Page 51

INSTALLATION

3.10.3

3

MX4000 InterBus-S Layout HOST (Master)

Local bus (max 10m) max 1,5

Remote bus (max 12,8 km)

max 1,5

Installation remote bus (max 50m)

max 50m Remote bus segment

MX4000 max. 400m

Figure 36 - MX4000 InterBus-S layout

43

Page 52

MX4000

4

4 TECHNICAL FEATURES ELECTRICAL FEATURES INPUT POWER Supply voltage

10 - 30 Vdc

Power consumption max.

6W

SERIAL INTERFACES MAIN

RS232 RS485 Full-Duplex RS485 Half-Duplex 20 mA C. L.

AUXILIARY

RS232

BAUD RATES Main

1200 to 115200

Auxiliary

1200 to 19200

Multidrop

1200 to 57600

CONTROL INPUTS IN1

(optocoupled NPN or PNP)

IN2

(optocoupled NPN or PNP)

Voltage max.

30 Vdc

Input current max.

25 mA

CONTROL OUTPUTS OUT1, OUT2, OUT3

(open emitter, open collector)

VCE max.

40 Vdc

Collector current max.

40 mA continuous; 130 mA pulsed

VCE saturation

1V at 10 mA

USER INTERFACE LED indicators

44 power on; data reception - mdrop, main; data transmission - mdrop, main; inputs - Ext trig1, Ext trig2

Page 53

TECHNICAL FEATURES

4

SOFTWARE FEATURES CONFIGURATION MODES

• • •

PARAMETER STORAGE

Non-volatile internal EEPROM through menus using WINHOST utility through KEYBOARD MODE receiving commands from one of the serial ports (HOST MODE)

ENVIRONMENTAL FEATURES Operating temperature (see Note) Storage temperature Humidity max. Vibration resistance Shock resistance

0 to 55 °C -20 to 70 °C 90% non condensing IEC 68-2-6 test FC 1.5 mm; 10 to 55 Hz; 2 hours on each axis IEC 68-2-27 test EA 30G; 11 ms; 3 shocks up and down on each axis

PHYSICAL FEATURES Mechanical dimensions Weight

240 x 200 x 66 mm approx. 1.915 Kg. (with Profibus board)

45

Page 54

MX4000

A

APPENDIX A

DATA FORMATTING

In the Standard Application Program, MX4000 collects data from a series of scanners and sends them to the Host. This appendix describes how these data are formatted towards the Host and on the MX4000 display.

DATA FORMATTING TOWARDS THE HOST Time Info Disabled When the “Time Info” option is disabled, the address of the scanner (an ASCII number from 0 to 31) and the ASCII space character (20H) are added to the data from the scanner. The data format is as follows: <scanner address> <(20H)> <scanner data> or in the case of a fragmented data string from the scanner: <scanner address> <&> <scanner data>...<scanner address> <(20H)> <scanner data> In the Standard Serial Interface case, the scanner address is represented by two decimal numbers: Example:

From scanner 27 the data string “ABCD” is collected.

MX4000 sends the following string to the Host: 0x32 0x37 0x20 0x41 0x42 0x43 0x44 In the AnyBus or Profibus cases, the scanner address is represented by a unique binary byte: From the example above the MX4000 sends the following string to the Host: 0x1B 0x20 0x41 0x42 0x43 0x44

46

Page 55

DATA FORMATTING

A

Time Info Enabled When the “Time Info” option is enabled, in addition to the formatting previously described, the elapsed time from the last power-up or reset is added to the data string. The data format is as follows: <scanner address> <Time Info> <(20H)> <scanner data> In the case of a fragmented data string from the scanner: <scanner address> <Time Info> <&> <scanner data>... <scanner address> <Time Info> <(20H)> <scanner data> The “Time Info” is formatted as follows: +hhmmss where hh, mm, and ss are respectively the hours, minutes and seconds elapsed. The scanner address is represented as before depending on the interface used. The following example refers to the Standard Serial Interface. Example:

From scanner 27 the data string “ABCD” is collected 1:20:45 from the last power-up.

MX4000 sends the following string to the Host: 0x32 0x37 0x2B 0x30 0x31 0x32 0x30 0x34 0x35 0x20 0x41 0x42 0x43 0x44

Header-Terminator Selection For Standard Serial Interface cases only, a “Header-Terminator” option can be selected. The format is as follows: <header> <scanner address> <(20H)> <scanner data> <terminator> None STX-ETX CR-LF CR

Header STX -

Terminator ETX CR/LF CR

47

Page 56

MX4000

A

DATA FORMATTING ON THE MX4000 DISPLAY To display the collected data on the MX4000 LCD, the “Echo On Display” option must be enabled; otherwise the display shows a fixed message of the software version. The data displayed on the MX4000 LCD is similar to that sent to the Host with 2 important differences: •

The scanner address is always displayed as an ASCII number independently from the type of interface being used, i.e. Standard Serial, AnyBus, etc.

•

The non-printable ASCII characters (i.e. 00H to 1FH) collected from the scanners are not displayed.

Example:

From scanner 27 the data string “0x02 0x41 0x42 0x43 0x44” is collected, (Time Info disabled).

MX4000 sends the following string to the display: “27 ABCD” In this case, 0x02 corresponds to the non-printable ASCII character represented by STX and is not displayed on the MX4000. MX4000 Header-Terminator formatting is not displayed.

48

Page 57

We

DATALOGIC S.p.A. Via Candini, 2 40012 - Lippo di Calderara Bologna - Italy declare under our sole responsibility that the product(s) MX4000-XXXX, Multiplexer Data Collection to which this declaration relates is in conformity with the following standards or other normative documents EN 55022, August 1994:

LIMITS AND METHODS OF MEASUREMENTS OF RADIO DISTURBANCE CHARACTERISTICS OF INFORMATION TECHNOLOGY EQUIPMENT (ITE)

EN 50082-2, March 1995:

ELECTROMAGNETIC COMPATIBILITY. GENERIC IMMUNITY STANDARD. PART 2: INDUSTRIAL ENVIRONMENT

Following the provision of the Directive(s): 89/336 CEE AND SUCCESSIVE AMENDMENTS: 92/31 CEE; 93/68 CEE

Lippo di Calderara, 02.06.1998 Ruggero Cacioppo Quality Assurance Supervisor