For the Echelon LPR-14

Page 37

4 Installation and Wiring of Base Plates

This chapter describes the process of installing LonPoint Base Plates. Type 1 Base Plates are used for mounting LonPoint Interface and Scheduler Modules to 4-inch square electrical boxes or Echelon's Eurobox. Type 1D DIN Rail Base Plates are used for mounting LonPoint Interface and Scheduler Modules to 35mm DIN rails (CENELEC EN 50022) or to walls or panels. Type 2 Base Plates are used for mounting LonPoint LPR Router Modules to 4-inch square electrical boxes or Echelon's Eurobox. Type 2D DIN Rail Base Plates are used for mounting LonPoint LPR Router Modules to 35mm DIN rails or to walls or panels.

LonPoint Hardware Guide

4-1

Page 38

LonPoint Type 1 Base Plate Installation Figure 4.1 presents a detailed view of the front side of the base plate. The circuit board inside the Type 1 Base Plate includes a large number “1A” in the lower right corner, as viewed from the front of the base plate, designating it as a Type 1 Base Plate with a Revision A circuit board. The “1A” designation indicates compatibility with LonPoint modules such as the DIO-10, that make use of screw terminal 14. Screw terminal 14 is NOT connected on older base plates marked “1”. Test points are provided on the circuit board for measuring all of the wiring connections. Symbols are silk-screened on the PCB to identify the functions of the test points.

4-2

Installation and Wiring of Base Plates

Page 39

Figure 4.1 LonPoint Type 1 Base Plate - Front Panel

Figure 4.2 shows a detailed view of the rear side of the base plate, the side to which

LonPoint Hardware Guide

4-3

Page 40

wiring connections are made.

Figure 4.2 LonPoint Type 1 Base Plate - Rear Wiring Panel As shown in figure 4.3, the Type 1 Base Plate is intended to be installed in an electrical box either vertically (base plate interior arrows pointing up) or rotated clockwise 90° (base plate interior arrows pointing to the right). These two orientations provide optimal viewing of the front panel legends of an installed LonPoint module, and also accommodate different methods of installing electrical boxes.

4-4

Installation and Wiring of Base Plates

Page 41

Figure 4.3 LonPoint Type 1 Base Plate Mounting Orientations

Installing A Compatible Electrical Box Compatible electrical boxes that will accept a Type 1 Base Plate include a 4” square electrical enclosure (Raco model No. 232, 236, 7232, 7054 or equal), two-gang PVC switch box (Raco 7834 or equal), and Echelon’s Model 48001 EuroBox for wall or electrical box applications. A 4” square electrical enclosures should be either affixed to a wall or to equipment using suitable mounting screws, or recessed using a suitable mounting clamp (figure 4.4). Due to variations in the location of knock-outs, care must be taken to ensure that 3/4” conduit fittings do not interfere with the Base Plate when it is installed in the electrical box; 1/2” conduit fittings have not been found to cause an interference problem.

LonPoint Hardware Guide

4-5

Page 42

Figure 4.4 4” Square Electrical Box Mounting There are four mounting options if Echelon’s EuroBox is used. The Eurobox requires the installer to drill cabling holes: ensure that suitable holes are drilled prior to mounting. In order to avoid interference with the Base Plate enclosure walls, all glands and conduit fittings must be located within 1.4”/35cm of the bottom of the box (as measured from the outside of the box). Wire glands and conduit fittings must not extend more than 0.63”/16mm into the EuroBox in order to prevent associated cabling from interfering with the Base Plate screw terminals. For UK applications, a second mounting option is to affix the EuroBox to a single gang 25mm BS4662 flush mounting box (MK 866ZIC or similar). Two keyhole slots are provided in the EuroBox to accomodate the flush mounting box as shown in figure 4.5. Use screws with flush mounting and ensure that suitable cabling holes are drilled in the Eurobox prior to mounting, as discussed above.

Figure 4.5 MK Electrical Box Mounting the EuroBox

4-6

Installation and Wiring of Base Plates

Page 43

For continental applications, a third mounting option is to affix the EuroBox to a recessed 6.5cm diameter plastic DIN box (Kaiser or equal). Two keyhole slots are provided in the EuroBox to accommodate DIN box mounting, as shown in figure 4.6. Use the screws provided with the DIN box and ensure that suitable cabling holes are drilled in the EuroBox prior to mounting.

Figure 4.6 DIN Box Mounting the EuroBox A fourth mounting option is to affix the EuroBox to 35mm DIN rail using DIN Clips (one pair included). Two sets of rectangular slots are provided for the DIN clips. Ensure that the clips provided with each EuroBox lock in place on the box and then snap them onto the DIN rail (figure 4.7). Ensure that suitable cabling holes are drilled in the EuroBox prior to mounting.

Figure 4.7 DIN Rail Mounting the EuroBox

The Type 1D DIN Base Plate offers a lower profile and easier access to wiring terminals for DIN rail applications.

LonPoint Hardware Guide

4-7

Page 44

Connecting Wiring Route network, power, and input/output cabling into the electrical enclosure using suitable conduit fittings, bushings, or wire glands. It is good practice to separate the input/output cabling as much as possible from the network and power cabling, especially if low level analog signals are being supervised. Once the cabling has been brought into the electrical enclosure, leave a service loop of 6 inches (15cm) of cable to simplify wiring the Type 1 Base Plate. Dress the cables using tie wraps or tape to ensure that the cabling is not compressed or caught when the base plate is screwed into place. Strip the cable jacket and wire conductors. The base plate screw terminals will accept 26AWG (0.4mm) to 12AWG (2.2mm) wire, which should be stripped to a length of 0.32” (8mm). Although not required, it may be useful to use a soldering iron to tin the stripped lengths of any stranded wires to prevent fraying and inadvertent contact with adjactent terminals. The screw terminal blocks on the real panel of the Type 1 Base Plate are color coded to simplify wiring. The color coding scheme is shown in table 4.1. The optimum tightening torque for the Type 1 Base Plate screw terminals is 4 lbs. in. (0.5Nm) maximum. The ideal flathead screwdriver tip width is 0.125” (3mm).

Table 4.1 Type 1 Base Plate Terminal Block Color Coding* Terminal Number 1-4 5 6-9 10 - 18

Terminal Color Orange Orange Black Green

Function Network Cable shield, if used Power I/O

* In beta release Type 1 Base Plates, terminals 5 and 14 were connected together but not connected to any I/O. In Type 1 Base Plate marked 1A, terminal 5 is floating and may be used to connect cable shield wires; terminal 14 is reserved for I/O. Two sets of screw terminals are provided for both the power and network wiring connections. These connections are internally jumpered on the Type 1 Base Plate PCB to provide continuity of the network and power wiring, even if no LonPoint module is installed, as shown figure 4.8. This feature permits the base plate wiring to be pre-installed and the network and power circuits checked for continuity throughout the installation, before a single LonPoint module is ever installed. This feature also prevents network and power interruptions as a result of hot-swapping LonPoint modules during commissioning or service operations. Finally, providing two sets of screw terminals permits incoming and outgoing wiring to be landed at separate screw terminals without the need to insert more than one wire in any given screw terminal.

4-8

Installation and Wiring of Base Plates