For the BayTech M3 DAC

Page 71

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Time Tag Mode Connect Port ID Echo Port EIA Driver Exit

8 9 A X

Enter Request :

You can make whatever changes are necessary by responding to the above menu. The Exit function returns you to Operations Mode. SERIAL PORT CONFIGURATION Type “2” (in the configuration main menu) and <cr> to change the serial port configuration. The module will respond: Enter Serial Port Number (? = Help, ENTER = Exit) :?

Type the port number of the selected module that you wish to reconfigure followed by <cr>. If you wish to review the status of the selected module, type "?". For example, if you enter "4", the module responds with the current status for Port 4 and a list of available options as follows: Current Module 2 Serial Port Configuration : Port

Device Name

Baud Rate

Word Size

Stop Bits

Parity

4

Device D

9600

8

1

None

Set Stop Bits Set Parity Set Xon/Xoff

4 5 6

Exit/Save Set Baud Rate Set Word Size Enter Request:

1 2 3

Xon / Xoff Xmit

Recv

Off

Off

You can now reconfigure Port 4 by selecting the appropriate option from the menu (1 to 6). For example, to change the baud rate to 115.2K baud, send "2" (set baud rate). The module will respond with this menu:

1 For 300 2 For 600 3 For 1200 4 For 2400 5 For 4800 6 For 9600 7 For 19200 8 For 38400 9 For 76.8K A For 115.2K

59

Page 72

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Enter Request :

Send "A" for 115.2K baud rate, and the module will respond with the reconfigured status of the port, the option menu, and the prompt: Current Module 1 Serial Port Configuration : Port

Device Name

Rate

Word Size

Stop Bits

Parity

4

Device D

115.2K

8

1

None

Set Stop Bits Set Parity Set Xon/Xoff

4 5 6

Exit/Save Set Baud Rate Set Word Size Enter Request:

1 2 3

Xon / Xoff Xmit

Recv

Off

Off

You can now select other options from the menu to reconfigure Port 4. For example, to enable Xon/Xoff handshaking in the receive data direction only, send "6" (Set Xon/Xoff Xmit) in response to the prompt. The module will respond with: Output Flow Control (Xmit) - Xon/Xoff is ( OFF ) Stop/Restart Output Upon Receiving of Xoff/Xon ? (Y/N) :

Enter "Y" to enable XON/XOFF on transmit or "N" to disable XON/XOFF on transmit. Following our example, enter "N" and the module will respond with: Input Flow Control (Recv) - Xon/Xoff is ( Off ) Xoff/Xon sent based on Buffer - Full/Empty condition ? (Y/N) :

Enter "Y" to enable XON/XOFF on receive or "N" to disable XON/XOFF on receive. Following our example, enter "Y" and the module will respond with the reconfigured status for Port 4 as follows: Current Module 1 Serial Port Configuration Port Device Baud Word Stop Name Rate Size Bits

Parity

4

1

None

Set Stop Bits Set Parity Set Xon/Xoff

4 5 6

Device D

Exit/Save Set Baud Rate Set Word Size Enter Request:

9600 1 2 3

8

Xon / Xoff Xmit

Recv

Off

On

If there are no other changes for this port, send "1" (Exit/Save) and the module will respond with:

60

Page 73

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Save Changes Permanently ? (Y/N) :

If you type "Y", the new configuration for the selected port is stored permanently in non-volatile memory and the module will subsequently power up at the new configuration. If you type "N", the new configuration is stored in RAM and lost once power is removed from the unit. After you type the desired response to the save changes prompt, the module will respond with: Enter Serial Port Number (? = Help, ENTER = Exit) :

Enter the number of any other port you wish to reconfigure. If there are no other ports, type <cr> and the module will return to the main configuration menu. CHANGE PORT DEVICE NAME Type “3” (in the configuration main menu) and <cr> to change the Port Device Name. The module will respond: Enter Port Number (? = Help, ENTER = Exit) :

Type the port number that you wish to reconfigure followed by <cr>. If you wish to review the device name status for all ports of the module, type "?". For example, if you enter "4", the module will respond with: Current Module 1 Serial Port Configuration : Port

Device Name

Baud Rate

Word Size

Stop Bits

Parity

4

Device D

115.2K

8

1

None

Xon / Xoff Xmit

Recv

Off

Off

Enter Port Device Name (Max 16 Characters) Or ENTER for no change…………………..:

Enter the desired port device name up to 16 characters. For example, if you enter "Port 4", the module will respond with: Current Module 1 Serial Port Configuration : Port

Device Name

Baud Rate

Word Size

Stop Bits

Parity

4

PORT 4

115.2K

8

1

None

Xon / Xoff Xmit

Recv

Off

Off

Enter Port Device Name (Max 16 Characters) Or ENTER for no change…………………..:

61

Page 74

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

If the port device name is satisfactory, type <cr> and the will respond with: Enter Port Number (? = Help, ENTER = Exit) :

Enter the number of any other port you wish to reconfigure. If there are no other ports, type <cr> and the module will return the main configuration menu. PORT ID Type “4” (in the configuration main menu) and <cr> to change the port ID. The module will respond: Enter Port Number (? = Help, ENTER = Exit) :

Type the desired port number followed by <cr> or type <cr> without any number to exit to the main configuration menu. For example, if you type "1" followed by <cr> for Port 1, the I/O module responds with: Current Module 3 Port I.D : Port Port ID 1 01:03,1 Disable Port I.D Use Unit,Module,Port number Use Device Name

1 2 3

Select Port I.D (ENTER = no change):

Type "1" to disable the Port ID feature, "2" to send the selected port's Unit Number:Module Number,Port Number as the Port ID, or "3" to send the selected port's device name as the Port ID. DESIGNATE HOST PORT LOCATION Type “5” (in the configuration main menu) and <cr> to designate the host port location. The module will respond: Current Host Designation is Module........1:1,1 Enter New Host Unit Number (1-30):

Type the desired unit number followed by <cr>. The module will respond with: Enter New Host Module Number (1 to 16):

Type the desired module number followed by <cr>.

62

Page 75

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

NOTE: If you type "0" from this menu, all completed messages are sent to the base unit (i.e., the service port or service modem). The module will respond with: Enter New Host Port Number (1 - 4):

Type the desired port number followed by <cr>. NOTE: If a V71 is the designated host module, the host port number is "1" (default). If the base unit is the designated host module, the host port number is "1" for the service port or "2" for the service modem. All completed messages received while operating in immediate reporting mode are sent to the designated host port. MESSAGE TERMINATE CHARACTER Type “6” (in the configuration main menu) and <cr> to change the message terminate character. The module will respond: Current Terminate Character is.............0DH Enter Terminate Character in Hex or ENTER for no change ....................:

Enter the desired message terminating character in the form of a two-digit hexadecimal character from 00 Hex to 7F Hex. For example, if you enter "0A" (Line Feed), the module will respond with: Current Terminate Character is.............0AH Enter Terminate Character in Hex or ENTER for no change ....................:

If the displayed terminate character is satisfactory, type <cr> and the module will return to the main configuration menu MODE OF OPERATION Type “7” (in the configuration main menu) and <cr> to change the mode of operation. The module will respond: MODE OF OPERATION Full Duplex Mode Immediate Message Mode Command Mode

1 2 3

63

Page 76

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Immediate Data Mode

4

Current Mode of Operation is Enter Mode of Operation :

1

You can now enter the mode of operation that you wish followed by <cr>. The module will return to the main configuration menu. TIME TAG MODE Type “8” (in the configuration main menu) and <cr> to enable or disable the time tag mode. The module will respond: Current Time Tag Mode is Enable Disable Exit

Disabled 1 2 X

Enter Selection:

Type the appropriate number to enable or disable time tag or "X" (for no change) followed by <cr>. The module will return to the main configuration menu. CONNECT PORT ID ECHO Type “9” (in the configuration main menu) and <cr> to enable or disable the connect port ID echo. The module will respond: Connect Port ID Echo is................Disabled Change it? (Y/N) :

Type “Y” to change the current setting or “N” to exit to the main configuration menu. If Connect Port ID Echo is enabled, the programmed Port ID will be sent to the host computer whenever a Serial port is selected. NOTE: Connect Port ID Echo is not functional if the peripheral module is operating in command mode. EXIT Type “X” (in the configuration main menu) and <cr> to exit the configuration mode.

V77 ADM-1 MODULE CONFIGURATION

64

Page 77

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

MAIN MENU CONFIGURATION To access the menu-driven configuration mode of the V77 ADM-1 from any host module, use the procedure on page 44. With $CONFIG input the V77 ADM-1 installed as Module X will respond with an identification block and a menu of the available configuration options similar to the following:

Copyright (c) Bay Technical Associates,1993 DAC V77 ADM-1 Rev. 1.## This Module is X CONFIGURATION MAIN MENU Module Status Sampling Setup Reporting Setup Channel Input Setup Dynamic Configuration Exit

1 2 3 4 5 X

Enter Selection:

NOTE: The configuration menus shown in the following sections are depicted with factory default settings and may vary slightly in presentation. Enter the number corresponding to your desired choice. Each choice will invoke a sub-menu. Each sub-menu is described in the following sections. When you exit a sub-menu, you will be returned to the configuration main menu. When "Exit" is selected from the main menu, the V77 ADM-1 will exit from configuration mode and go into an active data collection mode. MODULE STATUS Type “1” and <cr> to enter the Module Status menu. The V77 ADM-1 will respond: MODULE STATUS

65

Page 78

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Sampling Method Sample Start Time Sample Period Sample Rate No. of Samples to Average Reporting Method Reporting Start Time Reporting Period Host Address Data Format Time Tagging Terminating Characters

COMMAND HH:MM HH:MM:SS 1S/sec 10 COMMAND 24:00 24:00 1:1,1 HEX DISABLED 0D0A

Press a key to continue or X to Exit... Range Unipolar / Bipolar Single Ended / Differential Active Channels Dynamic Configuration

+/-5 or 0-10 Volts BI SE 1000000000000000 DISABLED

Press any key t o Exit

SAMPLING SETUP Type “2” and <cr> to enter the Sampling Setup menu. The V77 ADM-1 will respond: Sampling Method Sample Start Time Sample Interval Sample Rate No. of Samples to Average Exit

1 2 3 4 5 X

Enter Selection:

The three Sampling Methods are Command (upon request only), Immediate (upon exiting configuration), and Schedule (where sampling begins at the Sample Start Time). Sample Interval is the interval between the start of sampling periods. Continuous sampling is selected if 00:00:00 is entered. Sample Rate can be programmed from 1 to 4000 samples per second. The sample rate for an individual channel is the programmed rate divided by the number of active channels. Number of Samples to Average is the number of samples averaged per data message. SAMPLING METHOD Type “1” and <cr> to enter the Sampling Method menu. The V77 ADM-1will respond:

66

Page 79

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ SELECT SAMPLING METHOD Sampling Method

COMMAND

Command Immediate Schedule Exit

1 2 3 X

Enter Selection:

The V77 ADM-1 provides three Sampling Methods. These are Command (upon request via data commands only), Immediate (upon exiting configuration), and Schedule (where sampling begins at a specified time). When Command Sampling Method is selected, the V77 ADM-1 will only sample when the SAn command is issued. One data message will be read at the programmed Sampling Rate and Number of Samples to Average and reported to the host device for each channel specified. The SAn command may be issued to the V77 ADM-1 in any of the three Sampling Methods. When Immediate Sampling Method is selected, the V77 ADM-1 will sample at the selected Sample Rate, Sample Interval, and Number of Samples to Average immediately after exiting the Configuration Main Menu. When Schedule Sampling Method is selected, the V77 ADM-1 will begin sampling at the programmed Sample Start Time. Sampling will occur at the programmed Sample Rate, Sample Interval, and Number of Samples to Average. The Sample Start Time is programmable up to 24 hours in advance of the current (time-of-day) clock time. IMPORTANT: If you program the V77 ADM-1 to commence sampling after the Report Start Time, data messages are not furnished until the Sampling Start Time is reached. Conversely, if you start sampling before the Report Start Time, the first report will contain all data sampled and buffered until reporting is initiated. NOTE: When a "Command" sample is requested by entering the SAn data command, the Reporting Method and Sampling Method currently programmed are overridden and a single data message is read and reported. Multiple SAn commands may be entered before returning to self-reporting operation. To resume the programmed Sampling Method and Reporting Method, send the port select code followed by <cr>. SAMPLE START TIME Type “2” and <cr> to enter the Sample Start Time menu. The V77 ADM-1 will respond:

67

Page 80

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ SAMPLING START TIME Sampling Start Time HH:MM Current Date04/28/00 and Time MM/DD/YY HH:MM:SS Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:

This menu shows the current Sample Start Time, the base unit's current date and time, and prompts you to enter the desired Sampling Start Time. Sampling can be delayed up to 24 hours from the current time. The Current Date04/28/00 and Time are the values reported by the base unit's time-of day clock when the reporting start time entry was selected. IMPORTANT: The Current Date04/28/00 and Time is not updated during data entry. Therefore, you must consider any delays from the time you enter the Sample Start Time until you exit the Configuration Main Menu. Be sure to set the Sample Start Time late enough to complete all configurations and exit the Configuration Main Menu before the designated Sample Start Time. If you set a Sample Start Time and exit the main configuration menu after the designated Sample Start Time elapses, sampling will be delayed until the following day. Enter the desired Sample Start Time. For example, suppose the current time is 9:20:30 and the Sample Start Time is set to 10:45. After you exit the Configuration Main Menu, the V77 ADM-1 will start sampling data at 10:45 the programmed Sampling Setup. If the M Series loses power, sampling resumes the next time the designated Sample Start Time is observed by the time-of day clock. If, for example, power is removed at 11:30 and restored at 12:00 and the Sample Start Time is set to 10:45, sampling will resume at 10:45 the following day. SAMPLE INTERVAL Type “3” and <cr> to enter the Sample Interval menu. The V77 ADM-1 will respond: SAMPLE INTERVAL Sample Period

HH:MM:SS or "CONTINUOUS"

NOTE Enter 00:00:00 for continuous sampling. Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit: Enter Seconds (0-59) <cr>, or X to Exit:

68