Page 81
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Enter the desired Sample Interval. Enter 00:00:00 for continuous sampling. Continuous sampling is conducted at the programmed Sample Rate and Number of Samples to Average. If a Sample Interval is entered, repetitive sampling will occur where the V77 ADM-1 will sample for a specified period of time and then stop sampling for a specified time interval. Sample Interval is the time interval between the start of sampling periods. The length of time of sampling periods is determined by the Sampling Rate and the Number of Samples to Average. SAMPLE RATE Type “4” and <cr> to enter the Sample Rate menu. The V77 ADM-1 will respond: SAMPLE RATE Sample Rate
1S/sec
Enter Rate (1-4000S/sec) <cr>, or X to Exit:
Samples rates between 1 and 4000 samples/sec can be selected. The programmed Sample Rate is the sample rate for individual channels. The maximum sample rate for an individual channel is 4000 divided the number of active channels. For example, if there are eight active channels, the maximum individual channel sample rate is 500S/sec. The maximum sample rate, based on the number of active channels selected, is calculated automatically. If you try to exceed the maximum individual channel sample rate, your entry is ignored and the correct maximum rate displayed. NOTE: The number "4000" in the above menu is automatically reduced to the maximum individual channel sample rate based upon the number of active channels. NUMBER OF SAMPLES TO AVERAGE Type “5” and <cr> to enter the Samples To Average menu. The V77 ADM-1 will respond: NUMBER OF SAMPLES TO AVERAGE No. of Samples to Average..........10 Enter Samples (1-4000) <cr>, or X to Exit:
Enter the desired Number of Samples to Average.
69
Page 82
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
REPORTING SETUP Type “3” and <cr> to enter the Reporting Setup menu. The V77 ADM-1 will respond: REPORTING SETUP Reporting Method Report Start Time Report Interval Host Address Data Format Time Tag Terminating Character(s) Exit
1 2 3 4 5 6 7 X
Enter Selection:
REPORTING METHOD Type “1” and <cr> to enter the Reporting Method menu. The V77 ADM-1 will respond: SELECT REPORTING METHOD Reporting Method COMMAND Command Immediate(when Sample Available Schedule Exit
1 2 3 X
Enter Selection:
The V77 ADM-1 provides three Reporting Methods. These are Command (via data commands only), Immediate (upon exiting configuration), and Schedule (where reporting begins at a specified time). When Command Reporting Method is selected, the V77 ADM-1 will report data messages to the host module only when the RAn and RSn commands are issued. If the V77 ADM-1 receives an RAn (Read All Buffered Samples) command, all data messages currently stored in the buffer of the selected channel(s) are transmitted to the host-controller. Each time the V77 ADM-1 receives an RSn (Report a Single Sample if available) command, the oldest data message available is transmitted to the host-controller. The RAn and RSn commands may be issued to the V77 ADM-1 in any of the three Reporting Methods. When Immediate Reporting Method is selected, the V77 ADM-1 will report data messages when they are available. If no data message is available, no report is made. Reporting begins immediately after exiting the Configuration Main Menu
70
Page 83
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
When Schedule Reporting Method is selected, the V77 ADM-1 will begin reporting data messages at the programmed Report Start Time. The Report Start Time is programmable up to 24 hours in advance of the current (time-of-day) clock time. Data messages are stored in the buffer until the Report Start Time is reached at which time all buffered data messages are reported to the host module. Further reporting is based upon the selected Report Interval. NOTE: When a data message is requested by entering the RAn or RSn data commands, the Reporting and Sampling Methods currently programmed are overridden and the data message(s) is reported. To resume the programmed Sampling Method and Reporting Method, send the port select code followed by <cr>.
REPORT START TIME Type “2” and <cr> to enter the Report Start Time menu. The V77 ADM-1 will respond: REPORT START TIME Reporting Start Time HH:MM Current Date04/28/00 and Time MM/DD/YY HH:MM:SS Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:
This menu shows the current Reporting Start Time, Current Date04/28/00 and Time as reported by the base unit's time-of day clock when the reporting start time entry was selected, and prompts you to enter the desired Report Start Time. Reporting can be delayed up to 24 hours from the current time. Enter the desired Report Start Time. For example, suppose the Current Time is 9:20:30 and the Reporting Start Time is set to 10:45. After you exit the Configuration Main Menu, the V77 ADM-1 will start reporting data messages at 10:45 at the programmed Sampling Setup. If the M Series loses power, reporting resumes the next time the designated Report Start Time is observed by the time-of day clock. IMPORTANT: The Current Date04/28/00 and Time is not updated during data entry. You must consider any delays from the time you enter the Report Start Time until you exit the Configuration Main Menu. Be sure to set the Report Start Time far enough ahead of the current time to complete all configurations and exit configuration mode.
71
Page 84
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
NOTE: When using Schedule Reporting Method and the ADM-1 is initially reporting, if you enter into the menu-driven mode of configuration and exit, the ADM-1 will not resume reporting data messages until the programmed Report Start Time elapses. You may program the ADM-1 without disrupting data message reporting by using dynamic configuration. REPORT INTERVAL Type “3” and <cr> to enter the Report Interval menu. The V77 ADM-1 will respond: REPORT INTERVAL Report Interval
HH:MM
Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:
Enter the desired Report Interval. The Report Interval can range from 1 minute to 24 hours. Once the Report Start Time elapses, the V77 ADM-1 will report all buffered data messages to the designated host module until the buffer is empty. The V77 ADM-1 will continue to transmit all buffered data messages every time the Report Interval expires. For example, if the Report Start Time is 12:00 and the Report Interval is 1:00 (1 hour), the ADM-1 will report all messages in its buffer every hour on the hour starting at 12:00. HOST ADDRESS Type “4” and <cr> to enter the Host Address menu. The V77 ADM-1 will respond: HOST ADDRESS Host Address
1:1,1
Enter Unit Number (1-32) <cr>, or X to EXIT: Enter Module Number (1-16) <cr>, or X to EXIT: Enter Port Number (1-4) <cr>, or X to EXIT:
Enter the appropriate Host Address. This consists of the Unit Number (1 to 32), Module Number (1 to 16), and Port Number (1 to 4) where the designated host module is located. Each entry should be followed by <cr>. If there is a single M Series unit in service, the Host Address would typically be Unit 1, Module 1, Port 1. NOTE: The Host Address must be supplied to direct self-reporting data messages to the desired destination. If the Host Address is incorrect, selfreporting data messages will be misdirected or lost.
72
Page 85
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
DATA FORMAT Type “5” and <cr> to enter the Data Format menu. The V77 ADM-1 will respond: SELECT DATA FORMAT Data Format
HEX
Hexadecimal Decimal Engineering Units Exit
1 2 3 X
Enter Selection:
Type the number corresponding to the desired choice. The "Data Format" sub-menu provides a choice in the format of the sampled data contained in each data message. Data can be reported in Hexadecimal, Decimal, or in Engineering Units (volts). TIME TAG Type “6” and <cr> to enter the Time Tag menu. The V77 ADM-1 will respond: ENABLE / DISABLE TIME TAGGING Time Tagging
DISABLED
Enable Disable Exit
1 2 X
Enter Selection:
With time tag enabled, a MM/DD/YY HH/MM/SS entry is appended to all samples, where MM is the month, DD is the day, YY is the year, HH is the hour, MM is the minute, and SS is the second according to the base unit's time-of-day clock. TERMINATING CHARACTER(S) Type “7” and <cr> to enter the Termnating Character(s) menu. The V77 ADM-1 will respond: ENTER TERMINATING CHARACTER Terminating Character(s) 0D0A Enter 1 or 2 Terminating Characters in Hex Format (i.e. 0D0A for CR+LF) <cr>, or X to Exit:
73
Page 86
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Type the hexadecimal representation of the desired terminating character(s). For example, <cr> would be represented by 0D Hex. NOTE: Only ASCII characters A-F and 0-9 are acceptable.
CHANNEL INPUT SETUP Type “4” and <cr> to enter the Channel Input menu. The V77 ADM-1 will respond: CHANNEL INPUT SETUP Range Unipolar / Bipolar Single Ended / Differential Active Channels Exit
1 2 3 4 X
Enter Selection:
RANGE Type “1” and <cr> to enter the Range menu. The V77 ADM-1 will respond: SELECT INPUT VOLTAGE RANGE Range
+/-5 or 0 -10 Volts
+/-10 Volts with JP1 installed +/-5 or 0 -10 Volts +/-2.5 or 0 -5 Volts +/-1.25 or 0-2.5 Volts4 +/-0.625 or 0-1.25 Volts Exit
1 2 3 5 X
Enter Selection:
Enter the number (1 to 5) corresponding to the desired Range. IMPORTANT: If you intend to operate at +/- 10 volts, insure jumper JP1 is installed before connecting inputs to the V77 ADM-1. NOTE: A correct Unipolar/Bipolar selection must be made in conjunction with Range selection to insure proper operation. UNIPOLAR/BIPOLAR
74
Page 87
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Type “2” and <cr> to enter the Unipolar/Bipolar menu. The V77 ADM-1 will respond: SELECT INPUT POLARITY Unipolar / Bipolar
UN
Unipolar Bipolar Exit
1 2 X
Enter Selection:
Select the desired Input Polarity (unipolar or bipolar). Unipolar allows the channel inputs to operate between 0 and +X volts and bipolar allows the channel inputs to operate between -X and +X volts, where X is the selected Range. The Input Polarity must be programmed in conjunction with the Range sub-menu to set up a correct signal input voltage mode of operation.
SINGLE ENDED/DIFFERENTIAL Type “3” and <cr> to enter the Single Ended/Differential menu. The V77 ADM-1 will respond: SELECT INPUT CONFIGURATION Single Ended / Differential Single Ended Differential Exit
SE
1 2 X
Enter Selection:
Select the desired Input Configuration. Singled-ended operation allows up to 16 inputs using grounds of the same potential. Differential operation allows up to 8 inputs using different reference polarities. See Figure 1 or Figure 2 on page 5 to determine the correct connections on connector J2. ACTIVE CHANNELS
75
Page 88
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Type “4” and <cr> to enter the Sample Start Time menu. The V77 ADM-1 will respond: SELECT ACTIVE CHANNELS Enter 1 to ENABLE or 0 to DISABLE each channel <cr>, or X to Exit. NOTE: Only channels 1-8 can be active if DIFFERENTIAL inputs selected! CHANNEL NUMBERS 1111111 1234567890123456 CURRENT STATUS 1000000000000000 ENTER SELECTION:
Type a number between 0000000000000000 and 1111111111111111 followed by <cr>. A "1" indicates that a channel is active and a "0" indicates the channel is inactive. You may enable or disable any individual input channel. It is not necessary to enter all 16 channels. You have only to enter up to the highest channel you wish to activate or deactivate. For example, if all channels are initially inactive (0000000000000000), and you only want to activate channels one and four, enter 1001<cr>. NOTE: Only channels 1 through 8 may be enabled if Differential inputs are selected (i.e., channels 9-16 cannot be active). If you enter a "1" for channels 9-16 while in differential mode, those entries will automatically revert to "0". If you increase the number of active channels and exceed the maximum sample rate, a menu appears showing the maximum permissible sample rate based on the number of active channels. For example, if you had eight active channels allowing a maximum sample rate of 500S/sec and increased to 16 active channels, the following message appears if you select Set Sample Rate under the Sampling Setup menu: SET SAMPLE RATE
250S/sec
Enter Rate (1-250S/sec) followed by ENTER or X to Exit:
An entry within the displayed range must be entered, or you can exit this menu and reduce the number of active channels. DYNAMIC CONFIGURATION
76
Page 89
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Type “5” and <cr> to enter the Dynamic Configuration menu. The V77 ADM-1 will respond:
DYNAMIC CONFIGURATION COMMANDS Dynamic Configuration Commands Enable Disable Exit
DISABLED
1 2 X
Enter Selection:
Dynamic configuration mode allows the V77 ADM-1 to be programmed by downloading dynamic (on-the-fly) commands. EXIT Type “X” and <cr> to exit the configuration menu. The V77 ADM-1 will respond: Save Changes as Defaults? (Y/N)
If you reply (Y), the settings are saved as the permanent power-up defaults. That is, if the M16/M8 loses power for any reason, the settings saved as defaults become the power-up settings. If you reply (N), your selections are saved as current (temporary) operating settings, but are lost upon power-down. The most recent menu selections saved as Defaults are restored as the current operating parameters when power is reapplied. If you respond with (Y), the V77 ADM-1 will respond with: Saving Configuration as Defaults... Configuration complete
DYNAMIC CONFIGURATION PROCEDURE AND COMMANDS V77 ADM-1 dynamic configuration commands are issued through a host module, the service port, or the service modem (config ports). The V77 ADM-1 will recognize dynamic configuration commands only when dynamic configuration is enabled. Use the following procedure to send dynamic configuration commands to the V77 ADM1: 1.
Select the V77 ADM-1 from a config port by sending a select sequence which consists of the port select code ($BT - default), the appropriate unit number followed by a colon (01: to 30: - for cascaded units only), the desired module number (2 to 16), and a terminating character for <cr> (0D Hex). For example, to select a
77
Page 90
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
V77 ADM-1 Module installed as Module 15 of a non-cascaded unit using the default port select code, send $BT15<cr>. 2.
Once the V77 ADM-1 is selected, it enters Command Mode and allows you to send dynamic configuration commands. The V77 ADM-1 configuration commands begin with two capital letters designating the specific command and are terminated with <cr>. Most configuration commands require a number between the command letters and <cr>. This number represents the desired configuration parameter.
3.
After you have sent the desired configuration command(s) to the V77 ADM-1 module, you may disconnect by sending $BT<cr>. You may disconnect from the V77 ADM-1 and select a different module or the base unit by sending $BTn<cr>.
NOTE: Multiple configuration commands may be sent while the V77 ADM-1 is in command mode. Each command should be terminated with <cr>. For example: AV300<cr>VR1<cr>SD1<cr> AVERAGE COMMAND The Average (AV) command programs the Number of Samples to Average between 1 and 4000. You must ensure the combination of Sample Rate and Sample Interval is sufficient to contain the desired number of samples to be averaged. For example, if you want to average 100 samples at a Sample Rate of 15/sec, the Sample Interval must be greater than 100 secs. If you enter an interval less than the time required to average the selected number of samples, the V77 ADM-1 continues taking samples until the selected number of samples to be averaged is met. In the example above, if you select an interval of 50 seconds, the sample will not be reported until all 100 samples are taken (100 seconds). The Average command has the following format: AVn<cr> where n = 1 to 4000. REPORTING METHOD COMMAND The Reporting Method (RM) command programs the V77 ADM-1 Reporting Method. The Reporting Method command has the following format: RMn<cr>
78