Page 51

M SERIES DAC CABLING ____________________________________________________________________________

Figure 1: PC, PS/2 Computer/Terminal Adapter BayTech Part No. 9FRJ45PC-3 Figure 2 shows the required adapter for a PC or terminal with a DB-25 connector. Use a crossed RJ-45 cable to connect these adapters to the EIA-232 port.

Figure 2: PC, PS/2 Computer/Terminal Adapter BayTech Part No. 25FRJ45PC-3 IMPORTANT: When modular connectors are used as shown in Figures 1 - 2 above with RJ-45 connectors, crossed RJ-45 cables are required. See the cable diagram that follows.

MODEM CONNECTION Connect the phone line to the RJ-11 connector on the V93A with a RJ-11 cable.

39

Page 52

M SERIES DAC INSTALLATION ____________________________________________________________________________

INSTALLATION UNPACKING Compare the unit and serial number of the equipment you received to the packing slip located on the outside of the box. Log this information on the sheet on page 186. Inspect equipment carefully for damage that may have occurred in shipment. If there is damage to the equipment or if materials are missing, contact BayTech technical support at 228-467-8231 or call toll free inside the United States at 800-523-2702. At a minimum, you should receive the following: a.

The M Series unit.

b.

This manual with any applicable addendum’s.

c.

Power Supply.

d.

1 ea. DE-9 (9 pin) PC com port adapter -- 9FRJ45PC-1.

e.

1 ea. RJ-45 cross over cable -- RJ08X007.

f.

1 ea. RJ-11 telco cable -- RJ04X007 (RPC-2 MD01 & RPC-2 RDR).

g.

1 ea. external modem adapter -- 25MRJ45MD-8 (RPC-2 RDR). NOTE: Keep the shipping container and packing material in the event future shipment is required.

PREPARING THE INSTALLATION SITE The installation area should be clean and free of extreme temperatures and humidity. Allow sufficient space behind the M Series unit for cabling and receptacle connections. POWER CAUTION: This unit is intended for indoor use only. Do not install near water or expose this unit to moisture. To prevent heat buildup, do not coil the power cord when in use. Do not use extension cords. Do not attempt to make any internal changes to the power source. Do not attempt to modify any portion or component of an RPC Series Unit unless specifically directed to. BayTech must perform any internal operations. 40

Page 53

M SERIES DAC INSTALLATION ____________________________________________________________________________

CAUTION: High-voltage surges and spikes can damage this equipment. To protect from such power surges and spikes, this unit must have a good earth ground. There is an earth ground connection next to the power input. CAUTION: Before removing or replacing any cables or power cords, turn off main power switch located on the M Series Unit. Communication to the unit will be disrupted while power is off. CAUTION: Do not exceed the AC current rating for the selected model. CAUTION: Although the power switch is turned OFF, the unit is not totally isolated from the power supply. In order to be absolutely removed from the power supply, the power cord must be unplugged from the unit. CAUTION: For PERMANENTLY CONNECTED EQUIPMENT, a readily accessible disconnect device shall be incorporated in the fixed wiring. For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and easily accessible. CIRCUIT BREAKER (In which units is this installed?) In the case of power overload, the circuit breaker automatically trips. Determine the cause of the tripped circuit breaker, correct the problem then reset the circuit breaker by depressing the circuit breaker switch. MODULE INSTALLATION Some of the modules that can be installed in the M Series include the following:

Part No.

Description

Connector Type

V71

Host module: EIA-232/EIA-422/current loop interface

DB-25 & RJ-45

V72 & V72TP

Host module: 10 BASE-T

BNC & RJ-45

V74

I/O module: 4 EIA-232 serial ports

RJ-45

V75

I/O module: 4 EIA-422/232 serial ports

RJ-45

V87

I/O module: 4 EIA-485/422 serial ports

RJ-45

V77 ADM-1

I/O module: 8 or 16 analog-to-digital channels

DB-25

V78 CRM-1

I/O module: 8 control relay channels

DB-25

V79 PDI-1

I/O module: 16 switch closure channels

DC-37

Ethernet (IEEE 802.3), 10BASE2 &

41

Page 54

M SERIES DAC INSTALLATION ____________________________________________________________________________ V80 PDI-2

I/O module: 16 optically isolated channels

DC-37

V82 PCM-1

Programmable Control module

Internal

V83 ECM-1

I/O module: 12 event counter channels

DC-37

V84 ADR-1

I/O module: 6 analog-to-digital channels, 6 switch closure channels, and 4 relay channels

HDL-44 DA-15

V89

Cascade module

BNC

V93A

Host module: V.32bis modem

RJ-11

M03*

Memory module: Expandable up to 16MB

N/A

* - The M03 memory module occupies one module slot thereby reducing the maximum number of host or I/O modules the can be installed by one

IMPORTANT: The first module slot (Module 1) of a M8 or M16 with a LCD display must be occupied by a host module. You will need a straight-slot screwdriver to perform the installation. 1.

IMPORTANT: Remove power from the unit by depressing the power switch on the front of the unit to OFF and also remove the power cord from the socket.

2.

Determine which module slot the module will install into. Modules are typically installed in sequence from left to right (facing rear of unit). The module slots are labeled on the top panel as "1", "2", ..., "16". If you need to upgrade the memory on the M03 memory module, please refer to Appendix B.4 before installing the module into the base unit.

3.

Remove the flat aluminum plate covering the slot into which the new module will be installed by loosening the 2 straight slot screws and then removing the plate from the rear panel. Save the aluminum plate in the event you have to remove the module in the future.

4.

Install the new module by sliding the horizontal card edges along the grooves inside the module slot. Each module has a card-edge connector that fits into a receptacle inside the base unit. Apply a moderate amount of pressure to the connector board of the module until you feel the card edge connector slip into the receptacle inside. You will not be able to mount the back plate of the module to the chassis if the module is not installed all the way.

5.

Mount the back plate of the module to the M Series chassis by tightening the 2 straight slot screws on the back plate.

42

Page 55

M SERIES DAC INSTALLATION ____________________________________________________________________________

6.

Apply power to the unit by plugging in the power cord and depressing the power switch on the front of the unit to ON.

43

Page 56

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

BASE UNIT AND MODULE CONFIGURATION BASE UNIT CONFIGURATION The base unit can be configured from the service port, the service modem, or a host control module. NOTE: Once the date has been programmed, the base unit will automatically adjust for months having 28, 29, 30, or 31 days for all years up to 2087. The base unit also tracks the correct day of the week automatically. HOST MODULE, SERVICE PORT, AND SERVICE MODEM CONFIGURATION (CONFIGURATION PORTS) To access configuration mode of the base unit from one of the configuration ports, use one of the following procedures. NOTE: The configuration ports will not respond to commands for approximately 15 seconds after the unit is powered up or reset. HOST MODULE ACCESS 1.

Connect a terminal to the host module and access the base unit configuration menu using either the menu mode: a)

Select configuration mode by typing “C” followed by <cr> at the main prompt ;

b)

and type the number of of the base unit (varies with number of module slots avaialable), followed by <cr>.

or the dynamic configuration mode.

a) NOTE:

Substitute module number (1-16) for base unit number (0) to configure other modules.

b)

44

Connect to the base unit by sending the port select code ($BT - default), 0, and <cr>.

Access configuration mode by sending $CONFIG<cr>. For example, if using the default port select code, send $BT0<cr>$CONFIG<cr> to enter into configuration mode

Page 57

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ for the base unit. No characters should be typed between $BT0<cr> and $CONFIG<cr>. To access the configuration mode of the base unit from the service port or service modem, use the following procedure: SERVICE PORT OR SERVICE MODEM ACCESS 1.

If configuring from the service port, connect a terminal to the EIA232 service port and configure the terminal's serial parameters to 9600 baud rate, 8 word size, 1 stop bit, and no parity. If configuring from the service modem, establish a connection between the remote terminal and service modem by dialing into the service modem. Once the unit is powered on, the following message will be sent out of the service port:

Bay Technical Associates Service Port Firmware Revision 4.XX

This same message will be sent to the remote modem once a connection is established with the service modem. The service modem has priority over the EIA-232 service port. When a connection is established between a remote modem and the service modem, the following message will be sent out of the EIA-232 service port: Incoming call Service port access locked out

A terminal connected to the EIA-232 service port is not allowed access to the M Series unit while the service modem has a connection with a remote modem. If a user connected to the EIA232 service port is currently communicating with the M Series unit and a remote user attempts to access configuration mode through the service modem, the remote user is not allowed access to the M Series unit. 2.

Place the base unit or desired module into command mode by sending $BT0n<cr>. (Use $BAYTECHn<cr> with M4 and M8 DAC units).

45

Page 58

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

NOTE:

Substitute module number (1-16) for base unit number (0) to configure other modules.

3.

Access configuration mode by sending $CONFIG<cr>. No characters should be typed between $BT0<cr> and $CONFIG<cr>. (Use $BAYTECH0<cr> on M4 and M8 DAC.)

Once you access configuration mode (for the base unit) from a host communications module, the service port, or the service modem, the following menu will appear on the terminal screen: Control Board System Menu Bay Technical Associates Copyright 199X Unit Number 001 Set Date Set Time Set Unit Number Exit System Menu

1 2 3 X

Enter Request:

Enter the desired selection. The "X" selection (Exit System Menu) will return you to operations mode. Once you exit configuration mode, you should disconnect by sending $BT<cr>. (Use $BAYTECH<cr> when using M4 and M8 DAC). NOTE:

Other configuration screens will appear based on the module number accessed. Refer to the appropriate module type for the proper configuration of those modules.

SET DATE Type "1" from the menu above to receive the following prompt: Enter date <MM/DD/YY>:

Type the desired date. For example, to enter December 31, 1999, type 12/31/99. SET TIME Type "2" from the menu above to receive the following prompt: Enter time <HH:MM:SS>:

Type the desired time. For example, to enter 11:59:59, type 11:59:59.

46

Page 59

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________

SET UNIT NUMBER Type "3" from the menu above to receive the following prompt: Enter unit (1-30):

Type the desired Unit Number. BASE UNIT DYNAMIC CONFIGURATION COMMANDS You can configure the date and time for the base unit from a host communications module by sending the "ST" (Set Time) dynamic configuration command. The host communications module must first select base unit prior to sending the "ST" command. This is done by sending the port select code, "0", and <cr>. The format of the "ST" command is as follows: ST HH:MM:SS,MM/DD/YY<cr>

HH is the desired hour, the first MM is the desired minute, SS is the desired second, the second MM is the desired month, DD is the desired day, YY is the desired year. For example; 11:59:59 on December 31, 1999 equates to: $BT0<cr>ST 11:59:59,12/31/99<cr>

V71 HOST MODULE CONFIGURATION V71 MAIN MENU CONFIGURATION Configuration changes for the V71 host module are made through one of the configuration ports. To access the configuration mode for the V71, use one of the procedures on page 44. With $CONFIG input the V71 host module installed as Module X will respond with an identification block and a menu of the available configuration options similar to the following: Copyright (c) Bay Technical Associates, 199X DAC V71 Rev. X.XX This Module is 1 1) Status 2) Port Select Code 3) Serial Port Configuration X) Exit Configuration

47

Page 60

M SERIES DAC BASE UNIT AND MODULE CONFIGURATION ____________________________________________________________________________ Enter Request :

NOTE: This menu shows the V71 installed as Module 1. A line showing the amount of memory is displayed as the third line in the header if an M03 memory module is installed. NOTE: Menu selections are case sensitive. keyboard be in the CAPS LOCK position.

It is recommended your

STATUS Type “1” and <cr> to review the status of the V71 module. The V71 will respond: Port

Baud Word Rate Size 1 9600 8 Port Select Code is:$BT

Stop Bits 1

Parity None

Xon / Xoff Xmit Recv Off Off

Line Interface EIA-232

Unit Number is : 1 Strike any key to continue Copyright (c) Bay Technical Associates, 199X DAC V71 Rev. X.XX This Module is 1 1) Status 2) Port Select Code 3) Serial Port Configuration X) Exit Configuration Enter Request :

You can now make whatever changes are necessary by responding to the above menu. The "X" (Exit Configuration) will return you to the operations mode. PORT SELECT CODE Type “2” and <cr> to enter the port select code menu. The V71 will respond:

48