "Motor Stalled” 1 = open circuit 0 1 1 Execute Program 4 "Motor Shutdown due to unstable gains" 0) 1 0 Execute Program 5 0 0 1 Execute Program 6 5 Amp Fault: Output set on (Sinking to Ground) during 0) 0 0 Execute Program 7 an amplifier fault. Note: While XP1 is enabled, the program inputs are continually
6 Stall Fault: Output set on (Sinking to Ground) during a stall scanned until one of the following occurs; fault. 1. The ESC key is pressed on the keypad. Note: For Fault outputs, the output will remain set until the power is cycled or a 2. An end of travel! limit is encountered. system reset is issued. 3.A System Input (S11 or S/4) is activated when set for 7 Current "Hold" Limit Active Configuration 3: Kill Motion. Output set ON (sinking to ground) when the Current "Hold" 4. An RS232 "kK" Kill Command is issued. Limit (set by Edit Mode CL Command) is tripped while being - - used with a programmed move. To start or resume scanning operation execute one of the Note: .Output remains latched until a new move is executed, power is cycled, or following; \ a system reset is issued. 1. Cycle the power p Disol 2. Perform a System Reset System Parameter Display via Run Mode Keypad press F1-F2-9, in that order via RS232 enter <a>ZZ, <a>=device address
Ex. System Outputs Default 00 via System Input (SI1-S!4) Activation when set for
SO(mn):13 efault Configuration 5: Warm Boot. System Output 1: set on when the actuator retracts and off System Parameter Display when the actuator extends. System Output 2: set on during any actuator motion and is off Ex. Ext Prog Select ‘when the cylinder is stopped. XP:0 1=On/0 =off Default 0 Reference: See Hardware Reference for Wiring and Scanning Operation Off ificati i 1 2), Low ; . Does Outputs regarding System Outputs(SO1 & SO2) Reference: Additonal Program Select Lines See System . Parameters: S] Command (System Inputs)
a 36 H3951/H4981 Linear Servo Controls
Page 39
WHANUG! UV PIC WWW ee Bbwiw write
H3951
Fuse 4 Display_|, 5 M1 Fuse 2 ity | f=) Dc |__| Intensity 2, Jt Power re) well fy va, “4 LoD Display va J2 q and Keypai o * AC/DC Motor/Power Select Interface Jumpers StICHA CHB cecal ee) 1 . 10 Dipswitches Encoder channel indicators AC Power 2 Motor J Pome oO Te a4 LED J] 20 \ LCD Display J2 and Keypad t4 - Fuse 3 t- - Fuse 2 Display__| S1|CHA CHB: Intensity” ]772--------, ; fefe) 1 |t - Fuse 1 v_ TL / [on | Jn Dipswitches Encoder channel _ indicators
1. LCD Display and Keypad 2. Dipswitches (1-8)
3. Jumpers (V1-V4)
4. LED Indicators
5. Fuses
Note 1: Top cover must be removed to expose the Jumpers and LED Indicators Note 2: Main cover must be removed to expose the Dipswitches
‘\ Keypad
Function: 20 multi-function keys which allow for program entry and manual operation of the Hx957 control.
_ LCD Display 32 character (16x2) Liquid Crystal Display which displays software entry via keypad or RS232 Serial Communication.
pepe Single turn potentiometer used to control the cer intensity of the LCD Display.
CW rotation decreases display intensity CCW rotation increases display intensity
Note: Hx951 denotes an H3951 or H4951 Control
Function: 8 Dipswitches allow user to enable or disable system control functions (Default: All dipswitches are off)
Dipswiiches Switch Function 1-5 Reserved 6 Keypad Access 7 Keypad Access 8 Keypad Access
Dipswitch Settings: Keypad Access
6 Function off | Normal Keypad Operation on | Disables Edit & Del Keys
7 8 Function off__ off Normal keypad operation on_ off Reserved off on |] Ali keys disabled except ESC on on keys are disabled
Note 1: When keypad is disabled, contro! operation is through external /O interface.
Note 2: RS232 program upload and download still functional during keypad disable.
Main Cover must be removed to expose the Dipswitches. Cover held in by four Allen screws(5/64)
Function: Allow user to individually select AC or DC voltage sourcing levels to activate each of the four high level logic inputs on connector J1. (Default: All inputs set for DC Voltage)
Jumper J1 Connector Designated Input AC/DC Input Pin v1 Sl1+ |Q] 44 System Input 1 123 Sii- 1@] 43 AC/DC v2 Si2+ ]@DI 42 System Input 2 123 sl2- |@| 41 AC/DC
V3 $i3+ |{@| 40 System Input 3 123 Si3z- |@| 39 AC/DC
V4 Si4+ |@] 38 | System Input 4 123. Sl4- 1QI 37
To Select AC Voltage [EXIS¥O] Jumper pins 1 & 2
To Select DC Voltage [GERRY Jumper pins 2&3 123
Note 1: The top cover must be removed to expose the AC/DC Select Jumpers Note 2: The H4951 control allows only DC voltages.
37
Page 40
wrap ewe wos ems
H3951 Fuse 1 Display_| vi 22\\ / Fuse 2 Intensity oa JA poe Oo (ot 44 LED J3 | 20 Te v3 LCD Display Va J2 i] and Keypad Oo AC/DC Motor/Power Select Interface Jumpers 31/CHA CHB fefe) 1 TT // 10 ~Dipswitches Encoder channel indicators AC Power 2 Motor oc Jt) Power 9. fT a| «LED. | 20 \ LCD Display J2 and Keypad . $- - _ Fuse 3 Display__| 3tICHA CHB #7 - Fuse 2 Intensity |” feXe) 1 |¢+ - Fuse 1 71 [on // on Dipswitches Encoder channel indicators
Function:
DC Power LED
CHA (encoder) CHB (encoder)
Note 1: Both encoder LED's will pulsate at low intensity levels during any cylinder
LED "ON" when the main logic board is being supplied DC power (12-16 VDC) on pins 21(PWR) and 22(GND), on connector J3.
LED “ON" when encoder channel A is active.
LED "ON" when encoder channel B is active.
motion, indicating both encoder channels are active. Note 2: At rest, the encoder LED's will cease pulsating, locking into a binary pattern indicating that the cylinder is stationary (no backdriving or drift).
The top cover must be removed to expose the LED Indicators.
H3951
Fuse 1
Fuse 2
H4951
Fuse 1
Fuse 2
Fuse 3
‘
Protects the internal 12vdc amplifier power supply prewired to the main logic board, pins 21({PWR) and 22(GND) on connector J3, from shorts or excessive current draw.
Rating: 1 amp, 250 voit, fast-blow type AGC 1
Protects the internal amplifier from surges or shorts on the Motor Output Terminals.
Rating: 5 amp, 250 volt non-time delay, type ABC 5
Protects the internal amplifier from surges or shorts on the Motor Output Terminals.
Rating: 8 amp, 250 volt non-time delay, type MDA 8
Protects the internal Low Level Logic Supply from shorts or excessive current draw. ; Rating: .25 amp, 250 volt, fast-blow type AGC 1/4
Protects the isolated internal 12vdc amplifier power supply prewired to the main logic board, pins 21 (PWR) and 22 (GND) on connector J3, from shorts or excessive current draw. ;
Rating: 1 amp, 250 volt, fast-blow type AGC 1
38