For the Cyclades TS2000 and Avocent TS2000

Page 297

Chapter 3 - Additional Features Browser Method To configure Power Management to control IPDUs through theAdvanced Secure Console Port Server SSH Web interface: Step 1: Point your browser to the Console Server. In the address or location field of your browser type the Console Access Server’s IP address. For example: http://10.0.0.0 Step 2: Log in as root and type the Web root password configured by the Web server. This will take you to the Configuration and Administration page. Step 3: Select the Serial Ports link. Click on the Serial Ports link on the Link Panel to the left of the page or in the Configuration section of the page. This will take you to the Port Selection page. Step 4: Select the serial port where the IPDU is connected. After selecting the port, click the Connect button. Step 5: Click the PM8 profile button in the Wizard Section. This will automatically set the protocol to IPDU, the IPDU type to cyclades, and the number of outlets to 8. Step 6: Scroll down to the IPDU Section. Change the number of outlets and the user permissions in this section, if necessary. Step 7: Click the Submit button. If there are more IPDUs to be configured, repeat steps 4 to 7. Step 8: Select the port whose server has the power supply plugged into one or more IPDU outlets. After selecting the port, click the Submit button. Step 9: Configure the port as a Console Access Server. Read the Access Method section in Chapter 3 for details.

User Guide

297

Page 298

Chapter 3 - Additional Features Step 10: Scroll down to the Power Management Section Set the hotkey to access the power management menu and the outlet(s) the server is plugged into. Step 11: Click on the Submit button. Step 12: If there are more servers to be configured, repeat steps 8 to 11. Step 13: Make the changes effective. Click on the Administration > Run Configuration link, check the Serial Ports/ Ethernet/Static Routes box and click on the Activate Configuration button. Step 14: Click on the link Administration > Load/Save Configuration. Step 15: Click the Save Configuration to Flash button. The configuration was saved in flash.

Wizard Method Step 1: Bring up the wizard. At the command prompt, type the following to bring up the Power Management custom wizard: wiz --pm Screen 1 will appear. Screen 1: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** INSTRUCTIONS for using the Wizard: You can: 1) Enter the appropriate information for your system and press ENTER. Enter '#' if you want to deactivate that parameter or 2) Press ENTER if you are satisfied with the value User Guide

298

Page 299

Chapter 3 - Additional Features within the brackets [ ] and want to go on to the next parameter or 3) Press ESC if you want to exit. NOTE: For some parameters, if there is nothing within the brackets, it will continue to ask for a value. In that case, you must enter a valid value or # if you do not wish to configure the value. Press ENTER to continue... Screen 2: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** Current configuration: (The ones with the '#' means it's not activated.) all.protocol : ipdu all.pmtype : cyclades all.pmusers : # all.pmoutlet : # all.pmkey : ^p all.pmNumOfOutlets : 8 Set to defaults ? (y/n) [n] : Screen 3: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** ALL.PROTOCOL - The possible protocols are telnet (socket_ server), ssh1/ssh2 (socket_ssh), raw data (raw_data), or integrated power distributed unit (ipdu). all.protocol[ipdu] :

User Guide

299

Page 300

Chapter 3 - Additional Features ALL.PMTYPE - Name of the IPDU manufacturer. all.pmtype[cyclades] : Screen 4: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** ALL.PMUSERS - List of the outlets each user can access. (e.g. Joe: 1-3; Jane: 4,5,6) all.pmusers[#] :

ALL.PMOUTLET - The number of the outlet where the server is plugged. all.pmoutlet[#] :

Screen 5: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** ALL.PMKEY - The hot-key that identifies the power management command. all.pmkey[^p] :

ALL.PMNUMOFOUTLETS - The number of outlets you have on the AlterPath PM. all.pmNumOfOutlets[8] :

User Guide

300

Page 301

Chapter 3 - Additional Features Screen 6: *********************************************************** ********* C O N F I G U R A T I O N W I Z A R D ********* *********************************************************** Current configuration: (The ones with the '#' means it's not activated.) all.protocol : ipdu all.pmtype : cyclades all.pmusers : # all.pmoutlet : # all.pmkey : ^p all.pmNumOfOutlets : 8

Are these configuration(s) all correct (y/n) [n] :

How to Access the AlterPath PM regular menu from the Console Session Step 1: Open a console session. Open a telnet or ssh session for the serial port. Step 2: Access the IPDU regular menu. This should be done, for example, when the server crashes and it necessary to change the power status. Type the preconfigured hot-key. If the user does not have permission to access any outlet, the following message will appear, and you will return to the Console Session: It was impossible to start a Power Management Session You can't access any Power Management functionality. Please contact your Console Server Administrator.

User Guide

301

Page 302

Chapter 3 - Additional Features If the user does not have permission to access the outlet(s) of this server, but can access another outlet, the following message will appear: You cannot manage the outlet(s) of this server. Please enter the outlet(s) (or 'h' for help): The user should type the outlet(s) he wants to manage, before reaching the main menu. The main menu will appear only if the user has permission for this/these outlet(s). Typing 'h' will cause the session to show text explaining what to type, and 'l' will cause the PM session to be logged out, and the user to return to the Console Session. If the user has permission to access the outlet(s) of this server, these outlets will be managed by the PM session. Step 3: Regular Menu. This is the AlterPath PM regular menu: ------------------------------------------------------Cyclades Corporation - Power Management Utility ------------------------------------------------------1 - Exit 2 - On 3 - Off 4 - Cycle 5 - Lock 6 - Unlock 7 - Status 8 - Help 9 - Other Please choose an option: Table 16: AlterPath PM Regular Menu Options

User Guide

Option

Description

Exit

Exits the Power Management Session.

On

Turns the outlet on.

Off

Turns the outlet off.

Cycle

Turns the outlet off and back on.

Lock

Locks the current status of the outlet.

Unlock

Unlocks the current status of the outlet.

Status

Shows the current status of the outlet.

Other

Allows user to control other outlets.

302

Page 303

Chapter 3 - Additional Features Step 4: Check the status of the server's outlet or the outlet list. Type '7' and wait for the answer. For example: Please choose an option: 7 IPDU 1 Outlet 8: Outlet Status User 8 OFF NONE ------------------------------------------------------Cyclades Corporation - Power Management Utility ------------------------------------------------------1 - Exit 2 - On 3 - Off 4 - Cycle 5 - Lock 6 - Unlock 7 - Status 8 - Help 9 - Other Please choose an option: Step 5: Reboot the server. If the outlet(s) is/are locked, the user must unlock the outlet(s) first (option 6 Unlock). The Cycle command turns the power off for some seconds and the turn it on again. Type '4' and wait for the answer. For example: Please choose an option: 4 IPDU 1 Outlet 8: 8: Outlet power cycled. ------------------------------------------------------Cyclades Corporation - Power Management Utility ------------------------------------------------------1 - Exit 2 - On 3 - Off 4 - Cycle 5 - Lock 6 - Unlock 7 - Status 8 - Help 9 - Other Please choose an option:

User Guide

303

Page 304

Chapter 3 - Additional Features Step 6: Change the outlet list. If the user needs to access another outlet(s) which can be managed by him, the option 9 - Other should be used. For example: ------------------------------------------------------Cyclades Corporation - Power Management Utility ------------------------------------------------------1 - Exit 2 - On 3 - Off 4 - Cycle 5 - Lock 6 - Unlock 7 - Status 8 - Help 9 - Other Please choose an option: 9 Please enter the outlet(s) (or 'h' for help): 1.2 ------------------------------------------------------Cyclades Corporation - Power Management Utility ------------------------------------------------------1 - Exit 2 - On 3 - Off 4 - Cycle 5 - Lock 6 - Unlock 7 - Status 8 - Help 9 - Other Please choose an option: From this point, all the commands will be related to the 2nd outlet of the IPDU in the port 1.

Step 7: Return to the Console Session. The user can exit from the PM session and return to the Console Session in three ways: 1. Type the hot-key again, any time. 2. If the session is waiting for a menu option, type the option 1 - Exit. 3. If the session is waiting for the outlet, type 'l'. When the user leaves the PM session, the following message will appear: Exit from PM session

User Guide

304

Page 305

Chapter 3 - Additional Features Power Management for the Authorized Users (firmware version prior to 1.4.0) This section applies only for units not running firmware version 1.4.0 or greater. If you are running version 1.4.0 or greater please disregard this section, since it its not necessary to associate a special group for power management users. You just have to configure sXX.pmusers as described in “Port Slave Parameters Involved and Passed Values” on page 294. The administrator or any user that belongs to the pmusers group, can log onto the Console server itself, and have total control over all the IPDU outlets. An additional menu, with more options than the regular menu, is provided for the administrator and users contained in the pmusers group to manage any IPDU. There are two commands which can be used to manage the IPDU. The first one (pm) deals with menu options, while the second one (pmCommand) deals with the commands as they are sent to the IPDU, and requires more knowledge about the AlterPath-PM commands.

Adding an user of the pmusers group Only the root user and users belonging to the pmusers group can do power management by using the pm or pmCommand. To add an user as member of the pmusers group, log in as "root" and run the 'adduser' command with the following syntax: # adduser -g pmusers <username>

Changing the group of an already existing user It is also possible to change the group of an already existing user. In this example we will change the groups of the already existing users: “cyclades” and “test”. To do that follow the steps below: Step 1: Open the file /etc/group. To open this file, run the command: # vi /etc/group

Step 2: Addind the “cyclades” and “test” users to the pmusers group. To change the group of these users, look for the line that begins with “pmusers”. At the end of this line, just after the ´:´ character, insert the “cyclades” and “test”users. User Guide

305

Page 306

Chapter 3 - Additional Features webadmin::504:root pmusers::505:cyclades,test cyclades:x:506: test:x:507:

Step 3: Save the configuration. To save the changes done, run the command: # saveconf pm command There are two ways to use this command: menu interface or command line. The menu is reached by typing the following command, from the prompt: pm <IPDU port> For example (menu for the root user): -----------------------------------------------------------------Cyclades Corporation - Power Management Utility -----------------------------------------------------------------1. Exit 7. Status 13. Who Am I 19. Restore 2. On 8. Interval 14. Help 20. Save 3. Off 9. Name 15. Buzzer 21. Syslog 4. Cycle 10. Current 16. Current Protection 22. Alarm 5. Lock 11. Temperature 17. Factory Default 6. Unlock 12. Version 18. Reboot

Please choose an option: Exit On Off Cycle Lock Unlock

User Guide

- Exits the Power Management session - Turn outlet(s) ON - Turn outlet(s) OFF - Turn outlet(s) OFF and back ON - Lock the current status of outlet(s) - Unlock the current status of outlet(s)

306