The text of a manual · part 10 of 16
LonPoint Module Hardware and Installation User's Guide, Version 2.0: CH6 - Installing the DIO-10 Digital Input/ Output Modules
Pages 73 to 78 of 115, from LonPoint Module Hardware and Installation User's Guide, Version 2.0
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Echelon LPR-14
Page 73
6 Installing the DIO-10 Digital Input/Output Modules
This chapter describes the process of installing the Model 41500 DIO-10 Digital Input/Output Modules.
Installing the DIO-10 Input/Output Modules
6-1
Page 74
LonPoint DIO-10 Digital Input/Output Modules The front panel is shown in figure 6.1. There are no user-configured jumper blocks on the DIO-10 module. A separate front panel LED is provided for each input, and a Hand/Off/Auto switch and LED are provided for each output. The four hand/off/auto switches control the outputs of the DIO-10 as long as the module is powered, regardless of the software state of the module. The four status LEDs will track the state of the outputs only if the application program is running and the module is in the configured state. The status LEDs will not fuction if the module is in an unconfigured state.
Network Access Jack; Use With Echelon PCC-10 Cable Model 78303
HAND/OFF/AUTO Switches (manual) (network)
E
™ int o nP Lo ce fa r te In
LonPoint Interface Model and Software Revision
DIO-10m c UL us ®
MODEL 41500 9820 LISTED 178K SW VERSION 3.0 ENERGY MANAGEMENT ID NUMBER EQUIPMNT SUBASMBLY OUTPUT: 30V AC/DC, 2A INPUT: 0-32VDC
1
2
1 2 3 4
1 2 1 2
DIO-10 MODEL 41500
ID NUMBER
DIO-10 MODEL 41500
ID NUMBER
Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number
Service LED Service Switch
Digital Input Status LEDs 1 Digital Input 1 LED 2 Digital Input 2 LED 1 Digital Input 1 LED 2 Digital Input 2 LED
Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing
Figure 11.1 LonPoint DIO-10 Digital Input/Output Module - Front Panel
6-2 Modules
Installing the DIO-10 Input/Output
Page 75
The DIO-10 module is intalled in a Type 1 or Type 1D Base Plate. Wiring connections to the DIO-10 module are presented in table 6.1. Specifications for the DIO-10 module are shown in table 6.4.
Table 6.1 DIO-10 Digital Input/Output Module Wiring Connections Screw Terminal 1 and 2 3 and 4 5 6 and 7
10 11 12 13 14 15 16 17 18
Wiring Connection Incoming network wiring, TP/FT-10 channel, polarityinsensitive Outgoing network wiring, TP/FT-10 channel, polarityinsensitive Unused Incoming power wiring, 16-30VAC or VDC, 4.75VA, polarityinsensitive. If using DC power, it is good practice to maintain continuity of the power polarity throughout the network: terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. Output 1 relay wiper Output 1 normally closed output Output 1 normally open output Output 2 relay wiper Output 2 normally closed output Output 2 normally open input - input of digital input 1 + input of digital input common - input of digital input 2
DIO-10 Module Digital Inputs The following table lists the input switching levels of the DIO-10 Module digital inputs (over full operational range).
Table 6.2 DIO-10 Module Input Switching Levels Input Range 0 - 5, dry contacts 0 - 12 V 0 - 24 V 0 - 31 V
Maximum Positive Threshold Voltage (Vpmax) [V] 3.85 9.48 19.28 24.90
Installing the DIO-10 Input/Output Modules
Minimum Negative Threshold Voltage (Vnmin) [V] 1.35 3.15 6.28 8.08
Minimum Hysterisis (Vhmin) [V] 0.40 0.93 1.86 2.39
6-3
Page 76
Both digital inputs have internal pull-up resistors (2.43 K ) connected to 5V through a diode. This pull-up resistor allows the use of low-cost (nonnoble, metal-plated) contacts in external dry contacts (relays). The diode prevents current flow through the pull-up resistor to the power supply when the input is not a dry contact but a logic voltage above 5V. When the input voltage is below 5V, the external electronics must sink current. When the input voltage is above 5V, then the diode prevents the flow of current through the pull-up resistor. For inputs above 5V, a separate protection diode is forward biased through a 21.5K resistor. Table 6.3 details the sink (-)/source (+) currents required of the external electronics at various input voltages.
Table 6.3 Sink/Source Currents
Input Voltage 0V 3V 5V 10V 20V 32V
Input Current -1.7mA -0.5mA 0mA +0.2mA +0.65mA +1.21mA
Note: The two inputs on the DIO-10 are isolated from the power supply and from the network, but are not isolated from each other. If the installation requires that the inputs be isolated from each other, additional LonPoint modules should be used.
Table 6.4 LonPoint DI-10 Digital Input Module Specifications Function Processor/memory Service function I/O
I/O isolation Transceiver type Network connector Input power Mounting Temperature
6-4 Modules
Description Neuron 3150 Chip, 10MHz, 56K flash memory Recessed service switch, service LED, power/wink LED. Dual tear-off bar-code Neuron ID self-adhesive tag for application to red-line drawings in the field 2 digital inputs, 5,12,24,31V or dry contact. Up to 20kHz frequency measurement; 2 relay outputs (each has one Form A and one Form B contact with a common wiper) rated at 2A continuous 6A surge at 30 VAC or 24VDC. Separate status LEDs for each input 100V, transformer isolation. Inputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility with link power channel Phone plug connector accessible from front panel 16-30VAC or VDC @ 4.75VA, internally isolated power supply Type 1 or Type 1D Base Plate -40 to +85°C, operating and non-operating
Installing the DIO-10 Input/Output
Page 77
DIO-10 Digital Input/Output Module Software Settings The software settings of the DIO-10 are described in the LonPoint Application and Plug-In Guide.
DIO-10 Digital Input/Output Module Firmware The DIO-10 firmware contains the following function blocks: Digital Input/Counter function block (2), Digital Output function blocks (2), Analog function block (2), Digital Encoder function block (2), Type Translator function block (4), Node Object (1). See the LonPoint Application and Plug-In Guide for details on those function blocks.
Installing the DIO-10 Digital Input/Output Module Installation of the DIO-10 module involves the following steps. 1. Ensure that the Type 1 or Type 1D Base Plate has been wired and installed correctly. 2. Check for continuity on all network and power wiring. Ensure that the correct sensors are connected to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the DIO-10 module into the Base Plate by aligning the network access jack on the module with the arrow head on the Base Plate (the arrow should point in the direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector. 5. The DIO-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off. 6. Securely attach the DIO-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in. (0.5Nm) torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the DIO-10 module. 8. See Troubleshooting for assistance with improper DIO-10 module operation.
Installing the DIO-10 Input/Output Modules
6-5
Page 78
6-6 Modules
Installing the DIO-10 Input/Output