The text of a manual · part 2 of 2
DS/DD Bar Code Decoder to 2760-RB/PLC-5 Application Note, pages 4 to 12
Pages 4 to 12 of 12: Running the Application; Back Cover
The original document is the PDF (80 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 2755-DD and Allen-Bradley 2755-DS
Page 4
4
Running the Application
The configuration screens for the 2760-RB and the 2755-DS/DD decoder should be entered exactly as shown in the following pages. Save them, and then restart the decoder. Figure 2 2755-DS/DD Host Communications Configuration Screen
Figure 3 2755-DS/DD Host Message Format Configuration Screen
Important: When configuring the 2760-RB module, first select “Main Menu Selection 90B” to reset the unit to factory defaults. Then configure screens 3, 21, and 11 in that order exactly as shown below.
2755-2.54 – September 1995
Page 5
5
Figure 4a 2760-RB Module Configuration Screens
2760–RB SERIES A REVISION J COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. –––––––––––––––––––––––––––––––––––––––––––––––––––– 1X – CONFIGURATION PARAMETERS 2X – IDENTIFICATION NUMBERS 3 – DEVICE PORT PROTOCOL NAMES 4DM – MATCH CODE ENTRIES 5I – DISCRETE BYTE INPUT ENTRIES 6 – THE DATA MATRIX ENTRIES 7 – THE PASS THROUGH ENTRIES 8 – NON–VOLATILE SCRATCH PAD AREA 9XF – RB MODULE FUNCTIONS AX – HARDWARE DIAGNOSTICS BX – SOFTWARE DIAGNOSTICS C – EXIT CONFIGURATION MODE WHERE X (0 TO 7) AND D (1 TO 3) ARE PORT NUMBERS WHICH ARE DEFINED BELOW : 0 – RB CMMND PRCSS 2 – SERIAL PORT 2 4 – CONFIG PORT 6 – I/O RACK SLT 1 1 – SERIAL PORT 1 3 – SERIAL PORT 3 5 – I/O RACK SLT 0 7 – RESERVED WHERE F (A TO E) ARE FUNCTIONS THAT RB CAN PERFORM WHICH ARE DEFINED BELOW : A – RESET B – SET DEFAULTS C – FLUSH D – INITIALIZE E – CLEAR DIAGS WHERE M (A TO T) AND I (A TO H) ARE ENTRY NUMBERS FOR THE SELECTION MADE ABOVE. ENTER A MAIN MENU SELECTION:
ENTER A MAIN MENU SELECTION: 3 PORT 1 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC1 DT , SERIES A , REVISION B (YES/NO) = YES. PORT 2 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC1 DT , SERIES A , REVISION B (YES/NO) = YES. PORT 3 = COPYRIGHT 1989 ALLEN–BRADLEY COMPANY, INC. 2760–SFC1 DT , SERIES A , REVISION B (YES/NO) = YES. EDIT THIS SELECTION (YES/NO) ?
2755-2.54 – September 1995
Page 6
6
Figure 4b 2760-RB Module Configuration Screens
ENTER A MAIN MENU SELECTION: 21 DUMB TERM. UNSPECIFIED PROTOCOL, 13fh (YES/NO) = YES. EDIT THIS SELECTION (YES/NO) ?
ENTER A MAIN MENU SELECTION: 11 MODEM CONTROL (ENABLE/DISABLE) = DISABLE. 9600 BITS PER SECOND (YES/NO) = YES. 8 BITS NO PARITY (YES/NO) = YES. XON/XOFF (ENABLE/DISABLE) = DISABLE. RS232 (YES/NO) = YES. RECEIVE MATRIXING (ENABLE/DISABLE) = DISABLE. BYTE SWAPPING (ENABLE/DISABLE) = ENABLE. BINARY DATA NO CONVERSIONS (YES/NO) = YES. HDR/TLR ON OUTPUT (ENABLE/DISABLE) = ENABLE. HEADER BYTE LENGTH (DEC 0...4) = 0. HEADER DATA[0] (HEX 0...ff) = 0. HEADER DATA[1] (HEX 0...ff) = 0. HEADER DATA[2] (HEX 0...ff) = 0. HEADER DATA[3] (HEX 0...ff) = 0. TRAILER BYTE LENGTH (DEC 0...4) = 2. TRAILER DATA[0] (HEX 0...ff) = a. TRAILER DATA[1] (HEX 0...ff) = d. TRAILER DATA[2] (HEX 0...ff) = 0. TRAILER DATA[3] (HEX 0...ff) = 0. MAX DATA BYTE LENGTH (DEC 0...124) = 0. MIN DATA BYTE LENGTH (DEC 0...124) = 0. CONTINUE THIS SELECTION (YES/NO) ?
2755-2.54 – September 1995
Page 7
7
Figure 5 Example PLC program for PLC-5, -15, -25, or 1771-ASB
Program Listing Report
PLC–5/10
3 August 1994 File 2_54FIG1
Page 1 Rung 2:0
Rung 2:0 USE THIS SAMPLE LOGIC WITH THE 5/10,15–25 PROCESSORS. THE RB MODULE CONTROLS THE ”BRR BIT” ADDRESS I:000/13. WHEN THE RB MODULE HAS DATA, IT WILL TOGGLE THE BRR BIT. | I:000 N7:0 N7:5 +BTR–––––––––––––––+ | +––] [–––]/[–––]/[–––––––––––––––––––––––––––+BLOCK TRNSFR READ +–(EN)–+ | 13 15 15 |Rack 00| | | |Group 0+–(DN) | | |Module 0| | | |Control Block N7:0+–(ER) | | |Data file N7:100| | | |Length 0| | | |Continuous N| | | +––––––––––––––––––+ | Rung 2:1 B3/0 IS ANY WRITE INITIATE BIT. IF THE BTW IS NOT USED, THIS RUNG CAN BE OMMITED ALONG WITH THE CONTROL ENABLE BIT ABOVE, N7:5/EN. THE ONLY WAY TO KNOW IF YOU HAVE SUCCESSFULLY COMPLETED A BTR OR BTW IS TO USE THE DONE BIT. THE BRR BIT IS AN UNRELIABLE INDICATOR OF READS. | B3 N7:0 N7:5 +BTW–––––––––––––––+ | +––] [–––]/[–––]/[–––––––––––––––––––––––––––+BLOCK TRNSFR WRITE+–(EN)–+ | 0 15 15 |Rack 00| | | |Group 0+–(DN) | | |Module 0| | | |Control Block N7:5+–(ER) | | |Data file N7:200| | | |Length 0| | | |Continuous N| | | +––––––––––––––––––+ | Rung 2:2 | | +––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––+ | |
2755-2.54 – September 1995
Page 8
8
Figure 6 Example PLC program for 2760-RB Revision H or above to PLC 5/20, -5/30, -5/40, or 5/50
Program Listing Report
PLC–5/30
3 August 1994 Page 1 File 2_54FIG2 Rung 2:0
Rung 2:0 | I:001 N7:5 N7:25 001 | +––]/[–––]/[–––]/[–––––––––––––––––––––––––––––––––––––––––––––––(IIN)–+ | 13 15 15 | Rung 2:1 USE THIS SAMPLE LOGIC IF YOU HAVE A SER A REVISION H OR ABOVE RB MODULE AND A NEW GENERATION 5/20–60 OR ABOVE PROCESSOR. THE IIN IS NEEDED TO FORCE A SCAN OF THE BRR BIT I:001/13. THIS DOES NOT APPLY TO REMOTE RACK APPLICATIONS, ONLY LOCAL USE. | I:001 N7:5 N7:25 +BTR––––––––––––––––––––+ | +––] [–––]/[–––]/[––––––––––––––––––––––+BLOCK TRNSFR READ +–(EN)–+ | 13 15 15 |Rack 00| | | |Group 1+–(DN) | | |Module 0| | | |Control Block N7:50+–(ER) | | |Data file N7:200| | | |Length 0| | | |Continuous N| | | +–––––––––––––––––––––––+ | Rung 2:2 THE BTR SHOULD COME BEFORE THE BTW. B3/0 CAN BE ANY WRITE INITIATE BIT. THE ONLY WAY TO KNOW YOUR INSTRUCTION IS COMPLETE AND SUCCESSFUL IS TO USE THE DONEBITS IN THE BTR AND BTW. | B3 N7:5 N7:25 +BTW––––––––––––––––––––+ | +––] [–––]/[–––]/[––––––––––––––––––––––+BLOCK TRNSFR WRITE +–(EN)–+ | 0 15 15 |Rack 00| | | |Group 1+–(DN) | | |Module 0| | | |Control Block N7:25+–(ER) | | |Data file N7:400| | | |Length 0| | | |Continuous N| | | +–––––––––––––––––––––––+ | Rung 2:3 | | +––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––+ | | NO MORE FILES
2755-2.54 – September 1995
Page 9
9
Figure 7 Cable diagrams 2760-RB Module (Configuration Port) 25-pin “D”, Male to
TX 2 RX 3
3 RX 2 TX 7 GND 4 – 5 jumper 6 – 20 jumper
GND 7
2760-RB Module (Configuration Port) 25-pin “D”, Male to
TX 2 RX 3 GND 7
2760-RB Module (Port 1) 25-pin “D”, Male
RX 2 TX 3 GND 7
Dumb Terminal (VT-100) 25-pin “D”, Female
3 RX 2 TX 7 GND to
TX 2 RX 3 GND 7
2755-DS/DD (Auxiliary Port) 25-pin “D”, Male
1784-T45 (Terminal Mode) 25-pin “D”, Female or 9-pin PC Com Port
2 RX 3 TX 5 GND 4 – 6 jumper 7 – 8 jumper
2755-DS/DD (Host Port) 25-pin “D”, Male
3 RX 2 TX 7 GND to
Dumb Terminal (VT-100) 25-pin “D”, Female
2 TX 3 RX 7 GND or 9-pin PC Com Port
3 TX 2 RX 5 GND 4 – 6 jumper 7 – 8 jumper
2755-2.54 – September 1995
Page 10
10
Notes:
2755-2.54 – September 1995
Page 11
11
Notes:
2755-2.54 – September 1995
Page 12
PLC and PLC-5 are registered trademarks of Allen-Bradley Co., Inc., a Rockwell International company Windows is a trademark of Microsoft Procomm is a registered trademark of Datastorm Technologies, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 2755-2.54 – September 1995
40062-319-01(A) Copyright 1995 Allen-Bradley Company, Inc. Printed in USA
1–1