2 Description of the LonPoint Modules and Base Plates
This chapter provides a description of the LonPoint Interface, Router, and Scheduler modules, Type 1 and Type 2 Base Plates, and Type 1D and Type 2D DIN Base Plates mounting enclosures.
LonPoint Hardware Guide
2-1
Page 12
LonPoint Interface Modules The LonPoint Interface Modules are designed to monitor and control a wide variety of analog and digital sensors and actuators, and are the primary means of interfacing a LonPoint system to devices that lack an integral LONWORKS interface, i.e., a Neuron Chip and transceiver. By selecting the correct LonPoint Interface Module and configuring both its hardware and software correctly, a wide and varied assortment of sensors and actuators can be supported. There are five types of LonPoint Interface Modules which share a common form factor but differ in terms of their I/O and internal software functions. The five modules include the DI-10 Digital Input Module, DO-10 Digital Output Module, DIO-10 Digital Input Output Module, AI-10 Analog Input Module, and AO-10 Analog Output Module. The DI-10 Digital Input Module provides four digital inputs for supervising voltage ranges 0-5VDC through 0-32VDC or dry contacts. Inputs are isolated from the input power and the network but not from each other. Separate status LEDs are provided for each input. The DO-10 Digital Output Module includes four digital outputs rated at 0-12V, 100mA source/sink per output, 110mA source, 400mA sink all outputs combined. Outputs are isolated from the input power and the network but not from each other. Each output may be separately overridden by a hand/off/auto switch accessible from the front panel. Separate status LEDs are provided for each output. The DIO-10 Digital Input Output Module provides two digital inputs and two relay outputs. The digital inputs include configurable input thresholds for supervising dry contacts or 5V, 12V, 24V, or 31V DC inputs. In addition, the digital inputs can be set to measure frequency ( 20kHz) inputs. The inputs are isolated from the input power and the network, but are not isolated from each other. Each relay output consists of a Form A (normally open) and Form B (normally closed) contact which share a common wiper. The relay contacts are rated for 2A continuous, 6A momentary, at 30VAC or 42VDC. Each output may be separately controlled by a hand/off/auto switch accessible from the front panel. Separate status LEDs are provided for each input and output. The AI-10 Analog Input Module provides two independent 16-bit resolution analog inputs which are isolated from the input power and the network but not from each other. Each input can be configured via jumper blocks to monitor RTDs, thermistors, and other types of analog inputs. Inputs can be separately configured as a voltage input, resistive transducer input, loop-powered 0-24mA current input, or remote-powered 024mA current input. Voltage input ranges can be selected via the LonPoint Plug-in to be 0-156mV, 0-625mV, 0-10V, or 0-20V. Current input ranges can be set via the LonPoint Plug-in to be 0-25mA, 0-12.5mA, 0-781µA, or 0-19.5µA. Resolution in the 020V range is 0.3mV per step; current input resolution in the 0 - 25mA range is 0.37µA per step. For resistive transducers, the module includes a configurable current source which can be set, under software control, to provide either 25µA or 400µA current for resistance measurement of transducers from 100 to 15k (nominal). The AO-10 Analog Output Module offers two independent 12-bit resolution analog outputs. Each output can be separately configured for voltage or current output, and can drive 0-10V into a 1k load or 0-20mA or 4-20mA @ 0-12V. Outputs are isolated from the input power and the network but not from each other.
2-2
LonPoint Modules and Base Plates
Page 13
Lo
E nP oi nt ™
In te r fa ce
The LonPoint Interface Modules share a common form factor that includes a front panel assembly to which a printed circuit board (PCB) with active electronics is connected. The front panel of all of the modules includes a service switch and service LED, a combination power/wink LED, and a network connector (figure 2.1).}
DI-10 m c U L us ®
MODEL 41100 972 LISTED 178K ENERGY MANAGEMENT SW VERSION 1.0 EQUIPMENT SUBASSEMBLY ID NUMBER INPUT: 0-32VDC
DI-10 MODEL 41100
ID NUMBER
DI-10 MODEL 41100
ID NUMBER
1 2 3 4
Figure 2.1 LonPoint Interface Module - Typical Front Panel The rear of the PCB assembly includes a polarized, shrouded, 14-pin interface connector that connects to a mating socket in a Type 1 Base Plate or Type 1D DIN Base Plate. Any user-configured jumpers are also located on the rear of the PCB assembly (figure 2.2).
LonPoint Hardware Guide
2-3
Page 14
Figure 2.2 LonPoint Interface Module - Typical Rear Panel and Jumpers Network, power, and I/O wiring is connected to screw terminals located on a Type 1 Base Plate (figure 2.3) or Type 1D DIN Base Plate (figure 2.4), into which the LonPoint Interface Module is plugged; no wiring is ever connected directly to an Interface Module. A writing space is provided on the back of the Type 1 Base Plate for recording the date of installation or other pertinent information. Installers should take care to use a finepoint (smudge-free) pen. Type 1/1D and Type 2/2D Base Plates are keyed to prevent accidental insertion of an incorrect module type. The Type 1 Base Plate (Model 40111) and the Type 1D DIN Base Plate (Model 48111) will only accommodate Interface Modules and Scheduler Modules. The Type 2 Base Plate (Model 40222) and the Type 2D DIN Base Plate (Model 48222) will only accept LPR-1X Router Modules. In either Type 1/1D or Type 2/2D Base Plates, the associated module is affixed to the Base Plate by means of two 8-32, 3/8” screws (Echelon 205-0130-01) that are provided with each module.
2-4
LonPoint Modules and Base Plates
Page 15
Cr
@®CH0N bode 40111
= _
O/O/O;/oj;oO;oO/;oO;oO/oO O/O/O;o;oO;oO/;/o;oO/o, = ous = hl PUT BC Ge
= =
= =
= =
= =.
VT LT ca a,
| i 12) 12)
Figure 2.3 LonPoint Type 1 Base Plate
LonPoint Hardware Guide
Front view
Rear View
2-5
Page 16
18
17
16
15
14
13
12
11
10
18
17
16
15
14
13
12
11
10
CAUTION
I/O
1A
Front View
Network 1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Jumper Plug (one supplied with each DIN Base Plate)
Figure 2.4 LonPoint Type 1D Base Plate
2-6
LonPoint Modules and Base Plates
Page 17
The Type 1 Base Plate is mounted to either a suitable US 4” square, 2” deep (10.16cm x 5.08cm) electrical box, US double gang electrical box, plastic Echelon EuroBox (figures 2.5-2.7), or an IP-65 (NEMA 4) enclosure.
Figure 2.5 LonPoint Interface Module 4” Square (2” Deep) Electrical Box Mounting Configuration
Figure 2.6 LonPoint Interface Module Double Gang (2” Deep) Electrical Box Mounting Configuration
Figure 2.7 LonPoint Interface Module Eurobox Mounting Configuration
LonPoint Hardware Guide
2-7
Page 18
The Type 1D DIN Base Plate may be mounted to either a 35mm DIN rail or to a wall panel (figures 2.8). A jumper plug supplied with the Base Plate permits the power and network connections of several Type 1D DIN Base Plates to be interconnected without additional wiring.
Figure 2.8 LonPoint Interface Type 1D Base Plate Mounting Configuration Prior to installing the base plate, it is important to understand the symbology used on the base plates, interface modules, and router modules.
2-8
LonPoint Modules and Base Plates
Page 19
LonPoint Interface and Router Module Symbology The front and rear panels of the LonPoint Modules and Base Plates contain legends that identify the function of the module and its various LEDs, switches, and network connector. A common legend marking scheme is used that allows the module to be rotated clockwise 90° and still be legible, in the event that the mounting enclosure is installed off axis. The symbols used are as follows: Network Connector
Each module includes a network connector for accessing the TP/FT-10 network directly from the front panel. This feature is intended to allow a laptop PC equipped with a Model 73200 PCC-10 PC Card and Model 78303 cable assembly to plug into the LonPoint module and program, monitor, troubleshoot, or update a LonPoint system. The 3.5mm mating plug is a Hosiden 315-0201-01 miniature phone jack, or equal.
Front Panel Label
DI-10 m c U L us ®
MODEL 41100 972 LISTED 178K ENERGY MANAGEMENT SW VERSION 3.0 EQUIPMENT SUBASSEMBLY ID NUMBER INPUT: 0-32VDC
DI-10 MODEL 41100
ID NUMBER
DI-10 MODEL 41100
ID NUMBER
Every module is supplied with a front panel label that identifies the model number and software version number of the module. The front panel label also includes two peel-off Code 39 bar code labels on which are printed the Neuron Chip ID of that module (LPR modules have two Neuron Chip IDs, one per channel). These labels are intended to assist the installer during installation time, and may be removed from the module and placed on installation drawings for reference purposes. Service Switch/LED
Every module includes a service switch and LED which may be used during module installation and to identify configured and unconfigured modules.
LonPoint Hardware Guide
2-9
Page 20
Power or Power/Wink LED
Every module includes either a power LED or a combination power/wink LED. The wink function is used by a network management/installation tool to visually identify a particular module; the wink command causes the power LED to blink.
I/O Number
1 2 3 4 Every input and output symbol is accompanied by an I/O Number designating which hardware input or output the function is associated. The DI-10 has four inputs, the DO10 has four outputs, the DIO-10 has two inputs and two outputs, the AI-10 has two inputs, and the AO-10 has two outputs.
Digital Input
This symbol designates the I/O as a digital input and is accompanied by an I/O Number.
Digital Output
This symbol designates the I/O as a digital or relay output and is accompanied by an I/O Number.
Analog Input
This symbol designates the I/O as an analog input and is accompanied by an I/O Number.
2-10
LonPoint Modules and Base Plates
Page 21
Analog Output
This symbol designates the I/O as an analog output and is accompanied by an I/O Number.
Hand/Off/Auto Switch
1234 1
1
2 3 4
1
0
DO-10 Hand/Off/Auto Switch
1 2 3 4
2
DIO-10 Hand/Off/Auto Switch
The DO-10 and DIO-10 modules include a Hand/Off/Auto switch that allows the user to determine the mode of operation of the outputs. One three-position switch is provided for each of the four outputs. The switch positions function as follows:
1
Output turned ON (voltage level high or relay actuated)
0
Output turned OFF (voltage level low or relay not actuated) Output state is determined automatically according configuration programs loaded into the LonPoint modules on the network.
Input Status LEDs
1 2 3 4 Input status LEDs indicate the state of the inputs.
Output Status LEDs
1 2 3 4 Output status LEDs indicate the logical state of the outputs.
LonPoint Hardware Guide
2-11
Page 22
Router Channel A
A LPR Routers route packets between two twisted pair channels, designated A and B.
Router Channel B
B LPR Routers route packets between two twisted pair channels, designated A and B.
Router Activity LED
Indicates that a router is transferring packets from one channel to another.
2-12
LonPoint Modules and Base Plates