Page 79

7 Installing the DO-10 Digital Output Module

This chapter describes the process of installing the Model 41200 DO-10 Digital Output Module.

LonPoint Hardware Guide

7-1

Page 80

LonPoint DO-10 Digital Output Module The front panel of the DO-10 module is shown in figure 7.1. There are no userconfigured jumper blocks on the DO-10 module. The front panel of the module includes four three-position hand/off/auto switches that permit the user to force an output to an ON or OFF state, or to allow the network to select the output state. The switches force the output low (0 position) or high (1 position), or allows the application program to select the output state (center network position). A separate front panel LED is provided for each output. The four hand/off/auto switches control the outputs of the DO-10 as long as the module is powered, regardless of the software state of the module. The four status LEDs will track the state of the outputs only if the application program is running and the module is in the configured state. The status LEDs will not fuction if the module is in an unconfigured state.

7-2 Module

Installing the DO-10 Digital Output

Page 81

Network Access Jack; Use With Echelon PCC-10 Cable Model 78303

™ int o E nP Lo ce fa r te In

DO-10 m c U L us ®

LonPoint Interface Model and Software Revision

MODEL 41200 9745 LISTED 178K ENERGY MANAGEMENT SW VERSION 3.0 EQUIPMENT SUBASSEMBLY ID NUMBER OUTPUT: 0-12VDC, 25mA EACH

1234 1

1

2 3 4

0

DO-10 MODEL 41200

DO-10 MODEL 41200

1 2 3 4

ID NUMBER

ID NUMBER

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number Service LED Service Switch

Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing Hand/Off/Auto Switch 1 ON (Hand) 0 OFF (Off) Network Controlled (Auto) 1 Digital Output 1 Switch 2 Digital Output 2 Switch 3 Digital Output 3 Switch 4 Digital Output 4 Switch

Digital Output Status LEDs 1 Digital Output 1 LED 2 Digital Output 2 LED 3 Digital Output 3 LED 4 Digital Output 4 LED

Figure 7.1 LonPoint DO-10 Digital Output Module - Front Panel

LonPoint Hardware Guide

7-3

Page 82

The DO-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections to the DO-10 module are presented in table 7.1. Specifications for the DO-10 module are shown in table 7.2.

Table 7.1 DO-10 Digital Output Module Wiring Connections Screw Terminal 1 and 2

Wiring Connection Incoming network wiring, TP/FT-10 channel, polarityinsensitive Outgoing network wiring, TP/FT-10 channel, polarityinsensitive Unused Incoming power wiring, 16-30VAC or VDC, 3.2 to 6.5VA depending on load maximum, polarity-insensitive. If using DC power, it is good practice to maintain continuity of the power polarity throughout the network. Terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. + output of digital output 1 - output of digital output 1 (common to all outputs) + output of digital output 2 - output of digital output 2 (common to all outputs) Unused + output of digital output 3 - output of digital output 3 (common to all outputs) + output of digital output 4 - output of digital output 4 (common to all outputs)

3 and 4 5 6 and 7

10 11 12 13 14 15 16 17 18

Table 7.2 LonPoint DO-10 Digital Output Module Specifications Function Processor/memory Service function I/O

I/O isolation Transceiver type Network connector Input power Mounting Temperature Humidity

7-4 Module

Description Neuron 3150 Chip, 10MHz, 56K flash memory Recessed service switch, service LED, power/wink LED. Dual tear-off bar-code Neuron ID self-adhesive tag for application to red-line drawings in the field 4 digital outputs, 0-12V, 100mA source/sink maximum on any one output, 110mA source/400mA sink combined; separate status LEDs for each output; separate hand/off/auto front panel DIP switches for each output 100V, transformer isolation. Outputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility with link power channel Phone plug connector accessible from front panel 16-30VAC or VDC @ 3.2 to 6.5VA depending on load, internally isolated power supply Type 1 or Type 1D Base Plate -40 to +85°C, operating and non-operating 10 to 95% RH @ 50°C

Installing the DO-10 Digital Output

Page 83

EMI Safety agency Function Blocks Software Configuration

FCC A, CE Mark UL 916 Node object (1), digital output open-loop actuator objects (4), digital encoder controller objects (2), analog function block controller objects (2), type translators (6) Wide variety of LONMARK Standard Configuration Parameter Types supported by direct memory read/write function of LNS compatible network management tools

DO-10 Module Software Settings The software settings of the DO-10 module are described in the LonPoint Application and Plug-In Guide

Installing the DO-10 Module Installation of the DO-10 module involves the following steps: 1. Ensure that the Base Plate has been wired and installed correctly, and is securely fastened to the electrical enclosure. 2. Check for continuity on all network and power wiring. Ensure that the correct actuators are connected to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the DO-10 module into Base Plate by aligning the network access jack on the DO-10 with the arrow head on the Base Plate (the arrow should point in the direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector. 5. The DO-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off. The hand/off/auto switches will not function unless the DO-10 module is powered. 6. Securely attach the DO-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in/0.5Nm torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the DO-10 module. 8. See Troubleshooting for assistance with improper DO-10 module operation.

LonPoint Hardware Guide

7-5

Page 84

7-6 Module

Installing the DO-10 Digital Output