M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ where n = 1 to 3. 1 = Command, 2 = Immediate and 3 = Schedule. SINGLE ENDED OR DIFFERENTIAL COMMAND The Single Ended or Differential (SD) command programs the V77 ADM-1 to use single ended or differential inputs. The Single Ended or Differential command has the following format: SDn<cr> where n = 1 or 2. 1 = single ended and 2 = differential. TIME TAG COMMAND The Time Tag (TT) command is used to enable or disable time tagging. The Time Tag command has the following format: TTn where n = 1 or 2. 1 = enable and 2 = disable. UNIPOLAR/BIPOLAR COMMAND The Unipolar/Bipolar command programs the V77 ADM-1 channel inputs for unipolar or bipolar operation. The Unipolar/Bipolar command has the following format: UBn<cr> where n = 1 or 2. 1 = unipolar and 2 = bipolar. VOLTAGE RANGE COMMAND The Voltage Range command is used to program the desired operating voltage range of the V77 ADM-1 channel inputs. The Voltage Range command has the following format: VRn<cr> where n = 1 to 5. 1 = -10 to +10V (with JP1 installed), 2 = -5 to +5V (or 0 to +10V), 3 = -2.5 to +2.5V (or 0 to +5V), 4 = -1.25 to +1.25V (or 0 to +2.5V), and 5 = -0.625 to +0.625V (or 0 to +1.25V).
79
Page 92
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
V78 CRM-1 MODULE CONFIGURATION To access configuration mode of the V78 CRM-1, use the procedures on page 44. CONFIGURATION MAIN MENU With $CONFIG input the V78 CRM-1 module installed as Module X will respond with an identification block and a menu of the available configuration options similar to the following: Copyright (c) Bay Technical Associates,1993 DAC V78 CRM-1 Rev. 1.01 This Module is X CONFIGURATION MAIN MENU Module Status Relay Operating Setup Reporting Setup Dynamic Configuration Exit
1 2 3 4 X
Enter Selection:
NOTE: The configuration menus shown in the following sections are depicted with factory default settings and may vary slightly in presentation. Enter the number corresponding to your desired choice. Each choice will invoke a sub-menu. Each sub-menu is described in the following sections. When you exit a sub-menu, you will be returned to the configuration main menu. When "Exit" is selected from the main menu, the V78 CRM-1 will exit from configuration mode and go into an active data collection mode. MODULE STATUS Type “1” (in the configuration main menu) and <cr> to display module status. The module will respond: MODULE STATUS Schedule Status Reporting Method Reporting Start Time Reporting Period
80
NO SCHEDULE ENTERED COMMAND 24:00 24:00
Page 93
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Host Address Data Format Time Tagging Terminating Character(s Dynamic Configuration
1:1,1 HEX DISABLED 0D0A DISABLED
Press a key to continue or X to Exit.
RELAY OPERATING SETUP Type “2” (in the configuration main menu) and <cr> to display the relay operating setup menu. The module will respond: RELAY OPERATING SETUP List Current Schedule Create/Modify Schedule Enable/Disable Events Delete Events/Schedule Exit
1 2 3 4 X
Enter Selection:
LIST CURRENT SCHEDULE Type “1” (in the relay operating setup menu) and <cr> to list the current schedule. The module will respond: CURRENT SCHEDULE EVENT START NO. TIME
DURATION
INTERVAL
DD
HH:MM:SS
HH:MM NN:NN
D HH:MM:SS
01 02 03 04 05 06 07 08 09 10 11 12
00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00 00:00:00
00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00 00:00
0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00 0 00:00:00
RELAY NO.
0 0 0 0 0 0 0 0 0 0 0 0
81
Page 94
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Press any key to EXIT
Press any key to return to the Relay Operating Setup menu. CREATE/MODIFY SCHEDULE Type “2” (in the relay operating setup menu) and <cr> to create or modify the current schedule. The module will respond: EVENT NUMBER Enter Event Number (1-12) <cr>, or X to EXIT:
Type the desired Event Number (1 to 12) followed by <cr>. The V78 CRM-1 will respond with the Event Start Time menu. The Event Start Time consists of the day of the week and time of day the initial occurrence of the selected relay event will happen. The CRM-1 will respond with: EVENT START TIME Event Start Time..................SU 00:00:00 Current Date04/28/00, Day-of-Week and Time.MM/DD/YY D HH:MM:SS Enter Day-of-Week (0=Any, 1=SUN, 2=MON....7=SAT)<cr>, or X to EXIT:
Type the desired day of the week for the initial relay event (1 to 7) or 0 for any day followed by <cr>. For example if you enter "1" for Monday, the V78 CRM-1 will respond with: Enter Hours (0-23)<cr>, or X to EXIT:
Type the desired hour for the initial relay event followed by <cr>. For example, if you enter "14" for 2:00pm, the CRM-1 will respond with: Enter Minutes (0-59)<cr>, or X to EXIT:
Type the desired minute of the selected hour for the initial relay event followed by <cr>. For example, type "0" to start at the top of the selected hour. After you have entered in the desired Event Start Time, the V78 CRM-1 will respond with the Event Duration menu which allows you to program how long the selected relay will stay energized once the Event Start Time elapses. The Event Start Time may be programmed in hours and minutes or in milliseconds. The V78 CRM-1 will respond with:
82
Page 95
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ EVENT DURATION Event Duration.......................00:00 Select Duration in (H)ours and Minutes or (M)illiseconds (H/M), or X to EXIT:
Type "H" to program the Event Duration in Hours and Minutes or "M" for milliseconds. For example, if you type "M" for milliseconds, the CRM-1 will respond with: Enter Duration (10-60000 Milliseconds)<cr>, or X to EXIT:
Type the desired number of milliseconds you want the selected relay to remain energized followed <cr>. The CRM-1 will prompt you to enter the desired relay number that you wish the selected event to energize. The CRM-1 will respond with: Enter Relay Number (1-8)<cr>, or X to EXIT:
Type the desired relay number (1 to 8) followed by <cr>. The CRM-1 will respond with: DATA CORRECT (Y/N)?
If the data displayed for the selected Event Number is correct type "Y". The CRM-1 will return to the Relay Operating Setup menu shown on page 16. If you type "N", the CRM-1 will return to the Event Start Time menu shown on the previous page. ENABLE/DISABLE EVENTS Type “3” (in the relay operating setup menu) and <cr> to enable or disable events. The module will respond: ENABLE/DISABLE EVENTS Event Number(s) 0 ENABLED Enter Event Number (1-12, 0=ALL)<cr>, or X to exit:
This menu shows the current Event Numbers enabled and prompts you to type the desired Event Number to enable or disable followed by <cr>. Enter the desired Event Number to enable or disable. The V78 CRM-1 will respond with: Enable Disable Exit
1 2 X
83
Page 96
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Enter Selection:
Type "1" to enable the selected relay event or "2" to disable the selected relay event. DELETE EVENTS/SCHEDULE Type “4” (in the relay operating setup menu) and <cr> to delete events or schedules. The module will respond: DELETE EVENTS Enter Event Number (1-12, 0=ALL)<cr>, or X to exit:
Type the Event Number you wish to delete or "0" for the entire schedule followed by <cr>. REPORTING SETUP Type “3” (in the configuration menu) and <cr> to display the reporting setup menu. The module will respond: REPORTING SETUP Reporting Method Report Start Time Report Interval Host Address Time Tag Terminating Character(s Exit
1 2 3 4 5 6 X
Enter Selection:
REPORTING METHOD Type “1” (in the reporting setup menu) and <cr> to change the reporting method. The module will respond: SELECT REPORTING METHOD Reporting Method COMMAND Command Immediate (When Event Occurs) Schedule Exit Enter Selection:
84
1 2 3 X
Page 97
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
The CRM-1 provides three Reporting Methods. These are Command (via data commands only), Immediate (upon exiting configuration), and Schedule (where reporting begins at a specified time). Regardless of the Reporting Method, when the V78 CRM-1 receives an SAn<cr> command, it will report the current status of the selected relay (energized or deenergized) to the host-controller. When Command Reporting Method is selected, the V78 CRM-1 will report event data messages to the host module only when the RAn or RSn commands are issued. If V78 CRM-1 receives a RAn (Read All Buffered Samples) command, all data messages currently stored in the buffer of the selected relay(s) are transmitted to the host-controller. Each time the V78 CRM-1 receives a RSn (Report a Single Sample if available) command, the oldest event data message available is transmitted to the host-controller. When Immediate Reporting Method is selected, the V78 CRM-1 will report data messages as events occur. If no event has occurred, no report is made. Reporting begins immediately after exiting the configuration main menu When Schedule Reporting Method is selected, the V78 CRM-1 will begin reporting data messages as events occur at the programmed Report Start Time. The Report Start Time is programmable up to 24 hours in advance of the current (time-of-day) clock time. Data messages are stored in the buffer until the Report Start Time is reached at which time all buffered data messages are reported to the host module. Further reporting is based upon the selected Report Interval. REPORT START TIME Type “2” (in the reporting setup menu) and <cr> to change the report start time. The module will respond: REPORT START TIME Reporting Start Time HH:MM Current Date04/28/00 and Time MM/DD/YY HH:MM:SS Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:
This menu shows the current Reporting Start Time, Current Date04/28/00 and Time as reported by the base unit's time-of day clock when the reporting start time entry was selected, and prompts you to enter the desired Report Start Time. Reporting can be delayed up to 24 hours from the current time.
85
Page 98
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Enter the desired Report Start Time. For example, suppose the Current Time is 9:20:30 and the Reporting Start Time is set to 10:45. After you exit the Configuration Main Menu, the V78 CRM-1 will start reporting data messages at 10:45 at the programmed Sampling Setup. If the M Series loses power, reporting resumes the next time the designated Report Start Time is observed by the time-of day clock. IMPORTANT: The Current Date04/28/00 and Time is not updated during data entry. You must consider any delays from the time you enter the Report Start Time until you exit the Configuration Main Menu. Be sure to set the Report Start Time far enough ahead of the current time to complete all configurations and exit configuration mode. NOTE: When using Schedule Reporting Method and the V78 CRM-1 is initially reporting, if you enter into the menu-driven mode of configuration and exit, the V78 CRM-1 will not resume reporting data messages until the programmed Report Start Time elapses. You may program the CRM-1 without disrupting data message reporting by using dynamic configuration. REPORT INTERVAL Type “3” (in the reporting setup menu) and <cr> to change the reporting interval. The module will respond: REPORT INTERVAL Report Interval
HH:MM
Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:
Enter the desired Report Interval. The Report Interval can range from 1 minute to 24 hours. Once the Report Start Time elapses, the V78 CRM-1 will report all buffered data messages to the designated host module until the buffer is empty. The V78 CRM-1 will continue to transmit all buffered data messages every time the Report Interval expires. For example, if the Report Start Time is 12:00 and the Report Interval is 1:00 (1 hour), the V78 CRM-1 will report all messages in its buffer every hour on the hour starting at 12:00. HOST ADDRESS Type “4” (in the reporting setup menu) and <cr> to change the host address. The module will respond: HOST ADDRESS Host Address
86
1:1,1
Page 99
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Enter Unit Number (1-32) <cr>, or X to EXIT: Enter Module Number (1-16) <cr>, or X to EXIT: Enter Port Number (1-4) <cr>, or X to EXIT:
Enter the appropriate Host Address. This consists of the Unit Number (1 to 32), Module Number (1 to 16), and Port Number (1 to 4) where the designated host module is located. Each entry should be followed by <cr>. If there is a single M Series unit in service, the Host Address would typically be Unit 1, Module 1, Port 1. NOTE: The Host Address must be supplied to direct self-reporting data messages to the desired destination. If the Host Address is incorrect, selfreporting data messages will be misdirected or lost.
TIME TAG Type “5” (in the reporting setup menu) and <cr> to enable or disable the time tag. The module will respond: ENABLE / DISABLE TIME TAGGING Time Tagging
DISABLED
Enable Disable Exit
1 2 X
Enter Selection:
With time tag enabled, a MM/DD/YY HH/MM/SS entry is appended to all samples, where MM is the month, DD is the day, YY is the year, HH is the hour, MM is the minute, and SS is the second according to the base unit's time-of-day clock. TERMINATING CHARACTER(S) Type “6” (in the reporting setup menu) and <cr> to change the terminating character(s). The module will respond: ENTER TERMINATING CHARACTER Terminating Character(s) 0D0A Enter 1 or 2 Terminating Characters in Hex Format (i.e. 0D0A for CR+LF) <cr>, or X to Exit:
87
Page 100
M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________
Type the hexadecimal representation of the desired terminating character(s). For example, <cr> would be represented by 0D Hex. NOTE: Only ASCII characters A-F and 0-9 are acceptable. DYNAMIC CONFIGURATION Type “5” (in the configuration main menu) and <cr> to enable or disable the dynamic configuration capability. The module will respond: DYNAMIC CONFIGURATION COMMANDS Dynamic Configuration Commands DISABLED Enable Disable Exit
1 2 X
Enter Selection:
Dynamic configuration mode allows the V78 CRM-1 to be programmed by downloading dynamic (on-the-fly) commands. EXIT Type “X” (in the relay operating setup menu) and <cr> to exit the configuration mode. The module will respond: Save Changes as Defaults? (Y/N)
If you reply (Y), the settings are saved as the permanent power-up defaults. That is, if the M16/M8 loses power for any reason, the settings saved as defaults become the power-up settings. If you reply (N), your selections are saved as current (temporary) operating settings, but are lost upon power-down. The most recent menu selections, saved as defaults, are restored as the current operating parameters when power is reapplied. If you reply (Y), the V78 CRM-1 will respond with: Saving Configuration as Defaults... Configuration complete
DYNAMIC CONFIGURATION PROCEDURE AND COMMANDS V78 CRM-1 dynamic configuration commands are issued through a host module, the service port, or the service modem (config ports). The V78 CRM-1 will recognize dynamic configuration commands only when dynamic configuration is enabled. Use
88