Page 41

INSTALLATION

3 Double Power Supply Installation

2 nd

Power Unit max. 2 m.

120 Ohm

VSGND2

1

DS41

4

#x (up to 31)

2 7

! DS41

4 2

1

#1

DS41

4 2

CHASSIS

1

7

#0

7

14 MX4000

13 12 11

VSGND1 max. 1200 m.

TX485TX485+ SGND

MULTIDROP MULTIDROP + MULTIDROP GND SHIELD

120 Ohm st

1 Power Unit

Figure 25 - Double supply single cable (power+multidrop line+shield)

33

Page 42

MX4000

3 Observe the following rules cabling the peripheral devices: • • •

• •

• •

• • •

34

Minimum wire size 24AWG The power line has to be used only for bar code readers and their accessories (i. e. photocells). Wire dimensioning must be selected and checked in order to avoid voltage drops greater than 0.8 Volts. st MULTIDROP GND is connected to GND1 (1 Power Unit) to avoid excessive 485 common mode voltage (485 driver references are to be connected together to avoid failure). All scanner SGNDs are floating since they are internally connected to GND, (if connected together, ground loop problems can occur). Then GND1 and GND2 nd (2 Power Unit) must be connected together with MULTIDROP GND using the third wire inside multidrop cable. GND2 should not be connected to earth to avoid possible ground loop problems if GND1 is also connected. This situation could result in failure or unreliable multidrop behaviour. If GND2 cannot be disconnected from earth, you must not wire GND2 to MULTIDROP GND. However this is not completely reliable since the 485 reference for the second group of scanner(s) is connected to the first group only through the earth connection depends on the quality of earth ground. Cable Shield connected only to Multiplexer earth. We suggest using the single cable layout shown in Figure 25 (multidrop+power). If not possible the separate DC voltage Power Cable (VS-GND) must be handled as a signal cable (do not put it together with other power cables) and must lie down as near as possible to the multidrop cable (avoiding wide loops between them). Scanner’s chassis may be connected to earth (it isn’t mandatory). The maximum distance, end to end, of the multidrop line should not exceed 1200 meters. 120 Ohm termination resistance required only for baud rates higher than 19200.

Page 43

INSTALLATION

3 Multiple Power Supply Installation max. 2 m.

~

Vdc

1 ~

~

CHASSIS

Vdc

DS41

4

#x

2

(up to 31)

7

DS41

4

#1

2

1

7

Vdc

DS41

4

#0

2

1

7

120 Ohm max. 1200 m.

TX485TX485+ SGND three wires + shield 14 MULTIDROP MX4000

13 12 11

MULTIDROP + MULTIDROP GND SHIELD

120 Ohm Figure 26 – Three-wire shielded multidrop cable

The multiple power supply installation is valid for both opto-isolated and non-isolated RS485 interfaces.

35

Page 44

MX4000

3 Observe the following rules when cabling the peripheral devices: • • • • • •

3.8

Minimum wire size 24AWG. MULTIDROP GND must be connected only to Power supply GND to avoid excessive 485 common mode voltage (485 driver references are to be connected together to avoid failure). Cable Shield connected only to Multiplexer earth. Scanner’s chassis may be connected to earth (it isn’t mandatory). The maximum distance, end to end, of the multidrop line should not exceed 1200 meters. 120 Ohm termination resistance required only for baud rates higher than 19200.

CONNECTIONS TO AUXILIARY INTERFACE

The auxiliary serial interface is used exclusively for RS232 point to point connections. The parameters relative to the auxiliary interface (baud rate, data bits, etc.) can be defined using the Winhost utility program or Keyboard Mode programming or Host Mode programming. For more details refer to the section "Auxiliary Interface Menu" in the Help On Line of the WINHOST utility program. 1

2

6

3

7

4

8

5

9

Figure 27 - 9-pin male connector

Connection to the auxiliary interface is provided through the standard RS232 9-pin male connector with the following pinout: 9-pin connector pinout

36

Pin

Name

Function

1 2 3 4 5 6 7 8 9

N.C. RXAUX TXAUX N.C. SGND N.C. RTSAUX CTSAUX N.C.

not connected auxiliary input auxiliary output not connected signal ground not connected auxiliary handshake auxiliary handshake not connected

Page 45

INSTALLATION

3

MX4000 AUX 9 pin D-sub

USER INTERFACE 2

RXAUX

3

TXAUX

8

CTSAUX

7

RTSAUX

5

SGND

TXD RXD DTR DCD SGND

MAXIMUM LENGTH: 15 m RTS/CTS HARDWARE HANDSHAKING ENABLED Figure 28 - RS232 auxiliary interface connections

The RTSAUX and CTSAUX signals control data transmission and synchronize the connected devices. If the RTS/CTS handshaking protocol is enabled, the MX4000 activates the RTSAUX output to indicate a message is to be transmitted. The receiving unit activates the CTSAUX input to enable the transmission.

3.9 3.9.1

CONNECTIONS TO I/O Inputs

The signals relative to these sensors must be connected to the MX4000 via the proper internal connector J4 (see Figure 12), respecting the following connections: Input signals (J4) Pin

Name

Function

7 8 9 10 11 12 13 14

IN1+ IN1IN1 GND IN1 VS IN2+ IN2IN2 GND IN2 VS input 1 (+) input 1 (-) input 1 signal ground input 1 operating voltage input 2 (+) input 2 (-) input 2 signal ground input 2 operating voltage

An input signal can be driven by sensors with NPN or PNP output and is optoisolated to assure maximum disturbance immunity.

37

Page 46

MX4000

3 The electrical features are: maximum voltage applicable at input: 30 V. maximum current: 25 mA.

IN1 VS and IN2 VS and their relative ground references (IN1 GND, IN2 GND) supply power to the input signals from the MX4000 with the following characteristics: typical voltage: 12 V. maximum current: 50 mA. A debounce filter is implemented on both inputs: the nominal value of the delay is 5 ms. USER INTERFACE

MX4000

J4

10,14

IN VS

7,11

IN+

8,12

IN-

9,13

IN GND

V

Signal Ground

IN VS = IN1 VS or IN2 VS IN+ = IN1+ or IN2+ IN- = IN1- or IN2IN GND = IN1 GND or IN2 GND Figure 29 - Input connections with NPN input interface

38

Page 47

INSTALLATION

3 MX4000

J4

USER INTERFACE 10,14

IN VS

7,11

IN+

8,12

IN-

9,13

IN GND

V Signal

IN VS = IN1 VS or IN2 VS IN+ = IN1+ or IN2+ IN- = IN1- or IN2IN GND = IN1 GND or IN2 GND

Figure 30 - Input connections with PNP user interface

3.9.2

Outputs

The following pins are present on the connector J4 (see Figure 12) of the MX4000: Output signals Pin

Name

Function

1 2 3 4 5 6

OUT1+ OUT1OUT2+ OUT2OUT3+ OUT3- output1 (+) output1 (-) output2 (+) output2 (-) output3 (+) 1 output3 (-)

The electrical features are: VCE max. Collector current max. VCE saturation

40 Vdc 40 mA continuous; 130 mA pulsed 1V at 10 mA

39

Page 48

MX4000

3

MX4000

USER INTERFACE Vext 40 Vdc max

J4

1, 3, 5

SIGNAL+

2, 4, 6

SIGNAL-

SIGNAL+ = OUT1+, OUT2+ or OUT3+ SIGNAL- = OUT1-, OUT2- or OUT3-

Figure 31 - Open collector output connection

MX4000

USER INTERFACE Vext 40 Vdc max

J4

1, 3, 5

SIGNAL+

2, 4, 6

SIGNAL-

SIGNAL+ = OUT1+, OUT2+ or OUT3+ SIGNAL- = OUT1-, OUT2- or OUT3Figure 32 - Open emitter output connection

40

Page 49

INSTALLATION

3

3.10 TYPICAL LAYOUTS The typical layouts for MX4000 depend on the model and therefore the type of system in which it is installed. There are many possibilities, some of which are shown in the following paragraphs.

3.10.1

MX4000 Standard Serial Interface Layout

The MX4000 is connected to a Host using one of the Standard Serial Interfaces: RS232, RS485 Half-Duplex or Full-Duplex, or 20 mA C.L. Each scanner or other peripheral device, is connected to the MX4000 using the RS485 Multidrop line.

RS485 Aux. RS232 Control Station

Main/Bus MX4000

Host

Figure 33 - MX4000 standard serial interface multistation layout

41

Page 50

MX4000

3

Aux. RS232 Control Station

Main/Bus MX4000 Host Figure 34 - MX4000 standard serial interface multi-sided layout

3.10.2

MX4000 Profibus DP Layout

PROFIBUS DP Master

Profibus DP Slave node #1

Profibus DP Slave node #n

MX4000 Profibus DP Slave node #2

Figure 35 - MX4000 Profibus DP layout

42