The text of a manual · part 7 of 16
LonPoint Module Hardware and Installation User's Guide, Version 2.0: CH4 - Installation and Wiring of Base Plates, pages 53 to 60
Pages 53 to 60 of 115, from LonPoint Module Hardware and Installation User's Guide, Version 2.0
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Echelon LPR-14
Page 53
LonPoint Type 2 Base Plate Installation All LonPoint LPR Routers may be installed in either a Type 2 Base Plate (Model 40222) or a Type 2D DIN Base Plate (Model 48222). Figure 4.16 presents a detailed view of the front side of the Base Plate. The circuit board inside the Type 2 Base Plate includes a large number “2” in the lower right corner, as viewed from the front of the base plate, designating it as a Type 2 Base Plate. Test points are provided on the circuit board for measuring all of the wiring connections; symbols are silkscreened on the PCB to identify the functions of the test points.
LonPoint Hardware Guide
4-17
Page 54
Figure 4.16 LonPoint Type 2 Base Plate - Front Panel
4-18
Installation and Wiring of Base Plates
Page 55
Figure 4.17 shows a detailed view of the rear side of the Base Plate, the side to which wiring connections are made.
Figure 4.17 LonPoint Type 2 Base Plate - Rear Wiring Panel
LonPoint Hardware Guide
4-19
Page 56
As shown in figure 4.18, the Type 2 Base Plate is intended to be installed in an electrical box either vertically (base plate interior arrows pointing up) or rotated clockwise 90° (base plate interior arrows pointing to the right). These two orientations provide optimal viewing of the front panel legends of an installed LonPoint module, and also accommodate different methods of installing electrical boxes.
Figure 4.18 LonPoint Type 2 Base Plate Mounting Orientations
Installing A Compatible Electrical Box Compatible electrical boxes that will accept a Type 2 Base Plate include a 4” square by 2” deep electrical enclosure (Raco model No. 232, 236, 7232, 7054 or equal), two-
4-20
Installation and Wiring of Base Plates
Page 57
gang PVC switch box (Raco 7834 or equal), and Echelon’s Model 48001 EuroBox for wall and 35mm DIN rail applications. A 4” square electrical enclosures should be either affixed to a wall or to equipment using suitable mounting screws, or recessed using a suitable mounting clamp (figure 4.19). Due to variations in the location of knock-outs, care must be taken to ensure that 3/4” conduit fittings do not interfere with the Base Plate when it is installed in the electrical box; 1/2” conduit fittings have not been found to cause an interference problem.
Figure 4.19 4” Square Electrical Box Mounting There are four mounting options if Echelon’s EuroBox is used. The Eurobox requires the installer to drill cabling holes: ensure that suitable holes are drilled prior to mounting. In order to avoid interference with a Type 1 or Type 2 Base Plate, all glands and conduit fittings must be located within 1.4”/35cm of the bottom of the box (as measured from the outside of the box). Wire glands and conduit fittings must not extend more than 0.63”/16mm into the EuroBox in order to prevent associated cabling from interfering with the Base Plate screw terminals. For UK applications, a second mounting option is to affix the EuroBox to a single gang 25mm BS4662 flush mounting box (MK 866ZIC or similar). Two keyhole slots are provided in the EuroBox to accomodate the flush mounting box as shown in figure 4.20. Use screws with flush mounting and ensure that suitable cabling holes are drilled in the Eurobox prior to mounting, as discussed above.
Figure 4.20 MK Electrical Box Mounting the EuroBox
LonPoint Hardware Guide
4-21
Page 58
A third mounting option is to affix the EuroBox to a recessed 6.5cm diameter plastic DIN box (Kaiser or equal). Two keyhole slots are provided in the EuroBox to accommodate DIN box mounting, as shown in figure 4.21. Use the screws provided with the DIN box and ensure that suitable cabling holes are drilled in the EuroBox prior to mounting.
Figure 4.21 DIN Box Mounting the EuroBox A fourth mounting option is to affix the EuroBox to 35mm DIN rail using DIN Clips (one pair included). Two sets of rectangular slots are provided for the DIN clips. Ensure that the clips lock in place on the EuroBox and then snap them onto the DIN rail (figure 4.22). Ensure that suitable cabling holes are drilled in the EuroBox prior to mounting.
Figure 4.22 DIN Rail Mounting the EuroBox
The Type 2D DIN Base Plate offers a lower profile and easier access to wiring terminals for 25mm DIN rail applications.
4-22
Installation and Wiring of Base Plates
Page 59
Connecting Wiring Since a Type 2 Base Plate is designed for use with an LPR Router, the only cabling that will be connected to the Base Plate is power and the network cables for the two channels between which the router is connected. Bring the cabling into the electrical enclosure using suitable conduit fittings, bushings, or wire glands, and be sure to leave a service loop of 6 inches (15cm) of cable to simplify wiring the Type 2 Back Plate. Dress the cables using tie wraps or tape to ensure that the cabling is not compressed or caught when the base plate is screwed into place. Strip the cable jacket and wire conductors. The base plate screw terminals will accept 24AWG (0.5mm) to 12AWG (2.2mm) wire, which should be stripped to a length of 0.32” (8mm). Although not required, it may be useful to use a soldering iron to tin the stripped lengths of any stranded wires to prevent fraying and inadvertent contact with adjactent terminals. The screw terminal blocks on the rear panel of the Type 2 Base Plate are color coded to simplify wiring. The color coding scheme is shown in table 4.3. The optimum tightening torque for the Type 1 Base Plate screw terminals is 4 lbs. in. (0.5Nm) maximum. The proper screwdriver tip width is 0.125” (3mm).
Table 4.3 Type 2 Base Plate Terminal Block Color Coding Terminal Number 1-4 5
Terminal Color Orange Orange
6-9 10 and 12
Black Black
11 and 13
Black
14
Orange
15 - 18
Orange
Function Network A Cable shield, if used, internally connected to terminal 14 Power None Jumpered together internally may be used to land extra wires None Jumpered together internally may be used to land extra wires Cable shield, if used, internally connected to terminal 5 Network B
Two sets of screw terminals are provided for both the power and network wiring connections. These connections are internally jumpered on the Type 2 Base Plate PCB to provide continuity of the network and power wiring, even if no LonPoint Router module is installed. This feature permits the Base Plate wiring to be preinstalled and the network and power circuits checked for continuity throughout the installation, before a single LonPoint module is ever installed. This feature also prevents network and power interruptions as a result of hot-swapping LonPoint modules during commissioning or servicing operations. Finally, providing two sets of screw terminals permits incoming and outgoing wiring to be landed at separate screw terminals without the need to insert more than one wire in any given screw terminal, which improves wiring reliability.
LonPoint Hardware Guide
4-23
Page 60
LonPoint Type 2D DIN Base Plate Installation Figure 4.23 presents a detailed view of the front side of the base plate. The circuit board inside the Type 2D DIN Base Plate includes an arrow with the designation "2." The 2D Base Plate is intended to be installed either on a 35mm DIN rail or, using the integral keyhole slots, on a wall or panel. An arrow indicates the vertical orientation of the base plate which will provide the base viewing of the front panel legends of an installed LonPoint module.
4-24
Installation and Wiring of Base Plates