Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeEnglishEspañolContact

The text of a manual · part 9 of 16

LonPoint Module Hardware and Installation User's Guide, Version 2.0: CH5 - Installing the DI-10 Digital Input Module

Pages 69 to 72 of 115, from LonPoint Module Hardware and Installation User's Guide, Version 2.0

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Echelon LPR-14

Page 69

5 Installing the DI-10 Digital Input Module

This chapter describes the process of installing the Model 41100 DI-10 Digital Input Module.

LonPoint Hardware Guide

5-1

Page 70

LonPoint DI-10 Digital Input Module The front panel of the DI-10 module is shown in figure 5.1. There are no userconfigured jumper blocks or other adjustable controls on the DI-10 module. A separate front panel LED is provided for each intput.

Network Access Jack; Use With Echelon PCC-10 Cable Model 78303

E nP o t oin

™

I e nt rfa ce

DI-10 m c UL us ®

L

LonPoint Interface Model and Software Revision

MODEL 41100 972 LISTED 178K SW VERSION 3.0 ENERGY MANAGEMENT EQUIPMENT SUBASSEMBLY ID NUMBER INPUT: 0-32VDC

1 2 3 4

DI-10 MODEL 41100

ID NUMBER

DI-10 MODEL 41100

ID NUMBER

Peel-Off Code 39 Format Bar Code of LonPoint Interface Neuron Chip ID Number Service LED Service Switch

Digital Input Status LEDs Digital Input 1 LED 1 Digital Input 2 LED 2 Digital Input 3 LED 3 Digital Input 4 LED 4

Power/Wink LED: Power ON: Illuminated Continuously Wink: Flashing

Figure 5.1 LonPoint DI-10 Digital Input Module - Front Panel

5-2

Installing the DI-10 Digital Input Module

Page 71

The DI-10 module is installed in a Type 1 or Type 1D Base Plate. Wiring connections to the DI-10 module are presented in table 5.1. Specifications for the DI-10 module are shown in table 5-2.

Table 5.1 DI-10 Digital Input Module Wiring Connections Screw Terminal 1 and 2

Wiring Connection Incoming network wiring, TP/FT-10 channel, polarityinsensitive Outgoing network wiring, TP/FT-10 channel, polarityinsensitive Unused Incoming power wiring, 16-30VAC or VDC, 2.2VA, polarityinsensitive. If using DC power, it is good practice to maintain continuity of the power polarity throughout the network: terminals 6 and 8 should be the same polarity, and terminals 7 and 9 should be the same polarity. + input of digital input 1 - input of digital input 1 (common to all inputs) + input of digital input 2 - input of digital input 2 (common to all inputs) Unused + input of digital input 3 - input of digital input 3 (common to all inputs) + input of digital input 4 - input of digital input 4 (common to all inputs)

3 and 4 5 6 and 7

10 11 12 13 14 15 16 17 18

Table 5.2 LonPoint DI-10 Digital Input Module Specifications Function Processor/memory Service function I/O I/O isolation Transceiver type Network connector Input power Mounting Temperature

LonPoint Hardware Guide

Description Neuron 3150 Chip, 10MHz, 56K flash memory Recessed service switch, service LED, power/wink LED. Dual tear-off bar-code Neuron ID self-adhesive tag for application to red-line drawings in the field 4 digital inputs, 0-32VDC or dry contact; 2.5V input logic threshold; separate status LEDs for each input 100V, transformer isolation. Inputs are isolated from the input power and the network but not from each other. FTT-10A with blocking capacitors for compatibility with link power channel Phone plug connector accessible from front panel 16-30VAC or VDC @ 2.2VA, internally isolated power supply Type 1 or Type 1D Base Plate -40 to +85°C, operating and non-operating

5-3

Page 72

Humidity EMI Safety agency Function Blocks Software Configuration

10 to 95% RH @ 50°C FCC A, CE Mark UL 916 Node object (1), digital input open-loop sensor objects (4), digital encoder controller objects (2), analog function block controller objects (4), type translators (6) Wide variety of LONMARK Standard Configuration Parameter Types supported by direct memory read/write function of LNS compatible network management tools

DI-10 Module Software Settings The software settings of the DI-10 module are described in the LonPoint Application and Plug-In Guide.

Installing the DI-10 Module Installation of the DI-10 module involves the following steps: 1. Ensure that the Type 1 or Type 1D Base Plate has been wired and installed correctly. 2. Check for continuity on all network and power wiring. Ensure that the correct sensors are connected to the correct Base Plate I/O terminals. 3. Make certain that all network channels are terminated with the correct number and type of Terminator. 4. Insert the DI-10 module into the Base Plate by aligning the network access jack on the DI-10 with the arrow head on the Base Plate (the arrow should point in the direction of the jack), and then pressing firmly to ensure that the module is properly seated in its mating Base Plate connector. 5. The DI-10 module can be hot-plugged: there is no need to disconnect power when installing the module. If power is present then the Power LED will illuminate continuously. If power is not present then the Power LED will remain off. 6. Securely attach the DI-10 module to the Base Plate by screwing the two Echelon 205-0130-01 screws (8-32 [M8], 3/8” [9.5mm]) into the threaded inserts in the Base Plate. Use approximately 4 lbs. in. (0.5Nm) torque on the screws. 7. Follow the node configuration procedure described in the LonPoint Application and Plug-In Guide to configure the software in the DI-10 module. 8. See Troubleshooting for assistance with improper DI-10 module operation.

5-4

Installing the DI-10 Digital Input Module