Page 101

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ the following procedure to send dynamic configuration commands to the V78 CRM1: 1.

Select the V78 CRM-1 from a config port by sending a select sequence which consists of the port select code ($BT - default), the appropriate unit number followed by a colon (01: to 30: - for cascaded units only), the desired module number (2 to 16), and a terminating character for <cr> (0D Hex). For example, to select a V78 CRM-1 Module installed as Module 15 of a non-cascaded unit using the default port select code, send $BT15<cr>.

2.

Once the V78 CRM-1 is selected, it enters Command Mode and allows you to send dynamic configuration commands. The V78 CRM-1 configuration commands begin with two capital letters designating the specific command and are terminated with <cr>. Most configuration commands require a number between the command letters and <cr>. This number represents the desired configuration parameter.

3.

After you have sent the desired configuration command(s) to the V78 CRM-1 module, you may disconnect by sending $BT<cr>. You may disconnect from the V78 CRM-1 and select a different module or the base unit by sending $BTn<cr>.

NOTE: Multiple configuration commands may be sent while the V78 CRM-1 is in command mode. Each command should be terminated with <cr>. For example: RM1<cr>TT2<cr> REPORTING METHOD COMMAND The Reporting Method (RM) command programs the V78 CRM-1 Reporting Method. The Reporting Method command has the following format: RMn<cr> where n = 1 to 3 (1 = Command, 2 = Immediate and 3 = Schedule). TIME TAG COMMAND The Time Tag (TT) command is used to enable or disable time. The Time Tag command has the following format:

89

Page 102

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ TTn where n = 1 or 2 (1 = enable and 2 = disable).

V79 PDI-1 AND V80 PDI-2 MODULE CONFIGURATION To access configuration mode of the V79 PDI-1 or V80 PDI-2 use the procedures on page 44. MAIN MENU CONFIGURATION With $CONFIG input the V79 PDI-1 module installed as Module X will respond with an identification block and a menu of the available configuration options similar to the following: NOTE: The only difference in the configuration main menu for the PDI-1 or PDI-2 modules is the second line in the header showing the module type. All subsequent menus are the same for both modules. Thus, only the V79 PDI-1 will be discussed in the following sections. The configuration menus shown in the following sections are depicted with factory default settings and may vary slightly in presentation. Copyright (c) Bay Technical Associates,1993 DAC V79 PDI-1 Rev. 1.XX This Module is X CONFIGURATION MAIN MENU Module Status Sampling Setup Reporting Setup Dynamic Configuration Exit Enter Selection:

MODULE STATUS

90

1 2 3 4 X

Page 103

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

Type “1” (in the configuration main menu) and <cr> to display module status. The module will respond: MODULE STATUS Debounce Delay (Milliseconds Latch Polarity Reporting Method Reporting Start Time Reporting Period Host Address Data Format Time Tagging Terminating Character(s) Dynamic Configuration

100 LO to HI COMMAND 24:00 24:00 1:1,1 HEX DISABLED 0D0A DISABLED

Press a key to continue or X to Exit.

SAMPLING SETUP Type “2” (in the configuration main menu) and <cr> to display the sampling setup menu. The module will respond: SAMPLING SETUP Debounce Delay Latch Polarity Exit

1 2 X

Enter Selection:

You may program the Debounce Delay the Latch Polarity from this menu. The Exit selection will return you to the configuration main menu. For example, if you type "1" (Debounce Delay), the PDI will respond with the following: SET DEBOUNCE DELAY (0-65535 Milliseconds) Debounce Delay Exit

100 X

Enter Value<CR>, or X to EXIT:

Type the desired debounce delay time followed by <cr>. The debounce delay is used to guard against erroneous events. An event will not be valid unless the input channel has remained at a changed state for the debounce duration. If you type "2" from the "Sampling Setup" menu shown on the previous page (Latch Polarity), the PDI will respond with the following:

91

Page 104

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ SET LATCH POLARITY Latch Polarity

HI TO LO

Low to Hi Transitions only Hi to Low Transitions only Exit

1 2 X

Enter Selection:

Enter the desired Latch Polarity. The Latch Polarity is used to latch initial events for individual inputs based on a positive going (LO to HI) or negative going (HI to LO) input. REPORTING SETUP Type “3” (in the configuration menu) and <cr> to display the reporting setup menu. The module will respond: REPORTING SETUP Reporting Method Report Start Time Report Interval Host Address Time Tag Terminating Character(s Exit

1 2 3 4 5 6 X

Enter Selection:

REPORTING METHOD Type “1” (in the reporting setup menu) and <cr> to change the reporting method. The module will respond: SELECT REPORTING METHOD Reporting Method COMMAND Command Immediate (When Event Occurs) Schedule Exit Enter Selection:

92

1 2 3 X

Page 105

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

The V79 PDI-1 provides three Reporting Methods. These are Command (via data commands only), Immediate (upon exiting configuration), and Schedule (where reporting begins at a specified time). Regardless of the Reporting Method, when the V79 PDI-1 receives an SAn<cr> command, it will report the current status of the selected relay (energized or deenergized) to the host-controller. When Command Reporting Method is selected, the V79 PDI-1 will report event data messages to the host module only when the RAn or RSn commands are issued. If V79 PDI-1 receives a RAn (Read All Buffered Samples) command, all data messages currently stored in the buffer of the selected relay(s) are transmitted to the hostcontroller. Each time the V79 PDI-1 receives a RSn (Report a Single Sample if available) command, the oldest event data message available is transmitted to the host-controller. When Immediate Reporting Method is selected, the V79 PDI-1 will report data messages as events occur. If no event has occurred, no report is made. Reporting begins immediately after exiting the configuration main menu When Schedule Reporting Method is selected, the V79 PDI-1 will begin reporting data messages as events occur at the programmed Report Start Time. The Report Start Time is programmable up to 24 hours in advance of the current (time-of-day) clock time. Data messages are stored in the buffer until the Report Start Time is reached at which time all buffered data messages are reported to the host module. Further reporting is based upon the selected Report Interval. REPORT START TIME Type “2” (in the reporting setup menu) and <cr> to change the report start time. The module will respond: REPORT START TIME Reporting Start Time HH:MM Current Date04/28/00 and Time MM/DD/YY HH:MM:SS Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:

This menu shows the current Reporting Start Time, Current Date04/28/00 and Time as reported by the base unit's time-of day clock when the reporting start time entry was selected, and prompts you to enter the desired Report Start Time. Reporting can be delayed up to 24 hours from the current time.

93

Page 106

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

Enter the desired Report Start Time. For example, suppose the Current Time is 9:20:30 and the Reporting Start Time is set to 10:45. After you exit the Configuration Main Menu, the V79 PDI-1 will start reporting data messages at 10:45 at the programmed Sampling Setup. If the M Series loses power, reporting resumes the next time the designated Report Start Time is observed by the time-of day clock. IMPORTANT: The Current Date04/28/00 and Time is not updated during data entry. You must consider any delays from the time you enter the Report Start Time until you exit the Configuration Main Menu. Be sure to set the Report Start Time far enough ahead of the current time to complete all configurations and exit configuration mode. NOTE: When using Schedule Reporting Method and the V79 PDI-1 is initially reporting, if you enter into the menu-driven mode of configuration and exit, the V79 PDI-1 will not resume reporting data messages until the programmed Report Start Time elapses. You may program the CRM-1 without disrupting data message reporting by using dynamic configuration. REPORT INTERVAL Type “3” (in the reporting setup menu) and <cr> to change the reporting interval. The module will respond: REPORT INTERVAL Report Interval

HH:MM

Enter Hours (0-24) <cr>, or X to Exit: Enter Minutes (0-59) <cr>, or X to Exit:

Enter the desired Report Interval. The Report Interval can range from 1 minute to 24 hours. Once the Report Start Time elapses, the V79 PDI-1 will report all buffered data messages to the designated host module until the buffer is empty. The V79 PDI1 will continue to transmit all buffered data messages every time the Report Interval expires. For example, if the Report Start Time is 12:00 and the Report Interval is 1:00 (1 hour), the V79 PDI-1 will report all messages in its buffer every hour on the hour starting at 12:00. HOST ADDRESS Type “4” (in the reporting setup menu) and <cr> to change the host address. The module will respond: HOST ADDRESS Host Address

94

1:1,1

Page 107

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Enter Unit Number (1-32) <cr>, or X to EXIT: Enter Module Number (1-16) <cr>, or X to EXIT: Enter Port Number (1-4) <cr>, or X to EXIT:

Enter the appropriate Host Address. This consists of the Unit Number (1 to 32), Module Number (1 to 16), and Port Number (1 to 4) where the designated host module is located. Each entry should be followed by <cr>. If there is a single M Series unit in service, the Host Address would typically be Unit 1, Module 1, Port 1. NOTE: The Host Address must be supplied to direct self-reporting data messages to the desired destination. If the Host Address is incorrect, selfreporting data messages will be misdirected or lost. TIME TAG Type “5” (in the reporting setup menu) and <cr> to enable or disable the time tag. The module will respond: ENABLE / DISABLE TIME TAGGING Time Tagging

DISABLED

Enable Disable Exit

1 2 X

Enter Selection:

With time tag enabled, a MM/DD/YY HH/MM/SS entry is appended to all samples, where MM is the month, DD is the day, YY is the year, HH is the hour, MM is the minute, and SS is the second according to the base unit's time-of-day clock. TERMINATING CHARACTER(S) Type “6” (in the reporting setup menu) and <cr> to change the terminating character(s). The module will respond: ENTER TERMINATING CHARACTER Terminating Character(s) 0D0A Enter 1 or 2 Terminating Characters in Hex Format (i.e. 0D0A for CR+LF) <cr>, or X to Exit:

Type the hexadecimal representation of the desired terminating character(s). For example, <cr> would be represented by 0D Hex.

95

Page 108

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

NOTE: Only ASCII characters A-F and 0-9 are acceptable.

DYNAMIC CONFIGURATION Type “5” (in the configuration main menu) and <cr> to enable or disable the dynamic configuration capability. The module will respond: DYNAMIC CONFIGURATION COMMANDS Dynamic Configuration Commands DISABLED Enable Disable Exit

1 2 X

Enter Selection:

Dynamic configuration mode allows the V79 PDI-1 to be programmed by downloading dynamic (on-the-fly) commands. EXIT Type “X” (in the relay operating setup menu) and <cr> to exit the configuration mode. The module will respond: Save Changes as Defaults? (Y/N)

If you reply (Y), the settings are saved as the permanent power-up defaults. That is, if the M16/M8 loses power for any reason, the settings saved as defaults become the power-up settings. If you reply (N), your selections are saved as current (temporary) operating settings, but are lost upon power-down. The most recent menu selections, saved as defaults, are restored as the current operating parameters when power is reapplied. If you reply (Y), the V79 PDI-1 will respond with: Saving Configuration as Defaults... Configuration complete

DYNAMIC CONFIGURATION PROCEDURE AND COMMANDS V79 PDI-1 dynamic configuration commands are issued through a host module, the service port, or the service modem (config ports). The V79 PDI-1 will recognize dynamic configuration commands only when dynamic configuration is enabled. Use the following procedure to send dynamic configuration commands to the V79 PDI-1:

96

Page 109

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

1.

Select the V79 PDI-1 from a config port by sending a select sequence which consists of the port select code ($BT - default), the appropriate unit number followed by a colon (01: to 30: - for cascaded units only), the desired module number (2 to 16), and a terminating character for <cr> (0D Hex). For example, to select a V79 PDI-1 Module installed as Module 15 of a non-cascaded unit using the default port select code, send $BT15<cr>.

2.

Once the V79 PDI-1 is selected, it enters Command Mode and allows you to send dynamic configuration commands. The V79 PDI-1 configuration commands begin with two capital letters designating the specific command and are terminated with <cr>. Most configuration commands require a number between the command letters and <cr>. This number represents the desired configuration parameter.

3.

After you have sent the desired configuration command(s) to the V79 PDI-1 module, you may disconnect by sending $BT<cr>. You may disconnect from the V79 PDI-1 and select a different module or the base unit by sending $BTn<cr>.

NOTE: Multiple configuration commands may be sent while the V79 PDI1 is in command mode. Each command should be terminated with <cr>. For example: RM1<cr>TT2<cr> DEBOUNCE DELAY COMMAND The Debounce Delay (DB) command programs the PDI Debounce Delay time. The Debounce Delay command has the following format: DBn<cr> where n = 0 to 65535 milliseconds. REPORTING METHOD COMMAND The Reporting Method (RM) command programs the PDI Reporting Method. The Reporting Method command has the following format: RMn<cr> where n = 1 to 3. 1 = Command, 2 = Immediate and 3 = Schedule.

97

Page 110

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

TIME TAG COMMAND The Time Tag (TT) command is used to enable or disable time tagging. The Time Tag command has the following format: TTn where n = 1 or 2. 1 = enable and 2 = disable.

V93A HOST MODULE CONFIGURATION Configuration changes for the V93A Host Module are made through the service port or the service modem. To access the configuration mode of the module, use the procedures on page 44. CONFIGURATION MAIN MENU With $CONFIG input the V93A host module installed as Module X will respond with an identification block and a menu of the available configuration options similar to the following: Status Serial Port Configuration Port Device Name Port Select Code Attention Character Disconnect Timeguard Login Password Local Modem Setup Exit Enter Request :

1 2 3 4 5 6 7 8 X

STATUS Type “1” (in the configuration main menu) and <cr> to display the module status. The module will respond: Installed Modules : 1,2 Port Select Code is $BT Attention Character is ; Disconnect Time Guard10:28 AM is

98

Disabled