The text of a manual · part 3 of 4

DS1100 Installation Manual, pages 19 to 27

Pages 19 to 27 of 36

The original document is the PDF (3.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Datalogic DS-1100

Page 19

INSTALLATION

2

For this interface type, the Multidrop Address must also be set via serial channel by the WinHost utility or by ESC sequences. Figure 7 shows an example of a multidrop configuration between a Multiplexer and DS1100 scanners. 120 Ohm max 2 m DS1100 #x (up to 31)

max 1200 m

DS1100 #1 RTX485 +

DS1100 #0

RTX485 SGND

Three wires + shield RTX485 + RTX485 MULTIPLEXER RS485 REF SHIELD

120 Ohm

Figure 7 - DS1100 Multidrop connection to a Multiplexer

9

Page 20

DS1100

2

2.3.3

Auxiliary Interface - RS232

The auxiliary serial interface is used exclusively for RS232 point-to-point connections. It is also used for configuring the DS1100. The parameters relative to the auxiliary interface (baud rate, data bits, etc.) can be defined using the Winhost utility program or "Host Mode Programming", installed from the diskette. The following pins of the 25-pin connector are used to connect the RS232 auxiliary interface: Pin

Name

Function

3, 20 2, 21 7

RXAUX TXAUX SGND received data transmitted data signal ground

DS1100

USER INTERFACE 3/20

RXAUX

2/21

TXAUX

7

SGND

TXD RXD

SGND

Figure 8 - RS232 auxiliary interface connections

10

Page 21

INSTALLATION

2.3.4

2

Inputs

The inputs available on the connector supplied with the scanner are indicated below: Pin

Name

Function

18 19 12, 22

IN1 EXT TRIGGND input 1 external trigger I/O reference

The EXT TRIG input is used to connect the external trigger which tells the scanner to scan for a code. The active state of this input is selected in software. Refer to the Winhost Help On Line. The yellow LED (Figure A, 5) is on when EXT TRIG- is shorted to GND. This input is driven by an NPN type command. The connections are indicated in the following diagram:

DS1100

EXTERNAL TRIGGER

+5V

13/9

VS

19

EXT TRIG -

12/22

GND

V

47 K

Signal Ground

Figure 9 - External Trigger Input command

The general purpose input IN1, in the Standard Application Program, can be used to store the code verifier (see “Store Verifier Hw” in the WinHost Help On Line).

DS1100 +5V

USER INTERFACE 13/9

VS

18

IN1 -

12/22

GND

V

47 K

Ground

Figure 10 - IN1 - Input command

11

Page 22

DS1100

2

An anti-disturbance hardware filter is implemented on the External Trigger input (about 1 millisecond delay). An additional 15 ms (typical) delay can be implemented through a dedicated software parameter (refer to WinHost Help On Line).

2.3.5

Outputs

Two general purpose outputs are available. These outputs can only be connected as open collector configurations. The following pins are present on the 25-pin connector of the scanner: Pin 8 11 12, 22

Name OUT1+ OUT2+ GND

Function output 1 + output 2 + I/O reference

The meaning of the two outputs OUT1 and OUT2 can be defined by the user (No Read, Right or Wrong). Refer to the Winhost Help On Line. By default, OUT1 is associated with the No Read event, which activates when the code signaled by the external trigger is not decoded, and OUT2 is associated with the Right event, which activates when the code is correctly decoded. DS1100

USER INTERFACE Vext 50 Vdc max., 50 mA max.

8/11

+

12/22

GND

Ground

Figure 11 - DS1100 Output connections

These outputs are both level or pulse configurable.

12

Page 23

INSTALLATION

2.4

2

POSITIONING

The DS1100 scanner is able to decode barcode labels at a variety of angles, however significant angular distortion may degrade reading performance. When mounting the DS1100 take into consideration these three ideal label position angles: Pitch 0°, Skew 15° to 30° and Tilt 0°. Follow the suggestions for the best orientation: The Pitch angle is represented by the value P in Figure 12. Position the reader in order to minimize the Pitch angle. P

Figure 12 - Pitch Angle

The Skew angle is represented by the value S in Figure 13. Position the reader to assure about 15° for the Skew angle. This avoids the direct reflection of the laser light emitted by the DS1100. For the raster version, this angle refers to the most inclined or external raster line, so that all other raster lines assure more than 15° Skew. For the skew angle value with DS1100 90° versions, refer to par. 2.2.1.

S

Figure 13 - Skew angle

13

Page 24

DS1100

2

The Tilt angle is represented by the value T in Figure 14. Position the reader in order to minimize the Tilt angle. T

Figure 14 - Tilt angle

2.5

TYPICAL LAYOUTS

The following typical layouts refer to system hardware configurations. Dotted lines in the figures refer to optional hardware configurations within the particular layout. These layouts also require the correct setup of the software configuration parameters. Complete software configuration procedures can be found in the Guide To Rapid Configuration in the WinHost Help On Line.

14

Page 25

INSTALLATION

2.5.1

2

Point-to-Point

In this layout data is transmitted to the Host on the RS232 Auxiliary serial interface. The Local Echo communication mode must be enabled (default) See the Winhost Help On Line. When On-Line Operating mode is used, the scanner is activated by an External Trigger (photoelectric sensor) when the object enters its reading zone.

Host 1

DS1100

2

1

Auxiliary Serial Interface

2

External Trigger (for On-Line mode)

Figure 15 – Point to Point Layout

2.5.2

RS485 Master/Slave

The RS485 master/slave connection is used to collect data from several scanners to build a multi-point or a multi-sided reading system; there can be one master and up to 5 slaves connected together. The Slave scanners are connected together using the RS485 half-duplex main serial interface. Every slave scanner must have a multidrop address in the range 0-4. The master scanner is also connected to the Host on the RS232 auxiliary serial interface. The External Trigger signal is unique to the system; there is a single reading phase and a single message from the master scanner to the Host computer. It is necessary to bring the External Trigger signal to all the scanners. The main and auxiliary ports are connected as shown in the following figure.

15

Page 26

DS1100

2

Slave

2

1 DS1100

1

DS1100

Slave

DS1100

3

1 1

Auxiliary serial interface

2

RS485 Main serial interface

3

External Trigger

Master

Host

Figure 16 – RS485 Master/slave layout

NOTE

16

The auxiliary serial port of the slave scanners can be used in Local Echo communication mode to control any single scanner (visualize collected data) or to configure it using the WinHost utility or Host Mode programming procedure. The termination resistors of the RS485 bus must not be installed.

Page 27

INSTALLATION

2.5.3

2

Multiplexer

Each scanner is connected to a Multiplexer (for example MX4000) with the RS485 half-duplex main interface. 1

31

1

0

MX4000 2

Host

DS1100

3

2

DS1100

2

3

DS1100

3

1

Main interface

2

Auxiliary Interface (Local Echo)

3

External Trigger (for On-Line mode)

Figure 17 - Multiplexer layout

The auxiliary serial interface can be used in Local Echo mode to control any single scanner (visualize collected data) or to configure it using the WinHost utility or Host Mode programming procedure. When On-Line Operating mode is used, the scanner is activated by an External Trigger (photoelectric sensor) when the object enters its reading zone.

17