Page 101

10 Installing the SCH-10 Scheduler Module

This chapter describes the process of installing the Model 43100 SCH-10 Scheduler Module.

LonPoint Hardware Guide

10-1

Page 102

LonPoint SCH-10 Scheduler Module The front panel of the SCH-10 module is shown in figure 10.1. There are no userconfigured jumper blocks or other adjustable controls on the SCH-10 module.

Network Access Jack; Use With Echelon PCC-10 Cable Model 78303 t™ E Poin n Lo ler du e h Sc

SCH-10 m c U L us ®

LonPoint Interface Model and Software Revision Numbers

MODEL 43100 976 LISTED 178K ENERGY MANAGEMENT SW VERSION 3.0 EQUIPMENT SUBASSEMBLY ID NUMBER I/O: 0-5 VDC

SCH-10 MODEL 43100

ID NUMBER

SCH-10 MODEL 43100

ID NUMBER

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number Service LED Service Switch

Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing Figure 10.1 LonPoint SCH-10 Scheduler Module - Front Panel The SCH-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections to the SCH-10 module are presented in table 10.1. Specifications for the SCH-10 module are shown in table 10.2.

10-2 Module

Installing the SCH-10 Scheduler

Page 103

Table 10.1 SCH-10 Scheduler Module Wiring Connections Screw Terminal 1 and 2 3 and 4 5 6 and 7

Wiring Connection Incoming network wiring, TP/FT-10 channel, polarity-insensitive Outgoing network wiring, TP/FT-10 channel, polarity-insensitive Unused Incoming power wiring, 16-30VAC or VDC, 2.4VA, polarityinsensitive. If using DC power, it is good practice to maintain continuity of the power polarity throughout the network. Terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. TXD GND RXD GND Unused RTS GND CTS GND

10 11 12 13 14 15 16 17 18

Table 10.2 LonPoint SCH-10 Scheduler Module Specifications Function Processor/memory Clock/calendar Service function I/O, Not Currently Supported, Reserved for Future Use I/O isolation Transceiver type Network connector Input power Mounting

LonPoint Hardware Guide

Description Neuron 3150 Chip, 10MHz, 56K flash memory, 512K batterybacked RAM (2 weeks minimum back-up, 5 months typical; low-battery detection) Battery-backed clock/calendar (10 year life, low-battery detection), seconds, minutes, hours, day of week, month, year Recessed service switch, service LED, power/wink LED. Dual tear-off bar-code Neuron ID self-adhesive tags for application to red-line drawings in the field EIA-232 serial port with software UART, selectable bit rate (600, 1200, 2400, 4800), two start, one stop, and no parity bits. Designed to support Termiflex or equal terminal 100V, transformer isolation. Outputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility with link power channel Phone plug connector accessible from front panel 16-30VAC or VDC @ 2.4VA, internally isolated power supply Type 1 or Type 1D Base Plate

10-3

Page 104

Temperature Humidity EMI Safety agency Function Blocks Software Configuration

-10 to +60°C, operating and non-operating 10 to 95% RH @ 50°C FCC A, CE Mark UL 916 Node object (1), state machine controller object, event scheduler controller object, real-time clock object Wide variety of LONMARK Standard Configuration Parameter Types supported by direct memory read/write function of LNS compatible network management tools

SCH-10 Module Software Settings The software settings of the SCH-10 module are described in the LonPoint Application and Plug-In Guide.

Installing the SCH-10 Module Installation of the SCH-10 module involves the following steps: 1. Ensure that the Base Plate has been wired and installed correctly, and is securely fastened to the electrical enclosure. 2. Check for continuity on all network and power wiring. Ensure that the correct EIA232 connections, if used, have been made to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the SCH-10 module into the Base Plate by aligning the network access jack on the SCH-10 with the arrow head on the Base Plate (the arrow should point in the direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector. 5. The SCH-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off. 6. Securely attach the SCH-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in/0.5Nm torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the SCH-10 module. 8. See Troubleshooting for assistance with improper SCH-10 module operation.

10-4 Module

Installing the SCH-10 Scheduler