Page 94

9 Installing the AO-10 Analog Output Module

This chapter describes the process of installing the Model 41400 AO-10 Analog Output Module.

LonPoint Hardware Guide

9-1

Page 95

LonPoint AO-10 Analog Output Module The front panel of the AO-10 module is shown in figure 9.1. There are no front panel LEDs associated with the outputs, however, there are userconfigured jumper blocks that must be set correctly for each analog output.

Network Access Jack; Use With Echelon PCC-10 Cable Model 78303

™ int E nPo Lo ce rfa e t In

LonPoint Interface Model and Software Revision Numbers

AO-10 m c U L us ®

MODEL 41400 9760 LISTED 178K ENERGY MANAGEMENT SW VERSION 3.0 EQUIPMENT SUBASSEMBLY ID NUMBER OUTPUT: 1012VDC, 0-20mA EACH

AO-10 MODEL 41400

ID NUMBER

AO-10 MODEL 41400

ID NUMBER

1 2

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number Service LED Service Switch

Analog Output Identifier (No LEDs For Analog Outputs) Analog Output 1 1 Analog Output 2 2

Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing

Figure 9.1 LonPoint AO-10 Analog Input Module - Front Panel The AO-10 module includes two 4 x 2 jumper blocks for each output. These jumper blocks, labeled 0-10V and 4-20mA, are used to configure the module for the type of analog output signal that will be generated (figure 9.2); using an incorrect jumper setting will result in improper output signals. Each of the two outputs may be

9-2 Module

Installing the AO-10 Analog Output

Page 96

configured differently. Table 9.1 presents the correct jumper position for different types of analog outputs. The AO-10 sources, but does not sink, current. For wiring simplicity, 4-20mA actuators attached to the AO-10 module should be operated in 2-wire mode, provided that they can operate at 12V or less. Actuators that require >12V across their terminals should be operated in a 4-wire mode and powered from a separate power supply.

Figure 9.2 LonPoint AO-10 Jumper Block Settings - Rear Panel Table 9.1 AO-10 Analog Output Module Wiring Connections Jumper Position Output #1

Function Output 1 0-10V Output

0-10V 4-20mA

LonPoint Hardware Guide

Description This setting is used for generating a 0-10V output from the 12-bit D/A converter via a voltage amplifier. Output load may be as low as 1K Ohms.

9-3

Page 97

Output #2

Output 2 0-10V Output 0-10V 4-20mA

Output #1

Output 1 Programmable range within 0-20mA 0-10V 4-20mA

Output #2

Output 2 Programmable range within 0-20mA 0-10V 4-20mA

This setting is used for generating a 0-10V output from the 12-bit D/A converter via a voltage amplifier. Output load may be as low as 1K Ohms. This setting is used for generating any output range from 0-20mA (software programmable), i.e., 4-20mA from the 12-bit D/A converter via a current amplifier. The AO-10 sources current only - it cannot function as a current sink. Output load may be as low as 1K Ohms. This setting is used for generating any output range from 0-20mA (software programmable), i.e., 4-20mA from the 12-bit D/A converter via a current amplifier. The AO-10 sources current only - it cannot function as a current sink. Output load may be as low as 1K Ohms.

The AO-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections to the AO-10 module are presented in table 9.2. Specifications for the AO-10 module are shown in table 9.3.

Table 9.2 AO-10 Analog Output Module Wiring Connections Screw Terminal 1 and 2 3 and 4 5 6 and 7

10 11 12 13 14 15 16 17 18

Wiring Connection Incoming network wiring, TP/FT-10 channel, polarity-insensitive Outgoing network wiring, TP/FT-10 channel, polarity-insensitive Unused Incoming power wiring, 16-30VAC or VDC @4.2VA, polarityinsensitive. If using DC power it is good practice to maintain continuity of the power polarity throughout the network. Terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. + input of analog output 1 - input of analog output 1 + input of analog output 2 - input of analog output 2 Unused Unused Unused Unused Unused

Table 9.3 LonPoint AO-10 Analog Output Module Specifications

9-4 Module

Installing the AO-10 Analog Output

Page 98

Function Processor/memory Service function I/O I/O type I/O resolution I/O isolation Transceiver type Network connector Input power Mounting Temperature Humidity EMI Safety agency Function Blocks Software Configuration

Description Neuron 3150 Chip, 10MHz, 56K flash memory Recessed service switch, service LED, power/wink LED. Dual tearoff bar-code Neuron ID self-adhesive tag for application to red-line drawings in the field 2 independent 12-bit resolution analog outputs 0-10V into 1k•, minimum, or 0 to 20mA @ 0-12V 0-10VDC: 2.5mV resolution 0-20mA: 5.0µA resolution 100V, transformer isolation. Outputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility link power channel Phone plug connector accessible from front panel 16-30VAC or VDC @ 4.2VA, internally isolated power supply Type 1 or Type 1D Base Plate -40 to +85°C, operating and non-operating 10 to 95% RH @ 50°C FCC A, CE Mark UL 916 Node object (1), analog output open-loop actuator objects (2), digital encoder controller objects (1), analog function block controller objects (2), PID controller objects (2), type translators (3) Wide variety of LONMARK Standard Configuration Parameter Types supported by direct memory read/write function of LNS compatible network management tools

AO-10 Module Software Settings The software settings of the AO-10 module are described in the LonPoint Application and Plug-In Guide.

Installing the AO-10 Module Installation of the AO-10 module involves the following steps: 1. Ensure that the Base Plate has been wired and installed correctly, and is securely fastened to the electrical enclosure. 2. Check for continuity on all network and power wiring. Ensure that the correct actuators are connected to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the AO-10 module into the Base Plate by aligning the network access jack on the AO-10 with the arrow head on the Base Plate (the arrow should point in the direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector.

LonPoint Hardware Guide

9-5

Page 99

5. The AO-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off.

9-6 Module

Installing the AO-10 Analog Output

Page 100

6. Securely attach the AO-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in/0.5Nm torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the AO-10 module. 8. See Troubleshooting for assistance with improper AO-10 module operation.

LonPoint Hardware Guide

9-7