Page 307
Chapter 3 - Additional Features Status Interval Name Current Temperature Version Who am I Help Buzzer Current Protection Factory Default Reboot Restore Save Syslog Alarm Password
- Show the current status of outlet(s) - Sets/reads the power up interval - Names an outlet - Show current consumption for the entire unit - Sets/reads/reset the temperature - Displays version information - Display the current username - Shows this message - Turn buzzer on or off - Sets/reads the over current protection - Brings the unit to factory configuration - Reboot the units in chain - Restore the configuration in flash - Save configuration and status - Turn syslog on or off - Set alarm threshold for current - Set a password for the specific user
Some of these options require the outlet number (On, Off, Cycle, Lock, Unlock, Status), and others don't. In the first case, when the option is selected, the number of the outlet will be asked. The user can enter one or more outlets (separated by commas or dashes), or “all,” to apply the option to all the outlets. Following are examples of some things which can be done through this command.
Turning the IPDU outlet 2 off -----------------------------------------------------------------Cyclades Power Management Menu PowerPort: pm10 -----------------------------------------------------------------1. Exit 7. Status 13. Who Am I 19. Restore 2. On 8. Interval 14. Help 20. Save 3. Off 9. Name 15. Buzzer 21. Syslog 4. Cycle 10. Current 16. Current Protection 22. Alarm 5. Lock 11. Temperature 17. Factory Default 6. Unlock 12. Version 18. Reboot Please choose an option: 3 Outlet name or outlet number(? for help, m for main menu): 2
User Guide
307
Page 308
Chapter 3 - Additional Features Locking the outlets 1 to 3 When the outlet is locked, the previous status cannot be changed, until the outlet is unlocked. This means that if the outlet was on, it cannot be turned off and, if it was off, it cannot be turned on. -----------------------------------------------------------------Cyclades Power Management Menu PowerPort: pm10 -----------------------------------------------------------------1. Exit 7. Status 13. Who Am I 19. Restore 2. On 8. Interval 14. Help 20. Save 3. Off 9. Name 15. Buzzer 21. Syslog 4. Cycle 10. Current 16. Current Protection 22. Alarm 5. Lock 11. Temperature 17. Factory Default 6. Unlock 12. Version 18. Reboot Please choose an option: 5 Outlet name or outlet number(? for help, m for main menu): 1-3
Retrieving the status of the outlets -----------------------------------------------------------------Cyclades Power Management Menu PowerPort: pm10 -----------------------------------------------------------------1. Exit 7. Status 13. Who Am I 19. Restore 2. On 8. Interval 14. Help 20. Save 3. Off 9. Name 15. Buzzer 21. Syslog 4. Cycle 10. Current 16. Current Protection 22. Alarm 5. Lock 11. Temperature 17. Factory Default 6. Unlock 12. Version 18. Reboot Please choose an option: 7 Outlet name or outlet number(all for all, ? for help, m for main menu): 8 Outlet 8
User Guide
Name
Status Unlocked ON
Users
Interval (s) 0.50
308
Page 309
Chapter 3 - Additional Features pmCommand command Through pmCommand command, the administrator has access to other options beyond the menu options, because he will be accessing the IPDU itself. The administrator must have a good knowledge of the AlterPath PM command set to use it. There are two ways to use this command. If only the IPDU port is passed as an argument, it will appear in a prompt where the administrator can write the command. Otherwise, the arguments after the IPDU port will be considered the PM command. Syntax: pmCommand <IPDU port> [<command>] For example: [root@CAS root]# pmCommand 1 You're entering the "Power Management Prompt". To go back to the Console Server's command line type: exitPm [Cyclades - Power Management Prompt]# The following are examples of some things which can be done through this command.
Listing the commands available for the AlterPath PM [Cyclades - Power Management Prompt]# help on <outlet><cr> off <outlet><cr> cycle <outlet><cr> lock <outlet><cr> unlock <outlet><cr> status <outlet><cr> list<cr> exit<cr> passwd <user><cr> help<cr> current<cr> adduser <username><cr>
User Guide
--Turn <outlet> ON --Turn <outlet> OFF --Turn <outlet> OFF and back ON --Lock the current status of <outlet> --Unlock the current status of <outlet> --Show the current status of <outlet> --List users created and eventual outlets assigned --Exit session --Set a password for the specific user --Show supported commands --Show the instantaneous current consump tion for the entire unit --Add user to the DB (8 maximum users
309
Page 310
Chapter 3 - Additional Features allowed) deluser <username><cr> --Delete user from the DB assign <outlet><username><cr> --Assign <outlet> to a specific user name <outlet> <name><cr> --Name an outlet [Cyclades - Power Management Prompt]#
Cycling all the outlets [Cyclades - Power Management Prompt]# cycle all 1: Outlet power cycled. 2: Outlet power cycled. 3: Outlet power cycled. 4: Outlet power cycled. 5: Outlet power cycled. 6: Outlet power cycled. 7: Outlet power cycled. 8: Outlet power cycled. [Cyclades - Power Management Prompt]#
Unlocking the outlets 1, 5 and 8 [Cyclades - Power Management Prompt]# unlock 1, 5, 8 1: Outlet unlocked. 5: Outlet unlocked. 8: Outlet unlocked.
Turning the outlet off [Cyclades - Power Management Prompt]# off 2 2: Outlet turned off.
User Guide
310
Page 311
Chapter 3 - Additional Features AlterPath PM Firmware Upgrade It is possible to upgrade the firmware of the IPDU unit connected to any serial port of the Cyclades-TS. It is also possible to upgrade the whole daisy-chain of AlterPath PM units, since the unit(s) before the targeted one has firmware version 1.2.2 or greater.
Upgrade Process To upgrade the firmware of the PM units follow the steps below: Step 1: Download the firmware. The first step of the upgrade process will be the download of the new firmware. Cyclades provides a directory on its ftp site where it is possible to check for new firmwares and download them to the Cyclades-TS. It is recommended to download the new firmware to the /tmp directory because files in this directory are deleted during the boot process. Step 2: Run the pmfwupgrade application. After downloading it is necessary to call an application called pmfwupgrade. This application has the following syntax: # pmfwupgrade [-h] [-f] [-F] [-v] <serial port number>[:<unit number>] <filename> where :
-h = Show the help message and exit -f = The upgrade is done without asking any questions -F = The upgrade is done without waiting logical connection with the AlterPath PM. This is should be used after possible power failure during the upgrade process. -v = show messages about the status of the upgrade. <serial port number> = the serial port where the PM unit is connected [:<unit number>] = number of the PM unit when in daisy-chain. If is not used, all units in the serial port will have the firmware upgraded, when possible <filename> = complete path of the file that has the PM firmware (default: /tmp/ pmfirmware)
User Guide
311
Page 312
Chapter 3 - Additional Features Important! If the AlterPath PM unit is not configured with the default password, it will be necessary to inform it to the Cyclades-TS by editing the / etc/pm.cyclades file and changing the parameter admPasswd with the correct password.
The pmfwupgrade application will try to stop all the process that are using the serial port. Just type YES to proceed into the upgrade process. Another message will prompt asking for confirmation to proceed with the upgrade process. Type ‘y’ to upgrade the PM unit firmware.
Warning! Depending on the hardware version of the AlterPath PM, it is possible that all outlets completely powers off during the upgrade process. Make sure to shutdown all devices connected to them before starting the firmware upgrade process.
User Guide
312
Page 313
Chapter 3 - Additional Features Power Management from a Browser The Console Server Web server also supports power management. From a Web browser it is possible to check the status of all the IPDUs connected to the Console Server, as well as their outlets. If the user has Administration privileges, he can also perform the commands to turn on, turn off, cycle, lock and unlock the outlets. Step 1: Point your browser to the Console Server. In the address or location field of your browser type the Console Access Server’s IP address. For example: http://10.0.0.0 Step 2: Log in as root and type the Web root password configured by the Web server. This will take you to the Configuration and Administration page. Step 3: Select the Power Management link. This link is in the Administration section. The following page will appear:
Figure 34: Power Management page
User Guide
313
Page 314
Chapter 3 - Additional Features In the figure above, all the outlets are off (the light bulbs are off) and unlocked. For this status, there are two possible commands: turn it on and lock it. The following steps are examples of what can be done in this page. Step 4: Turn the outlet 1 on. Click on the “On 48:1” button. The following page will appear:
Figure 35: Power Management page after turning outlet 1 on After this operation, the outlet 1 was turned on (the light bulb is on), and now the administrator can turn it off and cycle this outlet.
Step 5: Lock outlet 1. Click on the “Lock 48:1” button. The following page will appear:
User Guide
314
Page 315
Chapter 3 - Additional Features
Figure 36: Power Management page after locking outlet 1 The padlock indicates that outlet 1 was locked. From this point, nothing can change the outlet status, until the outlet is unlocked.
User Guide
315
Page 316
Chapter 3 - Additional Features Menu Shell The menu shell feature allows a user to be presented with a menu in order to connect to a set of hosts as defined by the Cyclades-TS administrator. It can be used as an easy method for users to access servers on the LAN.
How to use Once the appropriate configurations are done the user will connect to the Cyclades-TS using a serial terminal . The user will then automatically receive a menu similar to that shown below: Welcome! 1) Sun server 2) Dell server 3) Linux server 4) Quit Option ==>
The user selects the option required to connect to the desired server or to exit the system.
How to configure Setting up the menu - from the command line Step 1: Type "menush_cfg" and use the options shown below to define the menu title and menu commands. ------------------------------------------------MenuShell Configuration Utility ------------------------------------------------Please choose from one of the following options: 1. Define Menu Title