Communicating with PanelView Terminals on a DeviceNet Network Introduction
This application describes how to connect and configure communications for the DeviceNet versions of the PanelView 900 terminals. This document provides supplemental information for the PanelBuilder Software User Manual (Publication No. 2711-6.0).
Hardware Requirements
The hardware items required for this application are: • 2755-SN3, -SN5 or -SN8 AdaptaScan Bar Code Reader • 2755-NB40 or -NB41 Wiring Base • 2755-PW46 or -PW47 Power Supply (if not power by DeviceNet) • 2755-NC43 or -NC48 Configuration Cable • DeviceNet trunk cable • 2711-K9C10, -T9C10, -K9A10, or -T9A10 PanelView 900 terminal • 1747-L532, -L541, -L542, or -L543 SLC Processor or 1785 PLC-5 processor and appropriate chassis • 1747-SDN Scanner Module (v2.05 firmware or later) or 1771-SDN Scanner Module (v3.04 firmware or later) • Computer running Windows 3.1 (or later) or Windows 95 • 9-to-25 Pin Adapter (for Computer with 25-pin COM port)
Software Requirements
The software requirements for this application are: • 2755-ASN AdaptaScan Offline Programming Software (v8.0 or later) • software • 6200 Series Programming Software or SLC Advanced Programming Software • 1787-MGR DeviceNet Manager Software (v3.0 or later)
Publication 2755-6.8
Page 324
17–2
Communicating with PanelView 900t Terminals on a DeviceNet Network
Related Publications
Related publications include: Publication
Description
2755-837
AdaptaScan Bar Code Readers User Manual
2755-838
AdaptaScan Software User Manual
1787-6.5.3
DeviceNet Manager Software Manual
1747-6.5.2
1747-SDN DeviceNet Scanner Configuration Manual
2711-6.0
PanelBuilder Software User Manual
2711-6.1
PanelView Operator Terminals User Manual
In addition, you may want to refer to the SLC and PLC-5 Hardware and Software User Manuals.
DeviceNet PanelViewt Terminals
The table below lists the DeviceNet versions of the PanelView terminals. The differences in the terminals relate to: • display type (monochrome or color) • operator input (touch screen or keypad) The DeviceNet terminals have: • DeviceNet communication port • RS-232 printer/file transfer port In addition, each terminal is available with either AC or DC power. The characters L1 at the end of the catalog number designate a terminal with DC power (e.g., -T9A10L1).
Terminal Type
PV900
Publication 2755-6.8
Display Type Color
Operator Input
Monochrome n n n n
Touch
Keypad
DeviceNet
RS-232
Catalog Number n n n n n n n n n
2711-K9A10 2711-T9A10 2711-K9C10 2711-T9C10 n n n
Ports
Page 325
Communicating with PanelView Terminals on a DeviceNet Network
Typical DeviceNet Network
17–3
Shown below is a typical DeviceNet network with PanelView terminals installed on two of the network drops.
PLC-5 Controller SLC 5/04 or
DeviceNet Scanner Module (Catalog No. 1747-SDN)
DeviceNet Scanner Module (Catalog No. 1771-SDN)
DeviceNet Network
PanelView 900 2711-T9A10, -T9C10
PanelView 900 2711-K9A10, -K9C10
DeviceNet Port
DeviceNet Port
RS-232 Port Computer for developing PanelView applications
Serial Link
ÎÎ ÎÎ ÎÎ SM C
Smart Motor Controller RediSTATION
AdaptaScan Bar Code Reader
Drive
Publication 2755-6.8
Page 326
17–4
Communicating with PanelView Terminals on a DeviceNet Network
Making DeviceNet Connections
Use DeviceNet cable to connect a DeviceNet version of a PanelView terminal to a DeviceNet Network. Cable
Catalog No.
DeviceNet Cable, 164 ft (50m)
1485C-P1A50
DeviceNet Cable, 328 ft (100m)
1485C-P1A150
DeviceNet Cable, 492 ft (150m)
1485C-P1A300
Important: Refer to the DeviceNet Cable System Planning and Installation Manual (Publication No. 1485-6.7.1) for network layout and design information. PanelView 900 Terminal Catalog Number 2711-K9A10, -T9A10, K9C10, -T9C10
5
DeviceNet Terminal Block
1
5
Publication 2755-6.8
Terminal
1
DeviceNet Port
Signal
Function
Color
1
COM
Common
Black
2
CAN_L
Signal Low
Blue
3
SHIELD
Shield
Uninsulated
4
CAN_H
Signal High
White
5
VDC+
Power Supply
Red
Page 327
Communicating with PanelView Terminals on a DeviceNet Network
Making Serial Port Connections
17–5
Use the RS-232 serial port on the DeviceNet terminal to: • download/upload applications over a serial link • or to connect a printer Computer
PanelView 900 Terminal Catalog Number 2711-K9A10,-T9A10, K9C10, -T9C10
COMM 1 or 2
RS-232 Printer/ File Transfer Port
PanelView 900 Terminal Catalog Number 2711-K9A10, -K9C10
Available Cables 2711-NC13 5 m (16.4 ft) 2711-NC14 10 m (32.7 ft) 3 m (10 ft) 2706-NC13
9-pin female 1 Data Out (TXD) 2 Data In (RXD) 3 4 Signal Common 5 6 7 8 9
9-pin male 1 2 Data In (RXD) 3 Data Out (TXD) 4 5 Signal Common 6 7 8 9
9 Pin to 25 Pin Adapter (if required)
ÇÇ Printer
RS-232 Port
RS-232 Printer/ File Transfer Port
Publication 2755-6.8
Page 328
17–6
Communicating with PanelView Terminals on a DeviceNet Network
Modifying DeviceNet Settings from the Terminal
You can display or modify DeviceNet settings directly from the terminal. From the Configuration Mode menu of the terminal, select Serial Communication Setup. The screen below appears.
!
ATTENTION: Settings downloaded with a DeviceNet application have priority over terminal settings. DeviceNet settings take effect immediately after an application is downloaded.
63
2 Words
63
2 Words
500
XX.XX.XX
XXXXXXXX
PV900 Touch Screen shown Other displays are similar
Restart Terminal [F1] Resets the terminal. New Node Address [F2] Opens the numeric entry scratchpad. Enter the node address (0 - 63) of the PanelView terminal on the DeviceNet link and press the Enter key. A node address change takes effect on reset. Active Node Address Displays the current network operating address of the PanelView. New Baud [F3] Step through the available baud rates with each key press. The options are 125K, 250K and 500K (default is 125K). The selected baud rate takes effect after a reset. The maximum cable length is restricted at higher baud rates. Active Baud Displays the current baud rate setting of the PanelView. The baud rate is set to the value for New Baud on power up. Note: The active baud is the baud rate of the PanelView not the network. The PanelView is not automatically set to the network baud rate.
Publication 2755-6.8
Page 329
Communicating with PanelView Terminals on a DeviceNet Network
17–7
Bus-off Interrupt [F4] Specify what occurs when a CAN bus-off interrupt occurs on the DeviceNet network. The PanelView is not allowed network access when Hold in Reset is selected and a bus-off interrupt occurs. • Hold in Reset holds the PanelView and waits for communications to be reset or a reset of the terminal. • Reset and Continue Communications resets DeviceNet communications and attempts to re-establish the communications link. Interscan Delay [F5] Opens the numeric entry scratchpad. Provide a delay between scans of the Explicit-Client tags. Enter a value of 0 to 65535 milliseconds. This time delay is inserted between each full scan of the Explicit-Client tags in the current screen context. This value is originally set by the downloaded application file but may be changed by an operator. When changed, the new value takes effect immediately. Input Size Displays the number of words (from 0 to 64) that are sent by the PanelView in an I/O message. 0 is the default value which indicates that no input data is exchanged with the scanner. This value is set by the downloaded application. Output Size Displays the number of words (from 0 to 64) that are received by the PanelView in an I/O message. 0 is the default value which indicates that no output data is exchanged with the scanner. This value is set by the downloaded application. EXIT To return to the Configuration Mode menu, press the Exit button. COMM LED Pattern
Indicates
Solid Fill
Normal operating state
Blinking
No communications established
No Fill
Hardware failure
Publication 2755-6.8
Page 330
17–8
Communicating with PanelView Terminals on a DeviceNet Network
Setting up Communications using PanelBuilder
Setting up DeviceNet communications for an application includes: • selecting a DeviceNet terminal when creating the application. • configuring communication parameters for the terminal on the DeviceNet link.
Selecting a DeviceNet PanelView Terminal Select a DeviceNet terminal for a PanelView application from: • New Application dialog when creating a new application or • Terminal Setup dialog when converting the application created for another terminal. Any catalog number with 10 as the last number is a DeviceNet terminal.
The following PanelView terminals are available with a DeviceNet port. Catalog No. 2711-K9C10 2711-T9C10 2711-K9A10 2711-T9A10
PV Type PV900C PV900C PV900M PV900M
Color Color Mono Mono
Keypad Touch Keypad Touch
Indicates the RS-232 port is set for downloading applications.