The text of a manual · part 6 of 16
LonPoint Module Hardware and Installation User's Guide, Version 2.0: CH4 - Installation and Wiring of Base Plates, pages 45 to 52
Pages 45 to 52 of 115, from LonPoint Module Hardware and Installation User's Guide, Version 2.0
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Echelon LPR-14
Page 45
1 2 3 4 5 6 7 8 9
Network
16-30VAC or VDC
Figure 4.8 Base Plate Power and Network Wiring Connections See chapters 5 through 9 for specific I/O wiring connections.
LonPoint Type 1D DIN Base Plate Installation Figure 4.9 presents a detailed view of the front side of the base plate. The circuit board inside the Type 1D DIN Base Plate includes an arrow with the designation "1A," designating it as a Type 1 Base Plate with a Revision A circuit board. The 1D Base Plate is intended to be installed either on a 35mm DIN rail, or using the integral keyhole slots, on a wall or panel. Two arrows indicates the vertical orientation of the Base Plate that will provide the best viewing of the front panel legends.
LonPoint Hardware Guide
4-9
Page 46
Terminal screw, tightening torque 4lbs. in. (0.5Nm) maximum
Wire entry
18
17
16
15
14
13
12
11
10
18
17
16
15
14
13
12
11
10
CAUTION
I/O
Keyhole slot for wall or panel mounting
1A
Threaded screw holes for attaching LonPoint modules to the Base Plate. Use 8-32, 3/8" screw, Echelon 205-0130-01 or equal
Network 1
1
DIN rail release activate with flathead
2
3
4
5
6
7
2
3
4
5
6
7
8
9
8
9
Jumper Plug storage location remove before installing LonPoint Module
Jumper Plug insertion points Figure 4.9 Front Side of Type 1D DIN Base Plate
4-10
Installation and Wiring of Base Plates
Page 47
The base plate contains two integral DIN rail tabs that securely grab a 35mm DIN rail onto which the base plate is mounted. The base plate may be used on both 35mm x 7.5mm and 35mm x 15mm DIN rails. To release the Base Plate from the DIN rail, sequentially insert a flathead screwdriver into the DIN rail release tabs and gently pull away from the DIN rail (figure 4.10). Four keyhole slots are provided for affixing the Type 1D DIN Base Plate to a wall or panel (figure 4.11). The 1D Base Plate is supplied with a jumper plug that connects the power and network connections between adjacent base plates. The Jumper Plug is shipped inserted into the main cavity of the Base Plate, and can be removed by gently pulling the plug handle in the direction of the mounting arrow. The Jumper Plug must be removed before a LonPoint module can be inserted into the Base Plate.
Figure 4.10 DIN Rail Base Plate Dimensions (Dimensions are in mm (inches).)
LonPoint Hardware Guide
4-11
Page 48
Figure 4.11 Mounting Holde Pattern Dimensions for Type1D Base Plates
Connecting Wiring Route all network, power, and input/output cabling to the pertinent screw terminals located at the top and bottom of the Base Plate. It is good practice to separate the input/output cabling as much as possible from the network and power cabling, especially if low-level analog signals are being supervised. Strip the cable jacket and wire conductors. The base plate screw terminals will accept 24AWG (0.5mm) to 12AWG(2.2mm) wire, which should be stripped to a length of 0.32" (8mm). Although not required, it may be useful to use a soldering iron to tin the stripped lengths of any strand wired to prevent fraying and inadvertent contact with adjacent terminals. Identifying screw terminal numbers are conveniently located both above and below each screw terminal. Symbols and/or language identifying the function of the screw terminals also are provided.
Note that terminals 1 and 9 are numbered from left to right, but terminals 10 to 18 are numbered from right to left. The optimum tightening torque for the screw terminals is approximately 4 pounds (0.5Nm). The ideal flathead screwdriver tip width is 3/32" (2.5mm).
4-12
Installation and Wiring of Base Plates
Page 49
Table 4.2 Type 1D Base Plate Terminal Block Connections Terminal Number
Function
1 -4
Network
5
Cable shield, if used
6-9
Power
10 - 18
I/O
Two sets of screws are provided for both the power and network wiring connections. These connections are internally jumpered on the Type 1D Base Plate PCB to provide continuity of the network and power wiring, even if no LonPoint module is installed, as shown in figure 4.12. This feature permits the base plate wiring to be pre-installed and the network and power circuits checked for continuitiy throughout the installation, before a single LonPoint module is ever installed. This feature also prevents network and power interruptions as a result of hot swapping LonPoint modules during commissioning or service operations. Finally, providing two sets of screw terminals permits incoming and outgoing wiritng to be landed at separate screw terminals without the need to insert more than one wire in any given screw terminal.
1 2 3 4 5 6 7 8 9
Network
16-30VAC or VDC
Figure 4.12 Base Plate Power and Network Wiring Connections
Connecting the Jumper Plug(s) From time to time it may be necessary to mount two or more LonPoint Type 1D or 2D Base Plates adjacent to one another. In these instances, power and network wiring must be daisy-chained between each Base Plate. Routing power and network wiring between multiple base plates can be a laborious and time consuming task, and there is always the risk of a wiring error. For this reason, the Type 1D and 2D Base Plates are each supplied with a Jumper Plug and Jumper Plug connecotrs which simply and easily bus the power and network between adjacent Base Plates. The Jumper Plug connectors are located on either side of the terminal block with connections 1 to 9 . The Jumper Plug connectors are wired in parallel with the network and power connections on the screw terminals. When two Base Plates are mounted adjacent to each other, with the mounting arrows pointing in the same direction, the Jumper Plug connectors will be aligned such that a Jumper Plug may be inserted into the two connectors, thus bridging power and network between the two Base Plates (figure 4.13).
LonPoint Hardware Guide
4-13
Page 50
18 1 1 1 1 1 1 1 1 7 6 5 4 3 2 1 0
18 1 1 1 1 1 1 1 1 7 6 5 4 3 2 1 0
1A
1A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
Jumper Plug (x-ray view) Figure 4.13 Mounting Two Base Plates with Jumper Plug Connectors When used with a Type 2D Base Plate, there are restrictions about the placement of the Type 2D Base Plates (and the routers they contain) relative to the adjacent Type 1D Base Plates. In all cases, any Type 2D Base Plates must be located to the left side of any Type 1D Base Plates (figure 4.14) with which they will share a common channel.
4-14
Installation and Wiring of Base Plates
Page 51
Type 2D
Type 1D
Type 1D
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
2
1A
1A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
Jumper Plugs (x-ray view) Figure 4.14 Mixing Type 1D and Type 2D Base Plates
The reason for this limitation is that only the right Jumper Plug connector on a Type 2D Base Plate bridges the network connection; the left Jumper Plug connector on a Type 2D Base Plate bridges only the power connection. This arrangement permits several routers, each with a different channel type, to be mounted on a common DIN rail and share a common power supply. Figure 4.15 shows mounting configurations that are problematic and must be avoided because the router will be unable to communicate with the other LonPoint modules via the Jumper Plug. If such a mounting arrangement must tbe used, then the base plates must be interconnected using wiring instead of the Jumper Plug.
LonPoint Hardware Guide
4-15
Page 52
Type 1D
Type 2D
Type 1D
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1A
2
1A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
Type 1D
Type 1D
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1 1 1 1 1 1 1 1 1 8 7 6 5 4 3 2 1 0
1A
1A
2
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
Jumper Plugs (x-ray view) Type 2D
Jumper Plugs (x-ray view)
Figure 4.15 Problematic Mounting Configurations when Using Routers
4-16
Installation and Wiring of Base Plates