Page 85

8 Installing the AI-10 Analog Input Module

This chapter describes the process of installing the Model 41300 AI-10 Analog Input Module.

LonPoint Hardware Guide

8-1

Page 86

LonPoint AI-10 Analog Input Module The front panel of the AI-10 module is shown in figure 8.1. There are no front panel LEDs associated with the inputs, however, there are user-configured jumper blocks that must be set correctly for each analog input.

Network Access Jack; Use With Echelon PCC-10 Cable Model 78303

™ int o E nP Lo ce fa er t In

LonPoint Interface Model and Software Revision

AI-10 m c U L us ®

MODEL 41300 9760 LISTED 178K SW VERSION 3.0 ENERGY MANAGEMENT EQUIPMENT SUBASSEMBLY ID NUMBER INPUT: 0-20VDC, 0-24mA EACH

AI-10 MODEL 41300

ID NUMBER

AI-10 MODEL 41300

ID NUMBER

1 2

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number Service LED Service Switch

Analog Input Identifier (No LEDs For Analog Inputs) Analog Input 1 1 Analog Input 2 2

Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing

Figure 8.1 LonPoint AI-10 Analog Input Module - Front Panel

8-2

Installing the AI-10 Analog Input Module

Page 87

The AI-10 module includes four 5 x 2 jumper blocks for each input. These jumper blocks, labeled 2WIR, 4WIR, RES, and VOLT, are used to configure the module for the type of analog input signal that will be monitored (figure 8.2); using an incorrect jumper setting will result in improper input supervision and could cause damage to the module and/or the sensor. Each of the two sensor inputs may be configured differently. Table 8.1 presents the correct jumper position for different types of analog inputs.

Figure 8.2 LonPoint AI-10 Jumper Block Settings - Rear Panel Table 8.1 AI-10 Analog Input Module Wiring Connections Function Input 1 4-Wire 0-24mA Remotely Powered

Jumper Position Input #1

4WIR 2WIR RES

LonPoint Hardware Guide

VOLT

Description This setting is used for connecting 0-20mA, 4-20mA, 4-24mA, or 0-24mA intelligent transmitters that are powered by either their own power supply or a separate power supply. The maximum allowable current range is 0-25mA. In this setting the AI-10 does not supply power to the current loop.

8-3

Page 88

Input #2

Input 2 4-Wire 0-24mA Remotely Powered 4WIR 2WIR RES

Input 1 2-Wire 4-20mA Current Loop Powered

Input #1

4WIR 2WIR RES

VOLT

4WIR 2WIR RES

VOLT

Input #2

Input 2 2-Wire 4-20mA Current Loop Powered

Input 1 Passive Resistive Sensor

Input #1

4WIR 2WIR RES

VOLT

4WIR 2WIR RES

VOLT

Input #2

Input 2 Passive Resistive Sensor

8-4

VOLT

This setting is used for connecting 0-20mA, 4-20mA, 4-24mA, or 0-24mA intelligent transmitters that are powered by either their own power supply or a separate power supply. The maximum allowable current range is 0-25mA. In this setting the AI-10 does not supply power to the current loop. This setting is used for connecting 4-20mA intelligent transmitters that are powered by the current loop provided by the AI-10 module. The maximum allowable current range is 0-25mA in order to permit fault conditions to be detected (open as 0mA, short circuit as 25mA). This mode is not suitable for measuring passive resistive devices. Minimum loop voltage is 12VDC. This setting is used for connecting 4-20mA intelligent transmitters that are powered by the current loop provided by the AI-10 module. The maximum allowable current range is 0-25mA in order to permit fault conditions to be detected (open as 0mA, short circuit as 25mA). This mode is not suitable for measuring passive resistive devices. Minimum loop voltage is 12VDC. This setting is used for connecting passive resistive sensors to the AI-10 module. Resistance is measured by passing a controlled current through the sensor and then measuring the resulting voltage across the AI-10 screw terminals. Measurements of passive resistive devices may only be taken using the RES mode - the 2WIR mode is not suitable for this purpose. See text below for a discussion of the range and software settings for the RES mode. In this mode 3.5V is provided on the (+) terminal and programmable current sink (25mA or 400mA on the (-) terminal). This setting is used for connecting passive resistive sensors to the AI-10 module. Resistance is measured by passing a controlled current through the sensor and then measuring the resulting voltage across the AI-10 screw terminals. Measurements of passive resistive devices may only be taken using the RES mode - the 2WIR mode is not suitable for this purpose. See text below for a discussion of the range and software settings for the RES mode. In this mode 3.5V is provided on the (+) terminal and programmable current sink (25mA or 400mA on the (-) terminal).

Installing the AI-10 Analog Input Module

Page 89

Input 1 Voltage Sensing

Input #1

4WIR 2WIR RES

VOLT

4WIR 2WIR RES

VOLT

Input #2

Input 2 Voltage Sensing

This setting is used for connecting an intelligent transmitter that generates a 0-5V, 0-10V, or 0-20V output. See text below for a discussion of the range and software settings for the VOLT mode. This setting also can be used to measure passive thermocouplers. The input resistance of the analog input is 7.246K Ohms ± 0.3%. This setting is used for connecting an intelligent transmitter that generates a 0-5V, 0-10V, or 0-20V output. See text below for a discussion of the range and software settings for the VOLT mode. This setting also can be used to measure passive thermocouplers. In this mode 3.5V is provided on the (+) terminal and programmable current sink (25mA or 400mA on the (-) terminal).

The AI-10 module is installed in a Type 1 Base Plate. Wiring connections to the AI-10 module are presented in table 8.2. Specifications for the AI-10 module are shown in table 8.3.

Table 8.2 AI-10 Analog Input Module Wiring Connections Screw Terminal 1 and 2 3 and 4 5 6 and 7

Wiring Connection Incoming network wiring, TP/FT-10 channel, polarity-insensitive Outgoing network wiring, TP/FT-10 channel, polarity-insensitive Unused Incoming power wiring, 16-30VAC or VDC, 2.1VA for all mdoes except 2-wire mode (4.5VA) maximum, polarity-insensitive. If using DC power, it is good practice to maintain continuity of the power polarity throughout the network. Terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. + input of analog input 1 - input of analog input 1 + input of analog input 2 - input of analog input 2 Unused Unused Unused Unused Unused

10 11 12 13 14 15 16 17 18

Table 8.3 LonPoint AI-10 Analog Input Module Specifications Function Processor/memory Service function I/O

LonPoint Hardware Guide

Description Neuron 3150 Chip, 10MHz, 56K flash memory Recessed service switch, service LED, power/wink LED. Dual tear-off bar-code Neuron ID self-adhesive tag for application to red-line drawings in the field 2 independent 16-bit resolution analog inputs

8-5

Page 90

I/O type

I/O resolution I/O isolation Transceiver type Network connector Input power Mounting Temperature Humidity EMI Safety agency Function Blocks Software Configuration

0 to 156mV 0 to 625mV 0 to 10V 0 to 20V 0 to 24mA 0 - 12.5µA 0 - 781µA 0 - 19.5µA Resistive transducer ranging from 100• to 15k•, nominal 0 to 20VDC: 0.3mV resolution 0 to 24mA: 0.37µA resolution 100V, transformer isolation. Inputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility with link power channel Phone plug connector accessible from front panel 16-30VAC or VDC, internally isolated power supply - 2.1VA for all modes except 2-wire mode (4.5VA) Type 1 or Type 1D Base Plate -40 to +85°C, operating and non-operating 10 to 95% RH @ 50°C FCC A, CE Mark UL 916 Node object (1), analog input open-loop sensor objects (2), digital encoder controller objects (2), analog function block controller objects (4), type translators (4) Wide variety of LONMARK Standard Configuration Parameter Types supported by direct memory read/write function of LNS compatible network management tools

AI-10 Module Software Settings The software settings of the AI-10 module are described in the LonPoint Application and Plug-In Guide.

Installing the AI-10 Module Installation of the AI-10 module involves the following steps: 1. Ensure that the Base Plate has been wired and installed correctly, and is securely fastened to the electrical enclosure. 2. Check for continuity on all network and power wiring. Ensure that the correct sensors are connected to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the AI-10 module into Base Plate by aligning the network access jack on the AI-10 with the arrow head on the Base Plate (the arrow should point in the

8-6

Installing the AI-10 Analog Input Module

Page 91

direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector. 5. The AI-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off.

LonPoint Hardware Guide

8-7

Page 92

6. Securely attach the AI-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in/0.5Nm torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the AI-10 module. 8. See Troubleshooting for assistance with improper AI-10 module operation.

8-8

Installing the AI-10 Analog Input Module

Page 93

LonPoint Hardware Guide

8-9