3 Network Cabling and Connections
This chapter provides information about network, power, and input/output cabling for the LonPoint system.
LonPoint Hardware Guide
3-1
Page 24
Network Cabling - TP/FT-10 Channel The LonPoint modules (excluding some LPR Routers) use Echelon’s FTT-10A Free Topology Transceiver for network communications. This transceiver operates at 78 kilobits per second and is designed to support free topology wiring; it will accommodate bus, star, loop, or any combination of these cabling topologies using a twisted pair cable. By eliminating restrictions on the cabling topology, the installer is free to locate LonPoint modules anywhere on the network cabling provided only that the maximum cabling distance limitations are observed99 This capability simplifies system installation and makes it easy to add nodes should the network need to be expanded. Figures 3.1 through 3.5 present five typical network topologies. In free topology cabling it is necessary to use one Echelon Model 44100 terminator. In bus topology cabling it is necessary to use two Echelon Model 44101 terminators. Terminators are required for proper network operation and must not be omitted.
Termination
Figure 3.1 Singly Terminated Bus Topology (Model 44100 Terminator)
Termination
Figure 3.2 Star Topology (Model 44100 Terminator)
Termination
Figure 3.3 Loop Topology (Model 44100 Terminator)
3-2
Network Cabling and Connections
Page 25
Termination
Figure 3.4 Mixed Topology (Model 44100 Terminator)
Termination
Termination
Figure 3.5 Doubly Terminated Bus Topology - Used for Very Long Cabling Distances (Two Model 44101 Terminators) A network consisting of LonPoint modules using the FTT-10A transceiver is said to reside on a “TP/FT-10 channel.” In some cases all of the LonPoint modules will be connected to a single TP/FT-10 channel. A maximum of 64 devices (LonPoint modules, routers, PCLTA-10 and PCC-10 PC adapters, third-party LONMARK® devices) may be connected to any one channel. If more than 64 devices are to be used, or if it is necessary to add more cabling than is permitted on a single channel, then one or more model 42100 LPR-10 Routers (TP/FT-10 to TP/FT-10) would be placed in series with the network cabling. Another application for the LPR Router is to limit the amount of network communications passing between different parts of a control network. For example, LPR Routers can restrict the transfer of messages from a portion of the network with many active PID loops to other, more quiescent parts of the network. In this case one or more model 42100 LPR-10 Routers would be placed in series with the network cabling. The LPR Router can also be used to create a high-speed backbone that brings together many different channels, perhaps to a monitoring PC. In this case it may be desirable to increase the speed of the backbone channel in order to better manage the communication traffic. For example, in a highrise building it might be desirable to have a78 kilobit per second TP/FT-10 free topology channel operating on each floor, and use a 1.25 megabit per second channel to link together all of the floor channels with a PC in the basement. In this case, one model 42102 LPR-12 Router (TP/FT-10 to TP/XF-1250) would be placed on each floor and a separate 1.25Mbps twisted pair channel would serve as a backbone.
LonPoint Hardware Guide
3-3
Page 26
The Model 42100 LPR-10 Router (TP/FT-10 to TP/FT-10) uses the TP/FT-10 channel cabling scheme. The Model 42102 LPR-12 Router (TP/FT-10 to TP/XF-1250) uses a different cabling scheme that is designed to handle high speed, 1.25Mbps communications. This 1.25Mbps cabling scheme is described in a later section.
System Performance and Cable Selection - TP/FT-10 Channel The system designer may choose a variety of cables, depending on cost, availability, and performance. Currently, Echelon has documented system performance on the cable types shown in tables 3.1 and 3.2. Up to 64 devices may be connected to each channel; one or more Model 42100 LPR-10 Routers may be used to increase the number of devices and cable distance. Network performance specifications assume that the average wire temperature is +55°C, although individual segments of wire may be as hot as +85°C. The free topology transmission specification includes two components which must both be met for proper system operation. The distance from each LonPoint module, network interface, or third party device to all other devices, and the distance from each LonPoint module, network interface, or third-party device to the Model 44100 Terminator, must not exceed the maximum node-to-node distance. If multiple paths exist, e.g., a loop topology, then the longest path should be used for the calculations. The maximum total wire length is the total amount of wire connected per channel.
Table 3.1 Free Topology Specifications
3-4
Maximum node-to-node distance
Maximum total wire length
Belden 85102
500 meters
500 meters
16AWG/1.3mm
Belden 8471
400 meters
500 meters
16AWG/1.3mm
Level IV, 22AWG
400 meters
500 meters
22AWG/0.65mm
JY (St) Y 2x2x0.8
320 meters
500 meters
20.4AWG/0.8mm
TIA Category 5
250 meters
450 meters
24AWG/0.51mm
Wire Diameter AWG/mm
Network Cabling and Connections
Page 27
If a shielded cable is used, the shield should be connected to earth ground via the termination circuit shown in the LONWORKS FTT-10A Free Topology Transceiver User's Guide, version 5 or later. Distributors of cable are listed in Echelon’s engineering bulletin, Junction Box and Wiring Guidelines, part number 005-0023-01.
Table 3.2 Doubly-Terminated Bus Topology Specifications (Requires Two Model 44101 Terminators)
Maximum bus length
Wire Diameter AWG/mm
Belden 85102
2700 meters
16AWG/1.3mm
Belden 8471
2700 meters
16AWG/1.3mm
Level IV, 22AWG
1400 meters
22AWG/0.65mm
JY (St) Y 2x2x0.8
900 meters
20.4AWG/0.8mm
TIA Category 5
900 meters
24AWG/0.51mm
A doubly-terminated bus may have cable lengths (stubs) of up to 3 meters from the bus to each LonPoint module, network interface, or third-party device.
TP/FT-10 Cable Termination The TP/FT-10 channel must be terminated for proper data transmission performance. Free Topology If free topology cabling is used then only one Model 44100 Terminator is required and may be placed anywhere on the free topology segment, as shown in figure 3.6. The Model 44100 Terminator's orange wires should be connected to the twisted pair network. The Terminator's green wire must be connected to earth ground. The green wire must never be connected to the shield of a twisted pair cable.
orange 44100 Terminator
Network Termination green
Figure 3.6 Single Termination for Free Topology (Model 44100 Terminator)
LonPoint Hardware Guide
3-5
Page 28
Doubly Terminated Bus Topology Segment If a doubly-terminated bus topology is used, then two Model 44101 terminators are required, one at each end of the bus, as shown in figure 3.7. The Model 44100 Terminator's orange wires should be connected to the twisted pair network. The Terminator's green wire must be connected to earth ground. The green wire must never be connected to the shield of a twisted pair cable.
orange orange 44100 Terminator
Network
Termination
Termination
44101 Terminator
Network green green
Figure 3.7 Double Termination for Bus Topology (Two Model 44101 Terminators)
Terminating Shielded Cables for the TP/FT-10 Channel Model 44100 and 44101 Terminators are intended for use exclusively with unshielded twisted pair cables and must NOT be used as terminators for shielded cables. If a shielded cable is to be used then special Terminators must be fabricated for both free topology and bus cabling architectures. These special Terminators will ensure the effectiveness of the shield in providing noise immunity in electromagnetically harsh environments. Figure 3.8 presents the schematic for a Free Topology Shielded Cable termination.
Network Cable
R2
R4
+
C1
Ground
Network Cable
+
R1
Cable Shield C2
R3
R1, R2, R3 R4 C1, C2
78.7 ž, 1%, 1/8W 150 ž , 1%, 1/8W 100 µ F±10%, 50V minimum aluminumelectrolytic type (observe polarity)
Figure 3.8 Free Topology Network Terminator for use with Shielded Cables (Use only one Terminator.) Figure 3.9 presents the schematic for a Bus Topology Shielded Cable termination.
3-6
Network Cabling and Connections
Page 29
Network Cable
R2
R4
+
C1
Ground
Network Cable
+
R1
Cable Shield C2
R3
R1, R2, R3 R4 C1, C2
316 ž, 1%, 1/8W 78.7 ž, 1%, 1/8W 150 ž , 1%, 1/8W 100 µ F ±10%, 50V minimum aluminumelectrolytic type (observe polarity)
Figure 3.9 Bus Topology Network Terminators for use with Shielded Cables (Two Required)
Network Cabling - TP/XF-1250 Channel If a high-speed backbone is created using the Model 42102 LPR-12 Routers (TP/FT-10 to TP/XF-1250), then a doubly-terminated bus topology using data grade cable that is intended specifically for this channel must be installed. The TP/XF-1250 channel can be used only with Level IV, 22 AWG (0.65mm) twisted pair cable, and the channel must be terminated at each end with a Model 44200 Terminator (do NOT use the Model 44100 or 44101 Terminators.) Suppliers of cable are listed in Echelon’s engineering bulletin, Junction Box and Wiring Guidelines, part number 005-0023-01, Rev D or higher. Under no circumstances should smaller gauge Level IV cable be substituted for Level IV, 22 AWG (0.65mm) twisted pair cable. Echelon periodically qualifies new cables for twisted pair transceivers, and it is advisable to check with Echelon from time to time to determine if new cables are available. DO NOT attempt to use any other type of cabling, including but not limited to Category 5 data cabling, or improper or erratic operation will result. A maximum of sixty-four (64) Model 42102 LPR-12 Routers (TP/FT-10 to TP/XF-1250), PC adapters, and other devices can be installed on a backbone channel, with a maximum cable length of 130 meters with a maximum stub length of 1 feet (0.3m). If additional cabling or devices must be installed, then one or more model 42105 LPR-15 (TP/XF-1250 to TP/XF-1250) Routers may be placed in series with the backbone cabling.
Distribution Rule for TP/XF-1250 Channel Due to the transmission characteristics of the TP/XF-1250 channel, communication failures may result from reflections of the TPT/XF-1250 transceiver’s 1.25Mbps transmitted signal under conditions where devices are concentrated in one point of cabling. These communication failures are eliminated when devices are used in a
LonPoint Hardware Guide
3-7
Page 30
distributed configuration. For this reason, it is essential to follow a simple topology rule when using the TPT/XF-1250 channel. Referred to as the “8-in-16” topology rule, this rule requires that no more than 8 devices be connected to the TP/XF-1250 channel within any 16 meter length of cable. This means that no matter where along the bus the 16 meter measurement is taken, there should be no more than 8 devices. Figure 3.10 provides a diagram of such a measurement technique.
Figure 3.10 8-in-16 Topology Rule Example In the example we see an installation with six groups of devices, varying in size from 2 to 7 devices, in a doubly-terminated bus that is terminated with Model 44200 Terminators. By using a 16 meter measurement stick that we can move from side-toside over the length of the bus, we can determine whether the 8-in-16 rule has been met (designated by the word "OK") or violated (shown by the designation "PROBLEM"). In the case of the PROBLEM area, a total of 13 devices are located within a 16 meter length of the bus, which amounts to five more devcies than are permitted under the 8in-16 rule. There are two solutions that can be applied to situations in which the 8-in-16 rule has been, or must be, violated by virtue of the installation scenario. The first and simplest remedy is to insert a Model 42105 LPR-15 Router (TP/XF-1250 to TP/XF-1250) and two Model 44200 Terminators in the bus to break the network into two channels (figure 3.11). Since each side of the router comprises a different channel, the bus is effectively split and the nodes divided between two channels.
Figure 3.11 Using a Router to Meet the 8-in-16 Topology Rule The second remedy to a violation of the 8-in-16 rule is to add additional cable to the bus such that the rule is no longer violated (figure 3.12). It is important to ensure that the maximum bus length (130 meters of 22AWG/0.65mm Level IV twisted pair) is not exceeded by the additional cable. Due to the complex interactions between the bus and the devcies with regard to reflections and transmission line delays, it is not possible to substitute an inductor/capacitor network in lieu of the additional cable to resolve this rule violation.
3-8
Network Cabling and Connections
Page 31
Figure 3.12 Using Additional Bus Cable to Meet the 8-in-16 Topology Rule
Terminator for TP/XF-1250 Channel It is necessary to terminate both endpoints of the TP/XF-1250 channel twisted pair bus for proper data transmission performance. Failure to terminate the bus will degrade network performance. Use only the Model 44200 Terminator, and connect it as shown in figure 3.13.
orange orange 44200 Terminator
Network
44200 Terminator
Network
Termination green
Termination green
Figure 3.13 Double Termination for Bus Topology (Two Model 44200 Terminators)
I/O Cabling The installer generally has wide latitude in the type of cabling selected for the I/O. It is good practice to ensure that all I/O cabling is made from twisted pair wire, as this has the advantage of minimizing susceptibility to differential noise. If the sensor or actuator requires a shield then a ground will have to be provided in the electrical box since the LonPoint modules are floating and do not include a ground screw connection. Note when selecting the I/O cabling that the Base Plate screw terminals accommodate wire guages from 24AWG/0.5mm to 12AWG/2mm. In all cases, use at least 90°C rated wire.
Power Cabling It is important to note that a maximum of 16 Amperes RMS at 24VAC RMS can be passed through the internal jumpers on the Power terminals of the Type 1/2 Base Plates, 10 Amperes RMS at 24 VAC RMS for Type 1D/2D DIN Base Plates using Jumper Plugs. This means that if power wiring is looped in and out of the power terminals of the LonPoint Base Plates, the current load presented by all of the LonPoint modules and any other devices powered by that circuit must be 16 Amperes ( 10 Amperes for Type 1D/2D DIN Base Plates using Jumper Plugs), as
LonPoint Hardware Guide
3-9
Page 32
shown in figure 3.14. If >16 Amperes (>10 Amperes RMS at 24 VAC RMS for Type 1D/2D DIN Base Plates using Jumper Plugs) must be supplied then the loopthrough capability of the LonPoint Base Plate power terminals must not be used and the power cabling should be run in parallel, as shown in figure 3.15. To calculate the load current, divide the total VA (sum of all devices powered by the power supply) by the power supply voltage. For example, if the total VA of all LonPoint Modules and sensors/actuators equals 100VA, and the power supply provides 24 VAC, then the load current is 4.16A.
Figure 3.14 Looped-through Power Wiring - •16 Amperes at 24VAC for Type 1/2 Base Plates, •10 Amperes for Type 1D/2D DIN Base Plates using Jumper Plugs
Figure 3.15 Parallel Power Wiring - >16 Amperes at 24VAC for Type 1/2 Base Plates, •10 Amperes for Type 1D/2D DIN Base Plates using Jumper Plugs As a rule of thumb, it is recommended that power and I/O cabling be separated by 18”/ 46cm to prevent inadvertent pick-up of noise from the power circuit by sensitive analog I/O cabling. Power and network twisted pairs may be combined in a common cable if using an approved network cable. Depending on the model, the LonPoint modules require between 2 and 6.5VA at an operating voltage of 16 to 30V DC or AC. The LonPoint Type 1/1D and Type 2/2D Base Plates include a power-looping capability that provides continuity through the Base Plate - even if the LonPoint module is removed - when the power cabling is daisy-chained through each Base Plate.
3-10
Network Cabling and Connections
Page 33
Tables 3.4 and 3.5 present the wire gauge that should be used in order to deliver the specified power (total VA) across the distance shown. These tables only include wire gauges from 24AWG (0.5mm) to 12AWG (2mm) as these are the wire gauges supported by the Base Plate screw terminals. For the supply cabling use at least 24AWG/0.5mm, 90° C rated wire. To determine the total power that a power cable must carry, total the VA requirements for all of the devices that will be drawing power from that cable, including both LonPoint modules and other devices. The VA ratings for the LonPoint Modules are shown in the module data sheets and are summarized in the following table.
Table 3.3 VA Ratings for LonPoint Modules LonPoint Module
VA Rating
DI-10 DO-10 DIO-10 AI-10 (all modes except 2-wire mode) AI-10 (2-wire mode) AO-10 SCH-10 LPR
2.2VA 6.5VA 4.75VA 2.1VA 4.5VA 4.5VA 2.4VA 2.0VA
To determine what gauge cable (in AWG or metric) will be required based on the total distance of the power cabling, refer to table 3.4 for cabling measured in AWG and table 3.4 for cabling measured in mm. If the wire gauge used is smaller than required, improper operation of one of more modules will result. All data in tables 3.4 and 3.5 assume an average wire temperature of +55°C.
Table 3.4 Power Cabling Requirements in AWG
Load (VA) Feet
Meters
35 40 55 65 70 75 90 100 105 115 135 145 150
10.7 12.2 16.8 19.8 21.3 22.9 27.4 30.5 32.0 35.1 41.1 44.2 45.7
10 22 22 22 22 22 22 22 22 22 22 22 22 22
15 22 22 22 22 22 22 22 22 22 22 22 22 22
LonPoint Hardware Guide
20 22 22 22 22 22 22 22 22 22 22 22 22 22
25 22 22 22 22 22 22 22 22 22 22 22 22 22
30 22 22 22 22 22 22 22 22 22 22 22 22 22
40 22 22 22 22 22 22 22 22 22 22 22 22 22
55 22 22 22 22 22 22 22 22 22 22 22 20 20
75 22 22 22 22 22 22 22 22 20 20 20 20 20
100 22 22 22 22 22 22 20 20 20 20 18 18 18
130 22 22 22 20 20 20 20 18 18 18 18 18 16
180 22 22 20 20 18 18 18 18 18 16 16 16 16
200 22 20 20 18 18 18 18 16 16 16 16 16 16
AWG
3-11
Page 34
155 165
47.2 50.3
22 22
22 22
22 22
22 22
22 22
22 22
20 20
20 18
18 18
16 16
16 16
14 14
180 14 14 14 14 14 14 12 12 12 12 12 12 12 12
200 14 14 14 14 12 12 12 12 12 12 12
Table 3.4 Power Cabling Requirements in AWG (continued)
Load (VA)
3-12
Feet
Meters
185 215 230 235 250 265 295 300 340 365 375 395 400 420 470 475 500 545 580 595 630 635 750 755 795 865 945 1000 1010 1190 1200 1260 1375 1500 1590 1645
56.4 65.5 70.1 71.6 76.2 80.8 89.9 91.4 103.6 111.3 114.3 120.4 121.9 128.0 143.3 144.8 152.4 166.1 176.8 181.4 192.0 193.5 228.6 230.1 242.3 263.7 288.0 304.8 307.8 362.7 365.8 384.0 419.1 457.2 484.6 501.4
10 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 20 20 20 20 20 20 20 18 18 18 18 18 18
15 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 22 20 20 20 20 20 20 20 20 18 18 18 18 18 18 18 16 16 16 16
20 22 22 22 22 22 22 22 22 22 22 22 20 20 20 20 20 20 20 20 20 18 18 18 18 18 18 18 16 16 16 16 16 16 16 14 14
25 22 22 22 22 22 22 22 22 20 20 20 20 20 20 20 20 18 18 18 18 18 18 18 18 16 16 16 16 16 16 16 14 14 14 14 14
30 22 22 22 22 22 20 20 20 20 20 20 20 18 18 18 18 18 18 18 18 18 16 16 16 16 16 16 16 14 14 14 14 14 14 14 12
40 22 20 20 20 20 20 20 18 18 18 18 18 18 18 18 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 12 12 12 12 12 12
55 20 20 18 18 18 18 18 18 18 16 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 12 12 12 12 12 12 12
75 18 18 18 18 18 16 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 14 12 12 12 12 12 12 12
100 18 16 16 16 16 16 16 16 14 14 14 14 14 14 14 14 12 12 12 12 12 12 12 12
130 16 16 16 14 14 14 14 14 14 14 12 12 12 12 12 12 12 12 12
AWG
Network Cabling and Connections
Page 35
Table 3.5 Power Cabling Requirements In mm Load (VA) Feet Meters 10 23.0 7 0.50 32.8 10 0.50 36.1 11 0.50 42.7 13 0.50 45.9 14 0.50 55.8 17 0.50 59.1 18 0.50 62.3 19 0.50 75.5 23 0.50 82.0 25 0.50 88.6 27 0.50 91.9 28 0.50 101.7 31 0.50 114.8 35 0.50 141.1 43 0.50 150.9 46 0.50 154.2 47 0.50 170.6 52 0.50 183.7 56 0.50 193.6 59 0.50 213.3 65 0.50 229.7 70 0.50 232.9 71 0.50 239.5 73 0.50 242.8 74 0.50 259.2 79 0.50 292.0 89 0.50 305.1 93 0.50 308.4 94 0.50 334.6 102 0.50 360.9 110 0.50 387.1 118 0.50 390.4 119 0.50 400.3 122 0.50 413.4 126 0.50 459.3 140 0.50 469.2 143 0.65 518.4 158 0.65
15 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65
LonPoint Hardware Guide
20 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 0.80
25 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 1.00
30 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00
40 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30
55 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30
75 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60
100 0.50 0.50 0.50 0.50 0.50 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 1.60 1.60 2.00
130 0.50 0.50 0.65 0.65 0.65 0.65 0.65 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00 2.00
180 0.50 0.65 0.65 0.65 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
200 0.50 0.65 0.65 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00 mm
3-13
Page 36
Table 3.5 Power Cabling Requirements In mm (continued)
Load (VA) Feet Meters 10 554.5 169 0.65 564.3 172 0.65 587.3 179 0.65 613.5 187 0.65 626.6 191 0.65 721.8 220 0.65 734.9 224 0.65 777.6 237 0.65 784.1 239 0.80 856.3 261 0.80 918.6 280 0.80 961.3 293 0.80 1036.7 316 0.80 1177.8 359 0.80 1227.0 374 1.00 1243.4 379 1.00 1312.3 400 1.00 1555.1 474 1.00 1571.5 479 1.00 1640.4 500 1.00
3-14
15 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30
20 0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60
25 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60
30 1.00 1.00 1.00 1.00 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 2.00
40 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00
55 1.30 1.30 1.60 1.60 1.60 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00 2.00
75 1.60 1.60 1.60 1.60 1.60 2.00 2.00 2.00 2.00 2.00 2.00 2.00
100 2.00 2.00 2.00 2.00 2.00 2.00
130 2.00
180
200 mm
Network Cabling and Connections